Specifications

hide show
Range of product
TeSys D
Range
TeSys
Device short name
LAD4
Product or component type
suppressor module
Product compatibility
  • 3P LC1D40A...D80A
  • 4P LC1DT60A...DT80A
    • Mounting location
      front
      Mounting mode
      by clips
      Suppressor technology
      bidirectional peak limiting diode
      [Uc] control circuit voltage
    • 12...24 V DC
    • 12...24 V AC 50/60 Hz
      • Maximum peak voltage
        2 Uc
        Net weight
        0.02 kg
        Compatibility code
        LAD4
        Ambient air temperature for operation
        -25-55 °C
        Ambient air temperature for storage
        -40-80 °C
        Unit Type of Package 1
        PCE
        Number of Units in Package 1
        1
        Package 1 Weight
        19 g
        Package 1 Height
        2 cm
        Package 1 width
        5 cm
        Package 1 Length
        10 cm
        Unit Type of Package 2
        BB1
        Number of Units in Package 2
        10
        Package 2 Weight
        194 g
        Package 2 Height
        6.2 cm
        Package 2 width
        7.5 cm
        Package 2 Length
        12 cm
        Unit Type of Package 3
        S01
        Number of Units in Package 3
        100
        Package 3 Weight
        2.18 kg
        Package 3 Height
        15 cm
        Package 3 width
        15 cm
        Package 3 Length
        40 cm
        Sustainable offer status
        Green Premium product
        REACh free of SVHC
        Yes
        EU RoHS Directive
        Compliant
        Toxic heavy metal free
        Yes
        Mercury free
        Yes
        RoHS exemption information
        Yes
        China RoHS Regulation
         Pro-active China RoHS declaration (out of China RoHS legal scope)
        Environmental Disclosure
        ENVPEP111253EN
        WEEE
        The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
        Warranty
        18 months

        Documents & downloads

        hide show
        Filter items
        • All

        • Product Brochures

        • Technical Data Catalogues

        • Product Environmental

        • Installation Instruction

        • Declaration of Conformity

        Frequently Asked Questions

        hide show

        What is the difference between the LAD4TB and LAD4TBDL bi-directional peak limiting diode?

        Issue:
        Identifying the difference between LAD4TB and LAD4TBDL

        Product Line:
        IEC contactors and starters

        Environment:
        Products sold and used in the United States

        Cause:
        Identifying the difference between two similar part numbers

        Resolution:
        The LAD4TB is for 24V AC coils for the Tesys Series LC1D09 through LC1D38 contactors when supplied with G7 voltage code. The LAD4TBDL is 24 vdc bi-directional diode offered as a replacement if for some reason the diode supplied with the Tesys LC1D09 through LC1D38 contactors when ordered with BD or BL voltage code breaks or is no longer working.


         

        Where can I find installation instructions for the LAD703 remote reset module?

        Issue:
        Installation and connection instructions for LAD703F

        Product line:
        Tesys D

        Environment:
        Remote reset module LAD703B LAD703F LAD703J LAD703E LAD703M LAD703Q LAD703N

        Cause:
        Documentation

        Resolution:
        See the attached instructions to mount the LAD703 onto the LRD style overloads.
        Apply wiring to the C1 and C2 terminals. 
        When the appropriate voltage is applied, the overload will reset.

        Are the LAD703F coils rated for continuous duty?

        Issue:
        Can you continuously press the reset button?

        Product line:
        Tesys D IEC Contactors and Overload Accessories

        Environment:
        LAD703 remote stop or electrical reset
        LA7D03 remote tripping or electrical reset

        Cause:
        Customer was using competitor brand and it burns after 10 seconds

        Resolution:
        The time for which the coil of the remote tripping or electrical resetting device, LAD703 or LA7D03 can remain energized depends on the rest time in between energizing the coil. 
        Minimum pulse to energize is 200ms

        1 second pulse needs a 9 second rest time
        5 second pulse needs a 30 second rest time
        10 second pulse needs a 90 second rest time
        Maximum duration of energizing the coil is 20 seconds and would require a 300 second rest time. 
         

        Will the LAD4BB adapter work with a LC1D12BD contactor?

        Issue:
        Can we use the LAD4BB with the LC1D12BD?

        Product Line:
        IEC contactors and starters

        Environment:
        Products sold and used in the United States

        Cause:
        Identifying product compatibility

        Resolution:
        The LAD4BB will not work on the DC contactors, just the AC contactors.
         

        I have a LC1D12BD contactor and want to fit a LA4DFB to it

         You need to use a LAD4BB adaptor

        In regards to LAD5C11 LAD5C31 LAD5C12 LAD5C32 What is the maximum kW range that TeSys SoLink can be used with motor starter combination?

        TeSys SoLink is the connection module to connect GV2/GV3 motor circuit breakers to associated contactors and can be used with GV2 / GV3 breakers up to 30kW.
        For more information please visit the Link provided
        https://www.schneider-electric.com.au/australia/en/products-services/offer-updates/news-viewer.page?c_filepath=/templatedata/Content/News/data/en/local/automation_control/general_information/2014/10/20141024_tesys_solink_integration_system.xml

        In regards to LAD5C11 LAD5C31 LAD5C12 LAD5C32 SoLink What is the maximum number of motor starters that can be connected and controlled with each logic controller?

        Each TM3 I/O module is able to monitor and control up to 4 motor starters and up to 56 motor starters can be connected to logic controller.
        For more information aboput this range please Visit the Schneider website on the link provided
        https://www.schneider-electric.com.au/australia/en/products-services/offer-updates/news-viewer.page?c_filepath=/templatedata/Content/News/data/en/local/automation_control/general_information/2014/10/20141024_tesys_solink_integration_system.xml

        In regards to LAD5C11 LAD5C31 LAD5C12 LAD5C32 SoLink , Can TeSys SoLink be used with AC control supply?

        TeSys SoLink is suitable for 24VDC control supply; the TM3 I/O module provides the 24V DC control voltage to the motor starter.
        For more information on this range please visit the Schneider electric web site on the link provided
        https://www.schneider-electric.com.au/australia/en/products-services/offer-updates/news-viewer.page?c_filepath=/templatedata/Content/News/data/en/local/automation_control/general_information/2014/10/20141024_tesys_solink_integration_system.xml

        What is the replacement AC coil for CAD32 and CAD50 relay?

        Issue:
        AC coil replacement for CAD32 and CAD50

        Product Line:
        Relays

        Environment:
        Tesys CAD Control Relays

        Cause:
        Product selection

        Resolution:
        Volt = coil part number
        12 = LXD1J7
        21 = LXD1Z7
        24 = LXD1B7
        32 = LXD1C7
        36 = LXD1CC7
        42 = LXD1D7
        48 = LXD1E7
        60 = LXD1EE7
        100 = LXD1K7
        110 = LXD1F7
        115 = LXD1FE7
        120 = LXD1G7
        127 = LXD1FC7
        200 = LXD1L7
        208 = LXD1LL7
        220/230 = LXD1M7
        230 595 21 LXD1P7
        230/240 = LXD1U7
        277 781 30 LXD1W7
        380/400 = LXD1Q7
        400 = LXD1V7
        415 = LXD1N7
        440 = LXD1R7
        480 = LXD1T7
        600 = LXD1X7
        690 = LXD1Y7

         

        Part number LA4DFB not fitting on LC1D12 Contactor?

        Can I use a LA9D6569 reversing kit with LC1D40AU7 contactors

        No, correct kit is a LAD9R3.

        What suppressor do I need for a LC1DT40 contactor 110Vac

        You need to use a LAD4RCU - RC circuit suppressor 110-240Vac.