LA4DE varistors for D range contactors
 Coil Suppressor Module for D range contactors
LA4DE varistors for D range contactors
 Coil Suppressor Module for D range contactors

Suppressor Block

Catalogue Number: LA4DE3E
LA4DE varistors for D range contactors
 Coil Suppressor Module for D range contactors
LA4DE varistors for D range contactors
 Coil Suppressor Module for D range contactors
Retail
$97.45
RRP (Inc. GST)

Specifications

hide show
Range of product
TeSys D
Range
TeSys
Device short name
LA4D
Product or component type
suppressor module
Product compatibility
  • 4P LC1D40008...D80008
  • 3P LC1D80...D95
  • 4P LP1D80004
    • Mounting location
      top
      Mounting mode
      by screws
      Suppressor technology
      varistor (peak limiting)
      [Uc] control circuit voltage
      24...48 V DC
      Maximum peak voltage
      2 Uc
      Net weight
      0.018 kg
      Compatibility code
      LA4D
      Ambient air temperature for operation
      -25-55 °C
      Ambient air temperature for storage
      -40-80 °C
      Unit Type of Package 1
      PCE
      Number of Units in Package 1
      1
      Package 1 Weight
      16 g
      Package 1 Height
      2.7 cm
      Package 1 width
      4 cm
      Package 1 Length
      5 cm
      Unit Type of Package 2
      S01
      Number of Units in Package 2
      78
      Package 2 Weight
      1.455 kg
      Package 2 Height
      15 cm
      Package 2 width
      15 cm
      Package 2 Length
      40 cm
      Sustainable offer status
      Green Premium product
      REACh free of SVHC
      Yes
      EU RoHS Directive
      Compliant
      Toxic heavy metal free
      Yes
      Mercury free
      Yes
      RoHS exemption information
      Yes
      China RoHS Regulation
       Pro-active China RoHS declaration (out of China RoHS legal scope)
      Environmental Disclosure
      ENVPEP111253EN
      WEEE
      The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
      Warranty
      18 months

      Documents & downloads

      hide show
      Filter items
      • All

      • CAD Files and Packs

      • Product Brochures

      • Technical Data Catalogues

      • Installation Instruction

      Frequently Asked Questions

      hide show

      What is the LA4DE1U alternative?

      LA4DE1U TeSys D - suppressor module - varistor - 110...250 V AC/DC

      to suit D40-D115 (3P) and D65-115 (4P):
      LA4DE2U TeSys D - suppressor module - varistor - 110...250 V AC
      OR
      LA4DE3U TeSys D - suppressor module - varistor - 110...250 V DC
       

      Are the LAD703F coils rated for continuous duty?

      Issue:
      Can you continuously press the reset button?

      Product line:
      Tesys D IEC Contactors and Overload Accessories

      Environment:
      LAD703 remote stop or electrical reset
      LA7D03 remote tripping or electrical reset

      Cause:
      Customer was using competitor brand and it burns after 10 seconds

      Resolution:
      The time for which the coil of the remote tripping or electrical resetting device, LAD703 or LA7D03 can remain energized depends on the rest time in between energizing the coil. 
      Minimum pulse to energize is 200ms

      1 second pulse needs a 9 second rest time
      5 second pulse needs a 30 second rest time
      10 second pulse needs a 90 second rest time
      Maximum duration of energizing the coil is 20 seconds and would require a 300 second rest time. 
       

      What do the LA4D timing modules require for mounting on LC1D40A through LC1D65A contactors?

      Product Line:
       
      Tesys D line Contactors and Accessories

      Resolution:
       
      Mounting this module to TeSys LC1D40A through LC1D65A contactor requires the use of the LAD4BB3 wiring adaptor. This adaptor can be fitted only to contactors with no coil suppressor.
       

      Is the voltage code BD3 valid for a CA3DN40 relay?

      Issue:
      Is the voltage code BD3 valid for a CA3DN40 relay?

      Product Line:
      Tesys Relays

      Environment:
      All Products

      Cause:
      Product selection

      Resolution:
      No.  The voltage code BD3 is for the CA4D Low Consumption relays only.   A 24 volt DC coil with built in transient suppression is not available on the CA3D relay.    Use the add on LA4DA1E varister style or the LA4DC1U diode style add on transient suppressors on the CA3D relays.
       

      Does LC1D80BD have internal bi-directional diode?

      Issue:
      LC1D80 and LC1D95 bi-directional diode

      Product Line:
      TeSys™ D Contactors

      Environment:
      Contactor Accessories

      Resolution:
      LC1D80 and LC1D95 does not have an internal bi-directional peak limiting diode on their DC coils. LA4DC3U (Screw connection of wire to the contactor coil terminals 24–250 Vdc, 3p-4p) must be ordered separately.

      The LC1D09 to LC1D38 have an internal diode by default on their DC coils.

      What is the capacity (in Lbs.) of NetShelter Cable Ladder, or the capacity of a structure containing cable ladder?

      Issue:
      Information regarding the capacity of NetShelter Cable Ladder is required.

      Product Line:
      NetShelter Cable Ladder

      Environment:
      All versions and serial ranges.

      Cause:
      Capacity is not listed in the product specifications.

      Resolution:
      See attached file

      What the DC current contact ratings for the CAD50, CAD32, CAD503, CAD323, CAD506, and CAD326 relay?

      Issue:
      Checking on the DC current contact ratings for the CAD50, CAD32, CAD503,  CAD323,  CAD506, and  CAD326 relay.

      Product Line:
      CAD Industrial Relays

      Environment:
      Relays and Timers

      Resolution:
      Inductive:
      125V DC - 0.55 Amps make and break, 2.5 Amps cont.
      250V DC - 0.27 Amps make and break, 2.5 amps cont.
      600V DC - 0.10 Amps make and break, 2.5 Amps cont.

       

      What is the replacement AC coil for CAD32 and CAD50 relay?

      Issue:
      AC coil replacement for CAD32 and CAD50

      Product Line:
      Relays

      Environment:
      Tesys CAD Control Relays

      Cause:
      Product selection

      Resolution:
      Volt = coil part number
      12 = LXD1J7
      21 = LXD1Z7
      24 = LXD1B7
      32 = LXD1C7
      36 = LXD1CC7
      42 = LXD1D7
      48 = LXD1E7
      60 = LXD1EE7
      100 = LXD1K7
      110 = LXD1F7
      115 = LXD1FE7
      120 = LXD1G7
      127 = LXD1FC7
      200 = LXD1L7
      208 = LXD1LL7
      220/230 = LXD1M7
      230 595 21 LXD1P7
      230/240 = LXD1U7
      277 781 30 LXD1W7
      380/400 = LXD1Q7
      400 = LXD1V7
      415 = LXD1N7
      440 = LXD1R7
      480 = LXD1T7
      600 = LXD1X7
      690 = LXD1Y7

       

      Will the LA4DC1U work with the new CAD32BD relay?

      Issue:
      Will the LA4DC1U work on the CAd32BD relay

      Product Line:
      IEC relays and accessories

      Environment:
      Products sold and used in the United States

      Cause:
      Identifying product compatibility

      Resolution:
      The CAD32BD with DC coil has built-in coil suppression protection as standard so the LA4DC1U is not needed.


      CTA-ID : 2031917

      Will the LA4DC1U diode suppressor mount to current Tesys D DC coils?

      Issue:
      Will the LA4DC1U diode suppressor mount to current Tesys D DC coils?
      Product Line:
      IEC contactors and starters

      Environment:
      Products sold and used in the United States

      Resolution:
      No. The LA4DC1U diode unit will only fit the older TeSys D contactors. Tesys D DC coils include suppression automatically, it`s not needed.

      Why does my other equiptment trip when my contactor releases?

      The colapsing coil voltage on DC is causing a Back EMF (electro magnetic field) issue. This is solved with either a varistor LA4SKE1E or a Diode LA4SKC1U on the LP1K09 contactor.

      For further information please visit https://www.clipsal.com/Trade
       

      What size is the threaded rod of the Ladder Stacking Kit, and will ours fit on other manufacturer's ladder?

      Issue:
      Customers ask for the thread size and dimensions of the threaded rod. They may also ask if the Ladder Stacking Kit can be used on other manufacturer's ladder.

      Product Line:
      NetShelter SX

      Environment:
      All versions and serial ranges.

      Cause:
      Customers need to know the spec of the threaded rod for installation design.

      Resolution:
      The threaded rod has 5/8"-11 coarse threads. The length is 12".
      The Ladder Stacking Kit will mount onto a ladder rail with the maximum dimensions of 1 1/4" tall x 1/2" thick.
      NOTE: Although this product is named Ladder Stacking Kit it is used to suspend a ladder. The ladder that's on top must be suspended, probably from above. This kit is then used to suspend another ladder underneath the first one.