Specifications

hide show
Range of product
TeSys D
Range
TeSys
Product or component type
auxiliary contact block
Range compatibility
  • TeSys LC1D
  • TeSys CAD
    • Auxiliary contacts operation
      instantaneous
      Pole contact composition
      1 NO + 1 NC
      Shielding continuity terminal
      without
      Connections - terminals
    • screw clamp terminals 1 cable(s) 1-2.5 mm²flexible with cable end
    • screw clamp terminals 1 cable(s) 1-2.5 mm²flexible without cable end
    • screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
    • screw clamp terminals 2 cable(s) 1-2.5 mm²flexible without cable end
    • screw clamp terminals 1 cable(s) 1-2.5 mm²solid
    • screw clamp terminals 2 cable(s) 1-2.5 mm²solid
      • Mounting location
        side
        [Ui] rated insulation voltage
      • 690 V conforming to IEC 60947-5-1
      • 600 V - certifications CSA
      • 600 V - certifications UL
        • [Ue] rated operational voltage
          690 V AC 25...400 Hz
          [Ith] conventional free air thermal current
          10 A (at 60 °C)
          Irms rated making capacity
        • 140 A AC conforming to IEC 60947-5-1
        • 250 A DC conforming to IEC 60947-5-1
          • Permissible short-time rating
          • 100 A 60 °C 1 s
          • 120 A 60 °C 500 ms
          • 140 A 60 °C 100 ms
            • Protection type
              gG fuse 10 A
              Mechanical durability
              30 Mcycles
              Minimum switching current
              5 mA
              Minimum switching voltage
              17 V
              Non-overlap time
            • 1.5 ms on de-energisation no overlap between NC and NO contact
            • 1.5 ms on energisation no overlap between NC and NO contact
              • Insulation resistance
                > 10 MOhm
                Tightening torque
                1.7 N.m
                Width
                12.5 mm
                Environmental characteristic
                normal environment
                Standards
              • EN/IEC 60947-5-1
              • UL 60947-5-1
              • CSA C22.2 No 60947-5-1
              • GB/T 14048.5
                • Specific use
                  general
                  Product certifications
                • IECEE CB Scheme
                • UL
                • CSA
                • CCC
                • EAC
                  • IP degree of protection
                    IP20 conforming to IEC 60529
                    Protective treatment
                    TH conforming to IEC 60068
                    Ambient air temperature for operation
                    -5-60 °C
                    Ambient air temperature for storage
                    -60-80 °C
                    Operating altitude
                    3000 m
                    Sustainable offer status
                    Green Premium product
                    REACh Regulation
                    Free of Substances of Very High Concern above the threshold
                    REACh free of SVHC
                    Yes
                    EU RoHS Directive
                    Compliant
                    Toxic heavy metal free
                    Yes
                    Mercury free
                    Yes
                    RoHS exemption information
                    Yes
                    China RoHS Regulation
                    X
                    Environmental Disclosure
                    ENVPEP110701EN
                    WEEE
                    The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                    Warranty
                    18 months

                    Documents & downloads

                    hide show
                    Filter items
                    • All

                    • CAD Files and Packs

                    • Product Brochures

                    • Technical Data Catalogues

                    • Installation Instruction

                    • Certificates (MSDS)

                    • Declaration of Conformity

                    Frequently Asked Questions

                    hide show

                    Is it possible to add side instantaneous auxiliary contacts blocks to the TeSys D DC coil contactors and relays?

                    No, with the TeSYS D range, the DC coil contactors (both standard and low consumption) only allow front mountable auxiliaries.
                    The part numbers LAD8N11, LAD8N20 and LAD8N02 will fit only the contactors with AC coils.

                    What is the replacement AC coil for CAD32 and CAD50 relay?

                    Issue:
                    AC coil replacement for CAD32 and CAD50

                    Product Line:
                    Relays

                    Environment:
                    Tesys CAD Control Relays

                    Cause:
                    Product selection

                    Resolution:
                    Volt = coil part number
                    12 = LXD1J7
                    21 = LXD1Z7
                    24 = LXD1B7
                    32 = LXD1C7
                    36 = LXD1CC7
                    42 = LXD1D7
                    48 = LXD1E7
                    60 = LXD1EE7
                    100 = LXD1K7
                    110 = LXD1F7
                    115 = LXD1FE7
                    120 = LXD1G7
                    127 = LXD1FC7
                    200 = LXD1L7
                    208 = LXD1LL7
                    220/230 = LXD1M7
                    230 595 21 LXD1P7
                    230/240 = LXD1U7
                    277 781 30 LXD1W7
                    380/400 = LXD1Q7
                    400 = LXD1V7
                    415 = LXD1N7
                    440 = LXD1R7
                    480 = LXD1T7
                    600 = LXD1X7
                    690 = LXD1Y7

                     

                    What is the part code for a 630A Contactor with 230V coil

                     The part codes you need LC1F630 + LX1FL220 + LADN11

                    In regards to LAD5C11 LAD5C31 LAD5C12 LAD5C32 What is the maximum kW range that TeSys SoLink can be used with motor starter combination?

                    TeSys SoLink is the connection module to connect GV2/GV3 motor circuit breakers to associated contactors and can be used with GV2 / GV3 breakers up to 30kW.
                    For more information please visit the Link provided
                    https://www.schneider-electric.com.au/australia/en/products-services/offer-updates/news-viewer.page?c_filepath=/templatedata/Content/News/data/en/local/automation_control/general_information/2014/10/20141024_tesys_solink_integration_system.xml

                    In regards to LAD5C11 LAD5C31 LAD5C12 LAD5C32 SoLink What is the maximum number of motor starters that can be connected and controlled with each logic controller?

                    Each TM3 I/O module is able to monitor and control up to 4 motor starters and up to 56 motor starters can be connected to logic controller.
                    For more information aboput this range please Visit the Schneider website on the link provided
                    https://www.schneider-electric.com.au/australia/en/products-services/offer-updates/news-viewer.page?c_filepath=/templatedata/Content/News/data/en/local/automation_control/general_information/2014/10/20141024_tesys_solink_integration_system.xml

                    In regards to LAD5C11 LAD5C31 LAD5C12 LAD5C32 SoLink , Can TeSys SoLink be used with AC control supply?

                    TeSys SoLink is suitable for 24VDC control supply; the TM3 I/O module provides the 24V DC control voltage to the motor starter.
                    For more information on this range please visit the Schneider electric web site on the link provided
                    https://www.schneider-electric.com.au/australia/en/products-services/offer-updates/news-viewer.page?c_filepath=/templatedata/Content/News/data/en/local/automation_control/general_information/2014/10/20141024_tesys_solink_integration_system.xml

                    Can the old D-line front mount attachments fit on the new CAD relays?

                    Issue: 
                    Can the old D-line attachments fit the new CAD relays
                     
                    Product Line:
                    IEC Contactors

                    Environment:
                    Tesys D contactors and relays
                     
                    Cause:
                    Using old accessories with new CAD relays

                    Resolution:
                     Yes, the old style front mount latch attachments, timing attachments, and auxiliary contacts will mount on the new Tesys D-line relays.

                    ETSNZ - Can Tesys F range contactors be used in safety applications?

                    According to IEC60947-4-1 appendix F, mirror contact is one of the means necessary to ensure safety for contactors
                    (in the standard "...mirror contact should not be relied upon exclusively as a means to ensure safety..." ).

                    TeSys F contactors do not include internal mirror contacts. So we, Schneider, do not actively promote TeSys F as a contactor for safety applications.
                    However, TeSys F can be fitted with auxiliary contacts add-on blocks. For some of these blocks LADN01, LADN02, LADN04, LADN11, LADN22, LADN31 and LADN13, a NC auxiliary contact has been recognised by VDE as mirror contact. This allows to use TeSys F in safety applications.
                    Attached are the VDE Certificates recognising the NC auxiliary contact with the blocks mentioned above as mirror contact.

                    To sum up and give clear answers to TeSys F and safety applications ;
                    1. If Tesys F contactor can be used for safety applications?

                    Yes, it can be used if, this is mandatory, it is fitted with one the above mentioned add-on blocks. VDE Certificate recognising the auxiliary contact as mirror can be provided.


                    2. When asked, can we answer that Tesys F have mirror contact, provided by auxiliary contact blocks?

                    Yes for the above mentioned add-on blocks and with the VDE Certificate

                    GV2 Adapter Plate Mounting

                    Two lock elements come with LAD311. The first one, already mounted on LAD311 when delivered is suitable for almost all cases of LC1D contactor. However, depending on the type of coil of the contactor (DC or AC), this element shall be mounted in one position for DC or turned by 180° around an horizontal axis for AC coil contactor. Note that on the lateral face of this elements the markings “DC” or “AC” mounted upwards indicates the right position to be used. The second LAD311 lock element shall be used when mounting contactors LC1D09 to LC1D18 with screw clamp. In this case, this element shall be mounted on LAD311 instead of the first one which can be scrapped away.

                    See attached document for reference. 

                    What is the auxiliary 3 x N/O and 1 x N/C front fitted needed for a LC1D5011 contactor

                    The Auxiliary is an LADN31

                    Will a single circuit auxiliary contact block, like a LADN10 or LADN01, fit onto the Tesys D09-D38 amp contactors?

                    Issue:
                    Identifying auxiliary contact blocks for Tesys D contactors

                    Product Line:
                    IEC contactors and starters

                    Environment:
                    Products sold and used in the United States

                    Cause:
                    single auxiliary contact block needed for use on a Tesys D line contactor

                    Resolution:
                    No, the single pole contact block will not fit . A LADN11,LADN20, LADN02 etc will fit. Anything with 2 auxiliary contacts in one block will fit.
                     

                    Can the single pole LA1DN and LADN auxiliary contact module be mounted on the TeSys contactors?

                    ISSUE
                    Can the single pole LA1DN and LADN auxiliary contact module be mounted on the TeSys contactors?
                    PRODUCT LINE
                    Auxiliary contacts for the Tesys D line
                    ENVIRONMENT
                    Tesys D-Line and Tesys F
                    CAUSE
                    Fit
                    RESOLUTION
                    These contacts will only fit on the following contactors:
                    Front mount only for LC1D40 through LC1D115 devices and LC1D40A - LC1D65A.
                    Left side mount only to LC1F contactors
                    CTA-ID : 2002751

                    What is the part code for a terminal block for Tesys base LUB320

                    Use a LU9BN11 code

                    Why will LA1SK11 adder deck not fit on CA2SK11 relay?

                    Issue:
                    Why will LA1SK11 adder deck not fit on CA2SK11 relay?

                    Product Line:
                    Tesys Relays

                    Environment:
                    All Products

                    Cause:
                    Product Features

                    Resolution:
                    No, LA1SK11 mounts only on the CA2SK20 relay.




                    CTA-ID : 2014524

                    Need the spare part code for a DOL starter LE1D12, only need the arm behind push button

                     The part code is LAD9091

                    What is the interlock for LCD18

                     The part code is LAD9R1V

                    What is the replacement AC coil for LC1D/LC2D40, D50, D65, D80, and D95?

                    Issue:
                    AC Coil information for LC1D/LC2D40, D50, D65, D80, and D95

                    Product Line:
                    Tesys D Replacement Parts

                    Environment:
                    TeSys™ D AC Coils

                    Resolution:

                    What is the part number for Side mount auxiliary 2NC and terminal shroud for LC1D1506 contactor?

                    The part number for Side mount auxiliary 2NC and terminal shroud for LC1D1506 contactor are LAD8N02 and LA9D115703.
                    LAD8N02                                                                                                                                    LA9D115703
                     TeSys D - auxiliary contact block - 2 NC - screw clamp terminals                              shrouds - for 3 poles TeSys model D

                    For more information see:

                    https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LAD8N02
                    https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LA9D115703

                                                                                                                                                                                                                                                                                                                                                                                                                           

                                                                

                    Is the LCUA32BL still available in NZ

                    TeSys motor starter LUB320 + LU9BN11 terminal block + LUCB32BL advance control unit

                    What is the replacement for LA1EN11?

                    LA1KN11  is the replacement code.

                    NOTE: new commercial reference found might not be an exact match

                    Need a LC2D323U7 reversing contactor

                    Use 2 x LC1D32U7 with a LAD9R1V reversing wiring kit

                    What is the part number of the mechanical link for reversing contactors LC1D25U7

                    LAD9R1V

                    Difference between LAD9ET1 and LAD9ET1S

                    Issue:
                    What is the difference between the LAD9ET1 and the LAD9ET1S

                    Product Line:
                    TeSys D accessories

                    Environment:
                    US Product

                    Cause:
                    Neither of these parts are in the Digest

                    Resolution:
                    The S designates a red cover.  These covers are red to designate that the contactor is being used for a safety application or part of a safety circuit.  The part number without the S is for a standard replacement covers.

                     

                    Is the LAD7B10 a UL and CSA Recognized Component?

                    Issue:
                    Is the LAD7B10 a UL or CSA recognized component?

                    Product Line:
                    IEC Overload Mounting Kit

                    Environment:
                    IEC Contactors

                    Cause:
                    Clarify CSA and UL listing for IEC components

                    Resolution:
                    As of 6/30/2016 this device has been UL component recongnized. This device has not been CSA recognized

                    Key words LAD7B10, UL, CSA, separate mounting

                    Case Subject:
                    LAD7B10

                    What is the mechanical interlock for an LC1D32U7

                     The LAD9R1V reverser kit contains the mechanical interlock you need for the LC1D32U7

                    What is the contactor to control 8A max with 24V AC coil and interlock kit to suite

                     Part codes LC1D09B7 + LAD9R1V

                    What is the interlock for LC1D38***

                    As the interlock is not sold separate the part number needed is LAD9R1V

                    What is the Mechanical Interlock for the LC1D12F7 ?

                    LAD9R1V Is the code for the Mechanical and Electrical Interlock kit.

                    Will the LAD** time delay auxiliary contact module fit the D2 series pre-Tesys contactors?

                    Issue:
                    Can new accessories be used on older style contactors

                    Product Line:
                    IEC contactors and starters

                    Environment:
                    Products sold and used in the United States

                    Cause:
                    Identifying product compatibility

                    Resolution:
                    Yes, all front mount D2 and Tesys series auxiliary modules are backward forward compatible.


                     

                    What size cable does a LAD7B10 accept?

                    Issue:
                    Need to know the size cable accepted by the LAD7B10 block.

                    Product Line:
                    IEC Contactors and starters

                    Environment:
                    Products sold and used in the United States

                    Cause:
                    Identifying cabling requirements.

                    Resolution:
                    It takes either a 1 flexible cable without cable end size 14-8 AWG or 1 flex cable with cable end size 16-12AWG or 1 solid cable without cable end size 16-10 AWG.


                     

                    What parts do I need to put together an LUB12

                    LUB12 is no longer available complete but can be built using  LUB120 + LU9BN11 (= LUB12)
                    Note: A control unit (overload) will still be required to be added to suit the motor current rating to complete the starter.

                    What is the Part Number for the Mechanical Interlock for the 4-pole LC1DT20, LC1DT25, LC1DT32, and LC1DT40 Contactors?

                    Issue:
                    Four-pole IEC contactors needs the part number for the mechanical interlock

                    Product Line:
                    IEC Contactors

                    Environment:
                    Tesys D contactors

                    Resolution:
                    LADT9R1 is the mechanical interlock and power wiring only. The LADT9RV1 also includes an electrical interlock (2 NC contacts).

                    Is there a mechanical interlock for the LC1DT range of contactors?

                    No, there is no interlock available specifically for the LC1DT contactors.

                    The mechanical interlock that comes with the 3 pole reversing kit LAD9R1V will fit, although the power interlock and reverse wiring included in this kit will not be compatible.

                    Will the LAD7B10 or the LAD7B106 work on the Pre-Tesys D line LR2D15*** overload relays?

                    Issue:
                    Separate mount block needed for older style overload relay

                    Product Line:
                    IEC contactors and starters

                    Environment:
                    North American Products

                    Resolution:
                    No. These are a different design and will not work with the pre - Tesys overload relays.


                     

                    Will the LA7D1064 fit the new TeSys LRD overload relays?

                    Issue:
                    Identifying separate mount for newer style LRD overload relays

                    Product Line:
                    IEC contactors and starters

                    Environment:
                    Products sold and used in the United States

                    Resolution:
                    No, they are a different design and will not work with the Tesys overload relays, you will need the LAD7B10 or LAD7B10..

                    Video: What auxiliary contact modules are available for the LC1D and LC2D contactors?

                    Issue:
                    Auxiliary contact modules for the LC1D and LC2D contactors

                    Product Line: 
                    Contactor and Starters - IEC

                    Environment:
                    North American Products

                    Resolution:
                    Select based on application requirements. Please note that the TeSys and Pre-TeSys auxiliary blocks are backward/forward compatible.
                    Front Mounting; maximum of 1 block per contactor:

                    N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                    --1-----------1---------LADN11-----------LA1DN11
                    --1-----------1---------LADN11G---------LA1DN11G (See Footnote 1)
                    --1-----------1---------LADN11P---------LA1DN11P (See Footnote 1)
                    --2-----------0---------LADN20-----------LA1DN20
                    --2-----------0---------LA1DX20---------LA1DX20 (See Footnote 2)
                    --2-----------0---------LA1DY20---------LA1DY20 (See Footnote 3)
                    --0-----------2---------LADN02-----------LA1DN02
                    --2-----------2---------LADN22-----------LA1DN22
                    --2-----------2---------LADN22G---------LA1DN22G (See Footnote 1)
                    --2-----------2---------LADN22P---------LA1DN22P (See Footnote 1)
                    --2-----------2---------LADC22------------LA1DC22 (See Footnote 4)
                    --3-----------1---------LADN31------------LA1DN31
                    --3-----------1---------LA1DZ31----------LA1DZ31 (See Footnote 5)
                    --1-----------3---------LADN13------------LA1DN13
                    --4-----------0---------LADN40------------LA1DN40
                    --4-----------0---------LA1DZ40-----------LA1DZ40 (See Footnote 6)
                    --0-----------4---------LADN04------------LA1DN04




                    Front Mounting; maximum of 1 block per contactor: For use with D2 Series 25 amp through 80 amp contactors and TeSys Series 40 amp through 80 amp only.

                    N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                    --1-----------0--------LADN10----------LA1DN10
                    --0-----------1--------LADN01----------LA1DN01

                    Side Mounting; maximum of 1 block on each side for D2 Series and Tesys Series 40 through 80 amp contactors. Tesys 9 through 32, 115, and 150 amps contactors will accept 1 block and is limited to left side only. (*) DC control devices will not accept side mount auxiliaries.
                    (*) DC control exceptions that will accept one left side mounted auxiliary: LC1D115 & LC1D150.

                    N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                    --1-----------1--------LAD8N11----------LA8DN11
                    --2-----------0--------LAD8N20----------LA8DN20
                    --0-----------2--------LAD8N02----------N/A

                    Footnotes:
                    {1} EN50 012 Machine Tool Terminal Markings
                    {2} (2) NO Sealed Dust Tight Contacts
                    {3} Gold Flash Contacts
                    {4} (1) NO & (1) NC Standard and (1) NO & (1) NC Make Before Break
                    {5} (2) NO Dust Tight Contacts & (1) NO & (1) NC Standard Contacts
                    {6} (2) NO Dust Tight Contacts & (2) NO Standard Contacts

                    What mechanical and electrical interlock kits are available to field assemble a reversing contactor from the LC1D09 through LC1D38 (9 to 38 amp ) Tesys contactors?

                    Issue:
                    Identifying interlocks to field assemble a reversing contactor

                    Product Line:
                    IEC contactors and starters

                    Environment:
                    Products sold and used in the United States

                    Cause:
                    Field assembling a reversing IEC contactor

                    Resolution:
                    Use the LAD9R1V kit for mechanical and electrical interlocking or use the LAD9R1 kit for mechanical interlocking without electrical interlocking. Both include power connections


                     

                    What interlock works with the LC1D128, 4 pole contactors?

                    Issue:
                    Interlocking 4 pole Tesys D contactors

                    Product line:
                    Tesys D IEC contactors

                    Environment:
                    4 pole contactors with 2NO and 2NC power poles - LC1D098 LC1D128 LC1D188 LC1D258

                    Cause:
                    Catalog lists interlock for contactors with 4NO poles only

                    Resolution:
                    It is recommended to use the LAD9R1V interlock kit with the contactors that have 2NO and 2NC power poles.  This kit provides the mechanical and electrical interlock needed to use in a reversing installation.