C-Bus Din Rail Mounted Sweep Fan Control Relay, 1 Channel, 3M Modules

C-Bus Din Rail Mounted Sweep Fan Control Relay, 1 Channel, 3M Modules

C-Bus Din Rail Mounted Sweep Fan Control Relay, 1 Channel, 3M Modules

Item Number: L5501RFCP

Retail
$311.47
RRP (Inc. GST)

Product Dimensions

Width icon

Width210 mm

Height icon

Height75.5 mm

Depth icon

Depth66 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

C-Bus

Range

C-Bus

Product brand

Clipsal

Product or component type

relay

Device application

fan speed controller

Physical

Load type

inductive

Rated voltage

100-250 V AC 50/60 Hz

Number of channels

1

Local signalling

LED

Connector type

screw terminals

Device mounting

DIN rail

Width

210 mm

Height

75.5 mm

Depth

66 mm

IP degree of protection

IP20

REACh free of SVHC

Yes

EU RoHS Directive

Compliant

Toxic heavy metal free

Yes

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

 Pro-active China RoHS declaration (out of China RoHS legal scope)

Others

[Us] rated supply voltage

15...36 V DC

Nominal output power

350 W

Number of modules

3

Package 1 Weight

273 g

Package 1 Height

80 mm

Package 1 width

115 mm

Package 1 Length

155 mm

WEEE

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • Product Brochures

  • CAD Files and Packs

  • Technical Data Catalogues

  • Technical Leaflet

  • Installation Instruction

  • Specifications

  • Application Solutions

  • Corporate Marketing

Frequently Asked Questions

hide show

What is the CBUS shutter relay

 Part code is L5501RBCP

What is the code for a CBus curtain module

 It is L5501RBCP

What is the part code for the C-Bus Single Channel Shutter Relay for Blinds/curtains?

The part number is L5501RBCP

How do I determine if a fan is suitable to be used with the C-Bus fan relay unit

Any fan which is switched via a 3 wire capacitor (low, medium, common) will be acceptable

Can you have more than one fan controlled from a DLT?

You cannot natively control more than one fan. However implemention of multiple fans can be achieved through the use of logic, please contact Technical Support for a logic example.

Any logic examples are provided as is and are not able to be supported.

What is required for a Fan to be compatible with C-Bus?

For a fan to be compatible with C-Bus, it will require a 3 wire capacitor built for low and medium speeds.

This capacitor can then be wired into a L5501RFCP which will act on behalf of the rotary dial.

From there, a C-Bus switch can then be programmed to step through the speeds.

What is the part number of the wall mounting enclosure to suit L5501RBCP 1 channel C-Bus Blind/Curtain/Shutter relay?

5501RE is the part number of the wall mounting enclosure to suit  L5501RBCP 1 channel C-Bus Blind/Curtain/Shutter relay.
For further information, please visit
https://www.clipsal.com/Trade/Products/ProductDetail?catno=5501RE
User-added image
 

What are the power limitations on a shutter relay L5501RBCP?

The power limitations to the shutter relay L5501RBCP are a maximum load output of 24V DC, 24-240V AC and a maximum motor load of 2A.

Some of the key features for the L5501RBCP are:
  • DIN rail mounted, 2M wide
  • AC input impedance 80 kOhm at 1 kHz
  • Electrical isolation 3.75 kV RMS from C-Bus to mains
  • Maximum units per network 80
  • Load current rating 2 A (motor load)
  • Load voltage rating 24 V DC, 24 - 240 V AC
  • Warm up time 5 s
  • Network clock software selectable
  • Network burden software selectable
  • Class II switch
  • 4 kV rated impulse withstand voltage
  • 0 - 45 deg C operating temperature
  • 10 - 95% RH operating humidity
  • Mains terminals Accommodates 2 x 1.5 mmsq or 1 x 2.5 mmsq (2 x 15 AWG or 1 x 13 AWG)
For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=L5501RBCP
 

 

What is the code for a CBus 4 channel relay without power supply

 Part code L5504RVFP

What is the difference between L5508RVFP and L5508RVF?

L5508RVFP and L5508RVF are C-Bus DIN Rail Mounted Relay Units, 250V AC 10A 8 Channel, 12M modules wide. The only difference between the two is L5508RVFP does not come with C-Bus Power Supply and L5508RVF is with 200mA C-Bus internal Power Supply.
For further information, please visit:
https://www.clipsal.com/Trade/Products/ProductDetail?catno=L5508RVFP
https://www.clipsal.com/Trade/Products/ProductDetail?catno=L5508RVF

User-added image
User-added image

What is the power output limitations of the L5501RFCP C-bus Sweep fan control?

The fan load rating must not exceed 1.5Amps.
The L5501RFCP C-Bus Ceiling Sweep Fan Controller unit is a DIN rail mounted C-Bus output device that provides speed control for a ceiling sweep fan. The Fan Controller uses multiple relays and a dual capacitor block for speed selection.
Some of its key features are:
  • C-Bus current requirement 18 mA, powered from C-Bus network, does not provide power for the C-Bus network
  • Maximum units per network 100
  • Network clock software selectable
  • Network burden Software selectable when Unit Address is 001
  • AC input impedance 100 kOhm at 1 k Hz
  • Warm-up time 10 s
  • Electrical isolation 3.75 kV from C-Bus to mains
  • Input voltage for fan motor 100 V AC to 240 V AC; input circuit must have a suitable circuit breaker
  • Fan load rating 1.5 A
  • Switch duty type (S1) Continuous duty. Line and neutral are switched. Fan motor and neutral are switched
  • Speed control Capacitive; capacitor block supplied by fan manufacturer for Low and Medium speeds. High speed uses direct on-line (no capacitor in the circuit). Three unique fan speeds Low, Med and Hi and Off
  • Connectors C-Bus: 2 x RJ-45
  • Capacitor block: 3 x push button for one 1.5 mm²
  • Fan: 2 x screw type for one 1.5 mm² wire
  • Input Power: 2 x screw type for up to two 1.5 mm² Indicators Unit, C-Bus, 3 x Fan speed
  • Control Local override pushbutton, not illuminated
  • Class of switch Class II
  • Rated impulse withstand voltage 4 kV
  • Proof tracking index (PTI) 175
  • Pollution degree 2
  • Glow wire test (GWIT) Level 3, 850° C
  • Mounting type DIN rail, or wall or ceiling space mounting in the optional plastic enclosure; For indoor use only
  • Operating temperature 0° to 65° C
  • Humidity 10 to 95% RH, non condensing
For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=L5501RFCP
 

What are the individual preset levels or percentages for Blind Shutter Relays?

Depending on the scenario they are being used in, you can have three options based on 1, 2 or 3 button control

1 Button Control:
98% - Shutter Toggle Open/Close

2 Button Control:
1% - Close Toggle/Stop
99% - Open Toggle/Stop

3 Button Control:
0% - Close
100% - Open
2% - Stop

If you find that the opposite of what is expected to happen is happening, please confirm the polarity of the wiring
Show More