Browse all
Browse all

TeSys D Contactor TeSys Deca, 3P(3 NO), AC-3/AC-3e, 0 to 440V, 9A, 24-60VAC/DC coil

TeSys D Contactor TeSys Deca, 3P(3 NO), AC-3/AC-3e, 0 to 440V, 9A, 24-60VAC/DC coil

Item Number: LC1D09BNE

Datasheet

Product Dimensions

Width icon

Width45 mm

Height icon

Height77 mm

Depth icon

Depth86 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product TeSys Deca Advanced
Product or component type contactor
Warranty 18 months

Physical

[ue] rated operational voltage power circuit: <= 690 V AC 25...400 Hz
[ie] rated operational current
  • 9 A (at <60 °C) at <= 440 V AC-3 for power circuit
  • 25 A (at <60 °C) at <= 440 V AC-1 for power circuit
  • 9 A (at <60 °C) at <= 440 V AC-3e for power circuit
Mechanical durability 15 Mcycles
Electrical durability
  • 2.4 Mcycles 8 A AC-3 at Ue <= 440 V
  • 0.6 Mcycles 25 A AC-1 at Ue <= 440 V
  • 2.4 Mcycles 8 A AC-3e at Ue <= 440 V
Connections - terminals
  • control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end
  • control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end
  • control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end
  • control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end
  • control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid
  • control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid
  • power circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end
  • power circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end
  • power circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end
  • power circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end
  • power circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid
  • power circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid
Insulation resistance > 10 MOhm for signalling circuit
Mounting support
  • rail
  • plate
Connections - terminals screw clamp terminals
Standards
  • EN/IEC 60947-4-1
  • EN/IEC 60947-5-1
  • UL 60947-4-1
  • CSA C22.2 No 60947-4-1
  • IEC 60335-1
Product certifications
  • CCC
  • CSA
  • EAC
  • UL
  • KC
  • DNV-GL
  • LROS (Lloyds register of shipping)
  • UKCA
Ip degree of protection IP20 front face conforming to IEC 60529
Climatic withstand
  • conforming to IACS E10 exposure to damp heat
  • conforming to IEC 60947-1 Annex Q category D exposure to damp heat
Height 77 mm
Width 45 mm
Depth 86 mm
Net weight 0.368 kg
Mercury free Yes
Rohs exemption information Yes
Environmental disclosure ENVPEP1609001EN
Reach regulation Reference contains Substances of Very High Concern above the threshold
China rohs regulation Product out of China RoHS scope
Eu rohs directive Compliant By Exemption

Others

Life cycle assessment data Yes
Substance regulation data deliverable Yes
Package 1 bare product quantity 1
Legacy weee scope In
At least in Europe
Package 2 bare product quantity 15
Package 3 bare product quantity 240
Average percentage of recycled plastic content 0 %
Warranty duration(in months) bmecat 18
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Device short name LC1D
Contactor application
  • motor control
  • resistive load
Utilisation category
  • AC-1
  • AC-3
  • AC-3e
Poles description 3P
[uc] control circuit voltage
  • 24...60 V AC 50/60 Hz
  • 24...60 V DC
Motor power kw
  • 2.2 kW at 220...230 V AC 50 Hz (AC-3)
  • 4 kW at 380...400 V AC 50 Hz (AC-3)
  • 4 kW at 415 V AC 50 Hz (AC-3)
  • 4 kW at 440 V AC 50 Hz (AC-3)
  • 5.5 kW at 500 V AC 50 Hz (AC-3)
  • 5.5 kW at 660...690 V AC 50 Hz (AC-3)
  • 2.2 kW at 220...230 V AC 50 Hz (AC-3e)
  • 4 kW at 380...400 V AC 50 Hz (AC-3e)
  • 4 kW at 415 V AC 50 Hz (AC-3e)
  • 4 kW at 440 V AC 50 Hz (AC-3e)
  • 5.5 kW at 500 V AC 50 Hz (AC-3e)
  • 5.5 kW at 660...690 V AC 50 Hz (AC-3e)
Motor power hp
  • 0.33 hp at 115 V AC 60 Hz for 1 phase motors
  • 1 hp at 230/240 V AC 60 Hz for 1 phase motors
  • 2 hp at 200/208 V AC 60 Hz for 3 phases motors
  • 2 hp at 230/240 V AC 60 Hz for 3 phases motors
  • 5 hp at 460/480 V AC 60 Hz for 3 phases motors
  • 7.5 hp at 575/600 V AC 60 Hz for 3 phases motors
Compatibility code LC1D
Pole contact composition 3 NO
Protective cover with
[ith] conventional free air thermal current
  • 10 A (at 60 °C) for signalling circuit
  • 25 A (at 60 °C) for power circuit
Irms rated making capacity
  • 250 A at 440 V for power circuit conforming to IEC 60947
  • 140 A AC for signalling circuit conforming to IEC 60947-5-1
  • 250 A DC for signalling circuit conforming to IEC 60947-5-1
Rated breaking capacity 250 A at 440 V for power circuit conforming to IEC 60947
[icw] rated short-time withstand current
  • 100 A - 1 s for signalling circuit
  • 120 A - 500 ms for signalling circuit
  • 140 A - 100 ms for signalling circuit
  • 30 A 40 °C - 10 min for power circuit
  • 61 A 40 °C - 1 min for power circuit
  • 105 A 40 °C - 10 s for power circuit
  • 210 A 40 °C - 1 s for power circuit
Associated fuse rating
  • 10 A gG for signalling circuit conforming to IEC 60947-5-1
  • 25 A gG at <= 690 V coordination type 1 for power circuit
  • 20 A gG at <= 690 V coordination type 2 for power circuit
Average impedance 2.5 mOhm - Ith 25 A 50 Hz for power circuit
Power dissipation per pole
  • 1.56 W AC-1
  • 0.2 W AC-3
  • 0.2 W AC-3e
[ui] rated insulation voltage
  • power circuit: 690 V conforming to IEC 60947-4-1
  • signalling circuit: 690 V conforming to IEC 60947-1
Overvoltage category III
Pollution degree 3
[uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947
Safety reliability level
  • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
  • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Control circuit type AC/DC at 50/60 Hz AC/DC electronic
Coil technology built-in bidirectional peak limiting
Control circuit voltage limits
  • <= 0.1 Uc (-40-70 °C):drop-out AC/DC
  • 0.85...1.1 Uc (-40-60 °C):operational AC
  • 0.8...1.1 Uc (-40-60 °C):operational DC
  • 1...1.1 Uc (60-70 °C):operational AC/DC
Inrush power in va 15 VA 50/60 Hz (at 20 °C)
Inrush power in w 14 W (at 20 °C)
Hold-in power consumption in va 0.9...0.9 VA 50/60 Hz (at 20 °C)
Hold-in power consumption in w 0.6...0.6 W at 20 °C
Heat dissipation 0.6...0.6 W at 50/60 Hz
Operating time
  • 45...55 ms closing
  • 20...90 ms opening
Maximum operating rate 3600 cyc/h at 60 °C
Tightening torque
  • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
  • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
  • power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
  • power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
  • power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
  • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Auxiliary contact composition 1 NO + 1 NC
Auxiliary contacts type
  • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
  • type mirror contact 1 NC conforming to IEC 60947-4-1
Signalling circuit frequency 25...400 Hz
Minimum switching voltage 17 V for signalling circuit
Minimum switching current 5 mA for signalling circuit
Non-overlap time
  • 1.5 ms on de-energisation between NC and NO contact
  • 1.5 ms on energisation between NC and NO contact
Maximum motor phase current 9 A
[uc] control circuit voltage 24...60 V
Permissible ambient air temperature around the device
  • -40...60 °C
  • 60...70 °C with derating
Operating altitude 0...3000 m
Fire resistance 850 °C conforming to IEC 60695-2-1
Flame retardance V1 conforming to UL 94
Mechanical robustness
  • vibrations contactor open (2 Gn, 5...300 Hz)
  • vibrations contactor closed (4 Gn, 5...300 Hz)
  • shocks contactor open (10 Gn for 11 ms)
  • shocks contactor closed (15 Gn for 11 ms)
Unit type of package 1 PCE
Number of units in package 1 1
Package 1 height 5.600 cm
Package 1 width 9.600 cm
Package 1 length 12.000 cm
Package 1 weight 395.000 g
Unit type of package 2 S02
Number of units in package 2 15
Package 2 height 15.000 cm
Package 2 width 30.000 cm
Package 2 length 40.000 cm
Package 2 weight 6.275 kg
Unit type of package 3 P06
Number of units in package 3 240
Package 3 height 75.000 cm
Package 3 width 60.000 cm
Package 3 length 80.000 cm
Package 3 weight 100.400 kg
Green premium status for reporting Green Premium product
Total lifecycle carbon footprint 8 kg CO2 eq.
Carbon footprint of the manufacturing phase [a1 to a3] 3.05329395824414
Carbon footprint of the manufacturing phase [a1 to a3] 3 kg CO2 eq.
Carbon footprint of the distribution phase [a4] 0.11024017747820003
Carbon footprint of the distribution phase [a4] 0.1 kg CO2 eq.
Carbon footprint of the installation phase [a5] 0.041152029342718374
Carbon footprint of the installation phase [a5] 0 kg CO2 eq.
Carbon footprint of the use phase [b2, b3, b4, b6] 4.38963157894737
Carbon footprint of the use phase [b2, b3, b4, b6] 4 kg CO2 eq.
Sustainable packaging Yes
Carbon footprint of the end-of-life phase [c1 to c4] 0.632401664023421
Carbon footprint of the end-of-life phase [c1 to c4] 0.6 kg CO2 eq.
Halogen-free status Halogen free plastic parts & cables product
F-gas free N/A
Take-back No
Product contributes to saved and avoided emissions No
Removable battery N/A
Total lifecycle carbon footprint 8.22671940803585
Average percentage of recycled metal content 0 %
Packaging made with recycled cardboard Yes
Packaging without single use plastic Yes
Scip number 7d699774-c34b-4bf4-9ecb-388a149eefdd
Halogen-free status Halogen free plastic parts & cables product
End of life manual availability ENVEOLI1609001EN
Take-back No
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Warranty (in months) 18

Documents & downloads

Filter items
  • All

  • Product Brochures

  • CAD Files and Packs

  • Technical Data Catalogues

  • Data Bulletin

  • End of Life Manual

  • Environmental Disclosure

  • Installation Instruction

  • Technical illustration

  • Certificates (MSDS)

  • Declaration of Conformity

  • Declaration of Conformity (Sustainability)

Important: Some software files may need a mySchneider or Club login to download.