Quantcast

TeSys D Contactor, 3P(3 NO), AC-3, <= 440V, 150A, 110VAC, 50/60 Hz Coil

TeSys D Contactor, 3P(3 NO), AC-3, <= 440V, 150A, 110VAC, 50/60 Hz Coil

TeSys D Contactor, 3P(3 NO), AC-3, <= 440V, 150A, 110VAC, 50/60 Hz Coil

Item Number: LC1D1506F7

Retail
$3,383.55
RRP (Inc. GST)

Product Dimensions

Width icon

Width120 mm

Height icon

Height158 mm

Depth icon

Depth136 mm

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys D

Range

TeSys

Product or component type

contactor

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

[Ue] rated operational voltage

  • power circuit: <= 1000 V AC 25...400 Hz
  • power circuit: <= 300 V DC
    • [Ie] rated operational current

    • 200 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
    • 150 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
      • Electrical durability

      • 0.85 Mcycles 150 A AC-3 at Ue <= 440 V
      • 1 Mcycles 200 A AC-1 at Ue <= 440 V
        • Mounting support

        • rail
        • plate
          • Standards

          • CSA C22.2 No 14
          • EN 60947-4-1
          • EN 60947-5-1
          • IEC 60947-4-1
          • IEC 60947-5-1
          • UL 508
            • Product certifications

            • RINA
            • BV
            • CSA
            • LROS (Lloyds register of shipping)
            • GOST
            • UL
            • GL
            • DNV
            • CCC
              • Connections - terminals

              • control circuit: lugs-ring terminals (external diameter: 8 mm)
              • power circuit: lugs-ring terminals (external diameter: 25 mm)
              • power circuit: bars 1 cable(s) - busbar cross section: 5 x 25 mm
                • Mechanical durability

                  8 Mcycles

                  Insulation resistance

                  > 10 MOhm for signalling circuit

                  IP degree of protection

                  IP20 front face conforming to IEC 60529

                  Ambient air temperature for operation

                • -40-60 °C
                • 60-70 °C with derating
                  • Ambient air temperature for storage

                    -60-80 °C

                    Height

                    158 mm

                    Width

                    120 mm

                    Depth

                    136 mm

                    Net weight

                    2.5 kg

                    REACh Regulation

                    Free of Substances of Very High Concern above the threshold

                    EU RoHS Directive

                    Compliant

                    Mercury free

                    Yes

                    RoHS exemption information

                    Yes

                    China RoHS Regulation

                    Product out of China RoHS scope. Substance declaration for your information

                    Environmental Disclosure

                    ENVPEP060301EN

                    Circularity Profile

                    ENVEOLI100405EN

                    California proposition 65

                    WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov

                    Others

                    Product name

                    TeSys D

                    Device short name

                    LC1D

                    Contactor application

                  • motor control
                  • resistive load
                    • Utilisation category

                    • AC-1
                    • AC-4
                    • AC-3
                      • Poles description

                        3P

                        Pole contact composition

                        3 NO

                        Motor power kW

                      • 40 kW at 220...230 V AC 50/60 Hz (AC-3)
                      • 75 kW at 380...400 V AC 50/60 Hz (AC-3)
                      • 80 kW at 415...440 V AC 50/60 Hz (AC-3)
                      • 90 kW at 500 V AC 50/60 Hz (AC-3)
                      • 100 kW at 660...690 V AC 50/60 Hz (AC-3)
                      • 75 kW at 1000 V AC 50/60 Hz (AC-3)
                      • 22 kW at 400 V AC 50/60 Hz (AC-4)
                        • Motor power hp

                        • 40 hp at 200/208 V AC 50/60 Hz for 3 phases motors
                        • 50 hp at 230/240 V AC 50/60 Hz for 3 phases motors
                        • 100 hp at 460/480 V AC 50/60 Hz for 3 phases motors
                        • 125 hp at 575/600 V AC 50/60 Hz for 3 phases motors
                          • Control circuit type

                            AC at 50/60 Hz

                            [Uc] control circuit voltage

                            110 V AC 50/60 Hz

                            Auxiliary contact composition

                            1 NO + 1 NC

                            [Uimp] rated impulse withstand voltage

                            8 kV conforming to IEC 60947

                            Overvoltage category

                            III

                            [Ith] conventional free air thermal current

                            200 A (at 60 °C) for power circuit

                            Irms rated making capacity

                          • 140 A AC for signalling circuit conforming to IEC 60947-5-1
                          • 250 A DC for signalling circuit conforming to IEC 60947-5-1
                          • 1660 A at 440 V for power circuit conforming to IEC 60947
                            • Rated breaking capacity

                              1400 A at 440 V for power circuit conforming to IEC 60947

                              [Icw] rated short-time withstand current

                            • 250 A 40 °C - 10 min for power circuit
                            • 580 A 40 °C - 1 min for power circuit
                            • 1200 A 40 °C - 10 s for power circuit
                            • 1400 A 40 °C - 1 s for power circuit
                            • 100 A - 1 s for signalling circuit
                            • 120 A - 500 ms for signalling circuit
                            • 140 A - 100 ms for signalling circuit
                              • Associated fuse rating

                              • 10 A gG for signalling circuit conforming to IEC 60947-5-1
                              • 315 A gG at <= 690 V coordination type 1 for power circuit
                              • 250 A gG at <= 690 V coordination type 2 for power circuit
                                • Average impedance

                                  0.6 mOhm - Ith 200 A 50 Hz for power circuit

                                  [Ui] rated insulation voltage

                                • power circuit: 600 V CSA certified
                                • power circuit: 600 V UL certified
                                • power circuit: 1000 V conforming to IEC 60947-4-1
                                • signalling circuit: 690 V conforming to IEC 60947-1
                                • signalling circuit: 600 V CSA certified
                                • signalling circuit: 600 V UL certified
                                  • Power dissipation per pole

                                  • 24 W AC-1
                                  • 13.5 W AC-3
                                    • Protective cover

                                      with

                                      Tightening torque

                                    • control circuit: 1.2 N.m - on lugs-ring terminals - with screwdriver flat Ø 6 mm M3.5
                                    • control circuit: 1.2 N.m - on lugs-ring terminals - with screwdriver Philips No 2 M3.5
                                    • power circuit: 12 N.m - on lugs-ring terminals hexagonal screw head 13 mm M8
                                    • power circuit: 12 N.m - on bars hexagonal screw head 13 mm M8
                                      • Operating time

                                      • 20...35 ms closing
                                      • 40...75 ms opening
                                        • Safety reliability level

                                        • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                                        • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                                          • Maximum operating rate

                                            1200 cyc/h 60 °C

                                            Coil technology

                                            built-in bidirectional peak limiting diode suppressor

                                            Control circuit voltage limits

                                          • 0.3...0.5 Uc (-40-70 °C):drop-out AC 50/60 Hz
                                          • 0.8...1.15 Uc (-40-55 °C):operational AC 50/60 Hz
                                          • 1...1.15 Uc (55-70 °C):operational AC 50/60 Hz
                                            • Inrush power in VA

                                            • 280-350 VA 60 Hz cos phi 0.9 (at 20 °C)
                                            • 280-350 VA 50 Hz cos phi 0.9 (at 20 °C)
                                              • Hold-in power consumption in VA

                                              • 2-18 VA 60 Hz cos phi 0.9 (at 20 °C)
                                              • 2-18 VA 50 Hz cos phi 0.9 (at 20 °C)
                                                • Heat dissipation

                                                  3-4.5 W at 50/60 Hz

                                                  Auxiliary contacts type

                                                • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                                                • type mirror contact 1 NC conforming to IEC 60947-4-1
                                                  • Signalling circuit frequency

                                                    25...400 Hz

                                                    Minimum switching current

                                                    5 mA for signalling circuit

                                                    Minimum switching voltage

                                                    17 V for signalling circuit

                                                    Non-overlap time

                                                  • 1.5 ms on de-energisation between NC and NO contact
                                                  • 1.5 ms on energisation between NC and NO contact
                                                    • Contact compatibility

                                                      M13

                                                      Compatibility code

                                                      LC1D

                                                      Protective treatment

                                                      TH conforming to IEC 60068-2-30

                                                      Pollution degree

                                                      3

                                                      Operating altitude

                                                      0...3000 m

                                                      Fire resistance

                                                      850 °C conforming to IEC 60695-2-1

                                                      Flame retardance

                                                      V1 conforming to UL 94

                                                      Mechanical robustness

                                                    • vibrations contactor open: 2 Gn, 5...300 Hz
                                                    • vibrations contactor closed: 4 Gn, 5...300 Hz
                                                    • shocks contactor closed: 15 Gn for 11 ms
                                                    • shocks contactor open: 6 Gn for 11 ms
                                                      • Unit Type of Package 1

                                                        PCE

                                                        Number of Units in Package 1

                                                        1

                                                        Package 1 Weight

                                                        2.214 kg

                                                        Package 1 Height

                                                        17.5 cm

                                                        Package 1 width

                                                        19 cm

                                                        Package 1 Length

                                                        21.5 cm

                                                        Unit Type of Package 2

                                                        P06

                                                        Number of Units in Package 2

                                                        27

                                                        Package 2 Weight

                                                        72.78 kg

                                                        Package 2 Height

                                                        80 cm

                                                        Package 2 width

                                                        80 cm

                                                        Package 2 Length

                                                        60 cm

                                                        WEEE

                                                        The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

                                                        PVC free

                                                        Yes
                                                        Show all specifications

                                                        Documents & downloads

                                                        hide show
                                                        Filter items
                                                        • All

                                                        • CAD Files and Packs

                                                        • Product Brochures

                                                        • Technical Data Catalogues

                                                        • Product Environmental

                                                        • End of Life Manual

                                                        • Installation Instruction

                                                        • Data Bulletin

                                                        • Certificates (MSDS)

                                                        • Declaration of Conformity

                                                        Frequently Asked Questions

                                                        hide show

                                                        What is the power terminal lug data for the LC1D40, LC1D50, LC1D65, LP1D40, LP1D50, and LP1D65 contactor?

                                                        Issue:
                                                        Identifying power terminal lug data for the D2 style contactors

                                                        Product Line:
                                                        IEC Contactors and Starters

                                                        Environment:
                                                        Tesys D line contactors

                                                        Cause:
                                                        Power terminal lug data required

                                                        Resolution:
                                                        For contactors with screw clamp terminals:
                                                        stranded cable w/o cable end : One #10-3 AWG or Two #10-4 AWG per terminal.
                                                        stranded cable w/cable end: One #10-4 AWG or Two #12-2 AWG per terminal.
                                                        solid cable: One #10-3 AWG or Two #10-6 AWG per terminal.

                                                        What is the power terminal lug data for the LC1D09, LC1DT20, LC1D12, and LC1DT25 contactor?

                                                        Issue:
                                                        Power terminal lug data required for the 9 and 12 amp rated Tesys D contactors

                                                        Product Line:
                                                        IEC Contactors and Starters

                                                        Environment:
                                                        Tesys D Contactors

                                                        Resolution:
                                                        For contactors with screw clamp terminals:
                                                        stranded cable w/o cable end : One or Two #18-10 AWG per terminal.
                                                        stranded cable w/cable end: One or Two #18-10 AWG per terminal.
                                                        solid cable: One or Two #18-8 AWG per terminal.

                                                        What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

                                                        Issue:
                                                        Identifying maximum voltage of an LC1D contactor

                                                        Product Line:
                                                        TeSys D Contactors

                                                        Environment:
                                                        IEC contactors and starters used in North America

                                                        Cause:
                                                        n/a

                                                        Resolution:
                                                        IThe maximum voltage per UL and CSA is 600VAC. 
                                                         

                                                        What is the coil tolerance for Tesys D-line contactors LC1D09 - LC1D38?

                                                        Issue:
                                                        LC1D09 - LC1D38 Coil tolerance

                                                        Product Line:
                                                        Contactors and Starters, IEC

                                                        Environment:
                                                        Tesys D Contactors

                                                        Cause:
                                                        Needs the coil tolerance for Tesys D-line contactors LC1D09 - LC1D38.

                                                        Resolution:
                                                        AC single frequency coils: 50Hz and 60 Hz (-20% / +10%);
                                                        AC dual frequency coils: 50Hz (-20% / +10%) ; 60Hz (-15% / +10%)
                                                        DC standard coil for LC1D09 -D38 and LC1DT20 to DT40: (-30% / +25%)
                                                        DC standard coil for LP1D12 and D25: (-20% / +10%)
                                                        DC wide range coil for LP1D12 and D25 : (-30% to +25%)

                                                        What is the replacement for LC1D25004?

                                                        LC1D25004 replaced by LC1DT40.

                                                         

                                                         

                                                        What is the replacement coil part number for the LC*D09 through LC*D32 and LC*DT20 through LC*DT40 TeSys contactors?

                                                        Issue:
                                                        Identifying replacement coils for tesys D non-reversing and reversing conactors

                                                        Product Line:
                                                        IEC Contactors and Starters

                                                        Environment:
                                                        Products sold and used in the United States

                                                        Cause:
                                                        Replacement coil is needed

                                                        Resolution:
                                                        DC replacement coils are not available.
                                                        AC Coils are 50/60 hertz for voltages as listed below:

                                                        Volts - Part Number
                                                        12 ____ LXD1J7
                                                        21 ____ LXD1Z7
                                                        24 ____ LXD1B7
                                                        32 ____ LXD1C7
                                                        36 ____ LXD1CC7
                                                        42 ____ LXD1D7
                                                        48 ____ LXD1E7
                                                        60 ____ LXD1EE7
                                                        100 ___ LXD1K7 ( never brought to North America )
                                                        110 ___ LXD1F7
                                                        115 ___ LXD1FE7
                                                        120 ___ LXD1G7
                                                        127 ___ LXD1FC7
                                                        200 ___ LXD1L7
                                                        208 ___ LXD1LE7
                                                        220 ___ LXD1M7
                                                        230 ___ LXD1P7
                                                        240 ___ LXD1U7
                                                        277 ___ LXD1W7
                                                        380 ___ LXD1Q7
                                                        400 ___ LXD1V7
                                                        415 ___ LXD1N7
                                                        440 ___ LXD1R7
                                                        480 ___ LXD1T7
                                                        575 ___ LXD1SC7
                                                        600 ___ LXD1X7
                                                        690 ___ LXD1Y7


                                                        Note: A contactor with an AC coil can be changed to a different AC voltage coil, IE you can take an LC1D09 with a 120VAC coil and put a 24VAC coil in it instead. An AC device cannot be switched to a DC coil, and a DC device cannot be switches to an AC coil. 