Specifications

hide show
Range of product
  • TeSys fuse-disconnector
  • TeSys GV2
    • Range
      TeSys
      Device short name
      LAD
      Product or component type
      adaptor plate
      Accessory / separate part category
      mounting accessory
      Product compatibility
    • LS1D32
    • LC1D09...D38
      • Net weight
        0.04 kg
        Compatibility code
        LAD
        Sustainable offer status
        Green Premium product
        REACh Regulation
        Free of Substances of Very High Concern above the threshold
        REACh free of SVHC
        Yes
        EU RoHS Directive
        Compliant
        Toxic heavy metal free
        Yes
        Mercury free
        Yes
        RoHS exemption information
        Yes
        China RoHS Regulation
        X
        Environmental Disclosure
        ENVPEP111213EN_V1
        WEEE
        The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
        Warranty
        18 months

        Documents & downloads

        hide show
        Filter items
        • All

        • Product Brochures

        • Technical Data Catalogues

        • Installation Instruction

        • Product Environmental

        Frequently Asked Questions

        hide show

        GV2 Adapter Plate Mounting

        Two lock elements come with LAD311. The first one, already mounted on LAD311 when delivered is suitable for almost all cases of LC1D contactor. However, depending on the type of coil of the contactor (DC or AC), this element shall be mounted in one position for DC or turned by 180° around an horizontal axis for AC coil contactor. Note that on the lateral face of this elements the markings “DC” or “AC” mounted upwards indicates the right position to be used. The second LAD311 lock element shall be used when mounting contactors LC1D09 to LC1D18 with screw clamp. In this case, this element shall be mounted on LAD311 instead of the first one which can be scrapped away.

        See attached document for reference. 

        What is the part code for a 630A Contactor with 230V coil

         The part codes you need LC1F630 + LX1FL220 + LADN11

        What is the part code for the Adaptor to join the GV2P16 to a LC1D09BL

        You can use GV2AF3 or GV2AF4 + LAD31

        What is the replacement AC coil for CAD32 and CAD50 relay?

        Issue:
        AC coil replacement for CAD32 and CAD50

        Product Line:
        Relays

        Environment:
        Tesys CAD Control Relays

        Cause:
        Product selection

        Resolution:
        Volt = coil part number
        12 = LXD1J7
        21 = LXD1Z7
        24 = LXD1B7
        32 = LXD1C7
        36 = LXD1CC7
        42 = LXD1D7
        48 = LXD1E7
        60 = LXD1EE7
        100 = LXD1K7
        110 = LXD1F7
        115 = LXD1FE7
        120 = LXD1G7
        127 = LXD1FC7
        200 = LXD1L7
        208 = LXD1LL7
        220/230 = LXD1M7
        230 595 21 LXD1P7
        230/240 = LXD1U7
        277 781 30 LXD1W7
        380/400 = LXD1Q7
        400 = LXD1V7
        415 = LXD1N7
        440 = LXD1R7
        480 = LXD1T7
        600 = LXD1X7
        690 = LXD1Y7

         

        What overload can be used with an LC1D65AU7?

        You can use the Everlink range which is LRD313 - LRD365

        What is the auxiliary 3 x N/O and 1 x N/C front fitted needed for a LC1D5011 contactor

        The Auxiliary is an LADN31

        In regards to LAD5C11 LAD5C31 LAD5C12 LAD5C32 What is the maximum kW range that TeSys SoLink can be used with motor starter combination?

        TeSys SoLink is the connection module to connect GV2/GV3 motor circuit breakers to associated contactors and can be used with GV2 / GV3 breakers up to 30kW.
        For more information please visit the Link provided
        https://www.schneider-electric.com.au/australia/en/products-services/offer-updates/news-viewer.page?c_filepath=/templatedata/Content/News/data/en/local/automation_control/general_information/2014/10/20141024_tesys_solink_integration_system.xml

        In regards to LAD5C11 LAD5C31 LAD5C12 LAD5C32 SoLink What is the maximum number of motor starters that can be connected and controlled with each logic controller?

        Each TM3 I/O module is able to monitor and control up to 4 motor starters and up to 56 motor starters can be connected to logic controller.
        For more information aboput this range please Visit the Schneider website on the link provided
        https://www.schneider-electric.com.au/australia/en/products-services/offer-updates/news-viewer.page?c_filepath=/templatedata/Content/News/data/en/local/automation_control/general_information/2014/10/20141024_tesys_solink_integration_system.xml

        In regards to LAD5C11 LAD5C31 LAD5C12 LAD5C32 SoLink , Can TeSys SoLink be used with AC control supply?

        TeSys SoLink is suitable for 24VDC control supply; the TM3 I/O module provides the 24V DC control voltage to the motor starter.
        For more information on this range please visit the Schneider electric web site on the link provided
        https://www.schneider-electric.com.au/australia/en/products-services/offer-updates/news-viewer.page?c_filepath=/templatedata/Content/News/data/en/local/automation_control/general_information/2014/10/20141024_tesys_solink_integration_system.xml

        ETSNZ - Can Tesys F range contactors be used in safety applications?

        According to IEC60947-4-1 appendix F, mirror contact is one of the means necessary to ensure safety for contactors
        (in the standard "...mirror contact should not be relied upon exclusively as a means to ensure safety..." ).

        TeSys F contactors do not include internal mirror contacts. So we, Schneider, do not actively promote TeSys F as a contactor for safety applications.
        However, TeSys F can be fitted with auxiliary contacts add-on blocks. For some of these blocks LADN01, LADN02, LADN04, LADN11, LADN22, LADN31 and LADN13, a NC auxiliary contact has been recognised by VDE as mirror contact. This allows to use TeSys F in safety applications.
        Attached are the VDE Certificates recognising the NC auxiliary contact with the blocks mentioned above as mirror contact.

        To sum up and give clear answers to TeSys F and safety applications ;
        1. If Tesys F contactor can be used for safety applications?

        Yes, it can be used if, this is mandatory, it is fitted with one the above mentioned add-on blocks. VDE Certificate recognising the auxiliary contact as mirror can be provided.


        2. When asked, can we answer that Tesys F have mirror contact, provided by auxiliary contact blocks?

        Yes for the above mentioned add-on blocks and with the VDE Certificate

        How to use LRD01…35 LRD33•• & LRD43•• and LRD33** as an indepentent relay?

        The LRD relays has a solid tag to be used with LC1D** contactors. If you are not using LC1D contactors then using the following accessories you can terminate cable directly.

        For LRD01…35 use the following part: LAD7B106
        For LRD33•• & LRD43•• (3) use the following part: LA7D3064

        Can the old D-line front mount attachments fit on the new CAD relays?

        Issue: 
        Can the old D-line attachments fit the new CAD relays
         
        Product Line:
        IEC Contactors

        Environment:
        Tesys D contactors and relays
         
        Cause:
        Using old accessories with new CAD relays

        Resolution:
         Yes, the old style front mount latch attachments, timing attachments, and auxiliary contacts will mount on the new Tesys D-line relays.
        Show More