Gv2 GV3 Undervolt Trip 24V Rhs Mt

Gv2 GV3 Undervolt Trip 24V Rhs Mt

Gv2 GV3 Undervolt Trip 24V Rhs Mt

Item Number: GVAU025

Retail
$229.01
RRP (Inc. GST)

Product Dimensions

Width icon

Width18 mm

Height icon

Height89 mm

Depth icon

Depth66 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

  • TeSys GV2
  • TeSys GV3
    • Range

      TeSys

      Product or component type

      undervoltage release

      Sustainable offer status

      Green Premium product

      Warranty

      18 months

      Physical

      Range compatibility

    • GV2ME
    • GV2LE
    • GV2L
    • GV2P
    • GV3L
    • GV3P
      • Connections - terminals

      • screw clamp terminals 1 cable(s) 1-2.5 mm²solid
      • screw clamp terminals 2 cable(s) 1-2.5 mm²solid
      • screw clamp terminals 1 cable(s) 0.75-2.5 mm²flexible without cable end
      • screw clamp terminals 2 cable(s) 0.75-2.5 mm²flexible without cable end
      • screw clamp terminals 1 cable(s) 0.75-1.5 mm²flexible with cable end
      • screw clamp terminals 2 cable(s) 0.75-1.5 mm²flexible with cable end
        • Mechanical durability

        • 10000 cycles with GV3P and GV3L
        • 30000 cycles with GV2ME and GV2P
          • Quantity per set

            set of 10

            Height

            89 mm

            Width

            18 mm

            Depth

            66 mm

            Net weight

            0.105 kg

            REACh free of SVHC

            Yes

            EU RoHS Directive

            Compliant

            Toxic heavy metal free

            Yes

            Mercury free

            Yes

            RoHS exemption information

            Yes

            China RoHS Regulation

            X

            Environmental Disclosure

            ENVPEP111252EN

            Others

            Device short name

            GVAU

            [Uc] control circuit voltage

            24 V AC 50 Hz

            Control circuit voltage limits

            0.85...1.1 Un

            [Ui] rated insulation voltage

          • 690 V AC conforming to IEC 60947-1
          • 600 V AC conforming to UL 60947-4-1
          • 600 V AC conforming to CSA C22.2 No 60947-4-1
            • Threshold tripping voltage

              0.7...0.35 Un

              Inrush power in VA

              12-12 VA AC

              Inrush power in W

              8 W

              Hold-in power consumption in VA

              3.5-3.5 VA AC

              Hold-in power consumption in W

              1.1-1.1 W

              Operating time

              10...15 ms conforming to IEC 60947-1

              On-load factor

              100 %

              Tightening torque

              < 1.4 N.m on screw clamp terminals

              Compatibility code

              GVAU

              Unit Type of Package 1

              PCE

              Number of Units in Package 1

              1

              Package 1 Weight

              115 g

              Package 1 Height

              3.5 cm

              Package 1 width

              8.3 cm

              Package 1 Length

              9.2 cm

              Unit Type of Package 2

              S02

              Number of Units in Package 2

              42

              Package 2 Weight

              5.324 kg

              Package 2 Height

              15 cm

              Package 2 width

              30 cm

              Package 2 Length

              40 cm

              WEEE

              The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
              Show all specifications

              Documents & downloads

              hide show
              Filter items
              • All

              • CAD Files and Packs

              • Product Brochures

              • Technical Data Catalogues

              • Product Environmental

              • Installation Instruction

              • eTechPub

              Frequently Asked Questions

              hide show

              Can GVAU225 operate on 60 HZ?

              What is the catalog number for an external rotary handle for a GV7 manual starter ?

              Issue:
              GV7 Manual starter handle kit

              Product Line:
              Motor Starters and Protectors

              Environment:
              TeSys™ GV Manual Starters and Protectors

              Resolution:
              Use the GV7AP01 for a black handle with black legend or a GV7AP02 for a red handle with yellow legend.

              What is the equivalent of GV2AP01 and GV2AP02 rotary handle

              The equivalent of GV2AP01 and GV2AP02 rotary handles are GV2APN01          
               and GV2APN02 respectively.Refer attached file for more details

              Do we offer a cable operated handle mechanism for the GV7 starters?

              Issue:
              They need to mount the GV7 back inside the enclosure and need a handle mechanism with a cable to operate. 

              Product line:
              Tesys GV7 manual motor controller

              Environment:
              all

              Cause:
              n/a

              Resolution:
              The GV7 do not offer a cable operator.  Consider switching to a Powerpact circuit breaker which offers the cable mechanism kits.

              What are the wire or cable sizes required for the GV7RE and GV7RS starters?

              Issue:
              What are the wire or cable sizes required for the GV7RE and GV7RS starters?

              Product Line:
              Manual starters and protectors

              Environment:
              Tesys GV2,GV3 and GV7

              Cause:
              Wiring and installation of starters

              Resolution:
              For the GV7R*20 thru R*150 use a mechanical lug kit / clip-on connectors for 1 #14-3/0 GV7AC021 (sold in lots of 3) . For the GV7R*220 use a kit for 1 #14-350mcm GV7AC022 (sold in lots of 3).

              GV2P disconnect options

              Issue:
              What is the product number for a complete through-the-door disconnect device for a GV2P

              Product Line:
              GV2P Manual Starters and Protectors

              Environment:
              US product

              Cause:
              Digest 176 is unclear as to what is a complete mechanism with shaft and handle

              Resolution:
              There are three devices which include mechanism, shaft and handle:
              GV2APN01 has a NEMA 1, 12 rating and is black
              GV2APN02 has a NEMA 1, 12 rating and is red/yellow
              GV2APN04 has a NEMA 3R, 4, 4X rating and is red/yellow

              Will the accessories used for the GV3ME06 through GV3ME63 work with the GV3ME80?

              Product Line:
              GV3 manual motor starters, IEC

              Resolution:
              The standard GV3 accessories will work on this device.

              What is the current rating of the GV1G02?

              Issue:
              GV1G02 electrical ratings

              Product Line:
              GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Selection

              Environment:
              Additional GV2 Wiring Accessories

              Resolution:
              25 amp maximum

              Can GVAE1, GVAE11 or GVAE20 be used with GV3 starters?

              Issue:
              Are the front mount auxiliary contacts GVAE1, GVEA11 and GVAE20 be used for GV3M devices?
               
              Product Line:

              Tesys GV Manual Starter and Protectors

              Environment:
              TeSys GV, GVA, GV2, GV3P

              Resolution:
              These auxiliary contacts can only be used with the rotary handled GV3P devices. They cannot be applied with the pushbutton GV3M devices.

              Can the GV* starters be used on 50 hertz applications?

              Issue:
              GV* Starter for 50/60hz application

              Product Line:
              Motor Starters and Protectors

              Environment:
              PowerPact™ Manual Starters

              Resolution:
              Yes, these starters are rated for 50/60 hertz.

              This applies to all GV2M, GV2ME, GV2P, GV3M, GV3ME devices.

              What is the wattage on the DL1BA and DL1BL bulbs used in the XVA indicating banks?

              Issue:
              What is the power in watts on the DL1BA and DL1BL  bulbs used in the XVA indicating banks?

              Product Line:
              Harmony Tower Lights

              Environment:
              Harmony XB4/ZB4 Metal Push Buttons

              Cause:
              Product Features

              Resolution:
              AC or DC
              2.5W 12V DL1BA012
              4W 24V DL1BA024
              6.5W 24V DL1BL024
              4W 48V DL1BA048
              7W 110V DL1BA110
              7W 120V DL1BL120
              5W 160V DL1BA160
              6W 260V DL1BA260

              Does the GV2MC02 include the sealing cover GV2E01?

              Issue:
              Determining contents of the GV2MC02 

              Product Line:
              GV type Tesys  manual starters.

              Environment:
              Tesys manual starters

              Resolution:
              Yes it does.
               
              Show More