TeSys GV2 & TeSys GV3 & TeSys U, Universal Retrofit

TeSys GV2 & TeSys GV3 & TeSys U, Universal Retrofit

TeSys GV2 & TeSys GV3 & TeSys U, Universal Retrofit

Item Number: GVAPP1

Retail
$32.99
RRP (Inc. GST)

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

  • TeSys GV2
  • TeSys GV3
  • TeSys U
    • Range

      TeSys

      Product or component type

      universal retrofit

      Product compatibility

    • GV2APN01
    • GV2APN02
    • GV2APN03
    • GV2APN04
    • GV3APN01
    • GV3APN02
    • GV3APN03
    • GV3APN04
    • LU9APN21
    • LU9APN22
    • LU9APN24
      • Sustainable offer status

        Green Premium product

        Warranty

        18 months

        Physical

        Net weight

        0.16 kg

        EU RoHS Directive

        Compliant

        Mercury free

        Yes

        RoHS exemption information

        Yes

        China RoHS Regulation

        Product out of China RoHS scope. Substance declaration for your information

        Environmental Disclosure

        ENVPEP111252EN

        Others

        Device short name

        GVAP

        Accessory / separate part category

        control accessory

        Compatibility code

        GVAP

        Unit Type of Package 1

        PCE

        Number of Units in Package 1

        1

        Package 1 Weight

        28 g

        Package 1 Height

        0.1 cm

        Package 1 width

        1 cm

        Package 1 Length

        3.6 cm

        Unit Type of Package 2

        S03

        Number of Units in Package 2

        80

        Package 2 Weight

        2.725 kg

        Package 2 Height

        30 cm

        Package 2 width

        30 cm

        Package 2 Length

        40 cm

        WEEE

        The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
        Show all specifications

        Documents & downloads

        hide show
        Filter items
        • All

        • CAD Files and Packs

        • Product Brochures

        • Technical Data Catalogues

        • Installation Instruction

        • eTechPub

        Frequently Asked Questions

        hide show

        GV2P disconnect options

        Issue:
        What is the product number for a complete through-the-door disconnect device for a GV2P

        Product Line:
        GV2P Manual Starters and Protectors

        Environment:
        US product

        Cause:
        Digest 176 is unclear as to what is a complete mechanism with shaft and handle

        Resolution:
        There are three devices which include mechanism, shaft and handle:
        GV2APN01 has a NEMA 1, 12 rating and is black
        GV2APN02 has a NEMA 1, 12 rating and is red/yellow
        GV2APN04 has a NEMA 3R, 4, 4X rating and is red/yellow

        Does the GVAE11 auxilliary contact block fit the GV2ME?

        The GVAE11 auxilliary contact block fits in the top of the GV2ME and GV2P/L

        What is the equivalent of GV2AP01 and GV2AP02 rotary handle

        The equivalent of GV2AP01 and GV2AP02 rotary handles are GV2APN01          
         and GV2APN02 respectively.Refer attached file for more details

        What is the length of the shaft in the GV3APN02 kit?

         The shaft included in the GV3APN02 kit is a GVAPA1. It has a length of 315 mm.
         

        How many of GVAN11 side Auxiliary can be put on GV3 circuit breakers?

        Maximum of 2 sides mounted Auxiliary can be used with GV3 circuit breaker.
         

        What is the part name for the side mount auxiliary contacts 1 N/C , 1N/O for GV3P40?

        The part name for the side mount auxiliary contacts is - GVAN11.

        Can a GV2AF3 or GV2AF4 interconnection block work on a contactor with a DC coil?

        Issue:
        Mounting adaptor for GV2 and LC1D contactor

        Product Line:
        Motor Starters and Protectors

        Environment:
        TeSys GV Manual Starter and Protectors
        Tesys D Contactors
         
        Resolution:
        The GV2AF3 clip has to be moved to the DC position to accommodate the contactor with a DC coil.

        Are explosion proof enclosures available for GV manual motor starters.

        Issue:
        NEMA 7/9 rated enclosure for GV manual motor starters

        Product Line:
        Tesys GV Motor Starters and Protectors

        Environment:
        TeSys™ GV Manual Starters and Protectors

        Resolution:
        No hazardous duty enclosures are available for the GV product line.
        For explosion proof applications consider the Class 2510 Type M or Type T offering.

        Will GVAN11 give fault indication?

        No, the GVAN11 will only give status of "off" or "on" of the Breaker, but no indication of "fault".

        The GVAD1010 and GVAD0110 will give fault indication and status of "off" or "on" of the breaker.

        The GVAM11 will give short circuit contact signaling .

        For further information please visit https://www.schneider-electric.com.au.

        What is the part number to get 2 extra N/C auxillary contacts on to a GV Motor C/B?

        The part numbers to get 2 extra N/C auxillary contacts on to a GV Motor C/B are - GVAE11 & GVAN11
        For further information , visit links below:-
        https://www.schneider-electric.com.au/en/search/GVAE11
        https://www.schneider-electric.com.au/en/search/GVAN11
         

        What is the catalog number for an external rotary handle for a GV7 manual starter ?

        Issue:
        GV7 Manual starter handle kit

        Product Line:
        Motor Starters and Protectors

        Environment:
        TeSys™ GV Manual Starters and Protectors

        Resolution:
        Use the GV7AP01 for a black handle with black legend or a GV7AP02 for a red handle with yellow legend.

        Can GVAE1, GVAE11 or GVAE20 be used with GV3 starters?

        Issue:
        Are the front mount auxiliary contacts GVAE1, GVEA11 and GVAE20 be used for GV3M devices?
         
        Product Line:

        Tesys GV Manual Starter and Protectors

        Environment:
        TeSys GV, GVA, GV2, GV3P

        Resolution:
        These auxiliary contacts can only be used with the rotary handled GV3P devices. They cannot be applied with the pushbutton GV3M devices.