MASTER YOUR CASTLE with your new build or reno project
Enter competition
GV4PE02N6

GV4PE02S6

Motor Breaker GV4PE Thermal/Magnetic 2A 100kA Lug Terminal

GV4PE02N6
Colour:
Colour: Per UOM Std.
  • 1 PCE
Added to cart
Successfully added, you can view your cart here

Key Features & Specifications

hide show
  • Everlink power connections with patented creep-compensation technology
  • One size up to 55KW at 415 VAC
  • Wide overload setting for easy selection and reducing the stock
  • 3 level short circuit breaking capacity (25KA, 50KA and 100KA)
  • Robust Rotary handle (Direct, side and extended)
  • Green Premium ecoLabel
Range
TeSys
Product name
TeSys GV4
Device short name
GV4PE
Product or component type
circuit breaker
Device application
motor
Protection type
  • ground fault protection
  • phase loss
  • short-circuit
  • phase unbalance
  • overload
  • short time short-circuit protection
    • Utilisation category
      category A
      Suitability for isolation
      yes conforming to IEC 60947-1
      Poles description
      3P
      [Ue] rated operational voltage
      690 V AC 50/60 Hz conforming to IEC 60947-2
      [In] rated current
      2 A
      Trip unit technology
    • thermal-magnetic
    • electronic
      • Thermal protection adjustment range
        0.8-2 A
        Motor tripping class
      • 10
      • 20
        • Breaking capacity
        • Icu 120 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
        • Icu 100 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
        • Icu 70 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
        • Icu 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
        • Icu 18 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
        • 100 kA at 208Y/120 V AC 50/60 Hz conforming to UL 60947
        • 100 kA at 240 V AC 50/60 Hz conforming to UL 60947
        • 65 kA at 480Y/277 V AC 50/60 Hz conforming to UL 60947
        • Icu 10 kA at 660...690 V AC 50/60 Hz conforming to IEC 60947-2
        • 25 kA at 600Y/347 V AC 50/60 Hz conforming to UL 60947
          • [Ics] rated service breaking capacity
          • 120 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
          • 100 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
          • 70 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
          • 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
          • 18 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
          • 2.5 kA at 660...690 V AC 50/60 Hz conforming to IEC 60947-2
            • [Uimp] rated impulse withstand voltage
              8 kV conforming to IEC 60947-2
              [Ui] rated insulation voltage
              800 V conforming to IEC 60947-2
              Mechanical durability
              40000 cycles
              Electrical durability
            • 40000 cycles for AC-3 at 440 V In/2
            • 40000 cycles for AC-3 at 440 V In
              • Motor power kW
              • 0.25-0.25 kW at 400...415 V AC 50/60 Hz
              • 0.37-0.37 kW at 400...415 V AC 50/60 Hz
              • 0.55-0.55 kW at 400...415 V AC 50/60 Hz
              • 0.75-0.75 kW at 400...415 V AC 50/60 Hz
              • 0.37-0.37 kW at 500 V AC 50/60 Hz
              • 0.55-0.55 kW at 500 V AC 50/60 Hz
              • 0.75-0.75 kW at 500 V AC 50/60 Hz
              • 1.1-1.1 kW at 500 V AC 50/60 Hz
              • 0.55-0.55 kW at 660...690 V AC 50/60 Hz
              • 0.75-0.75 kW at 660...690 V AC 50/60 Hz
              • 1.1-1.1 kW at 660...690 V AC 50/60 Hz
              • 1.5-1.5 kW at 660...690 V AC 50/60 Hz
                • Control type
                  toggle
                  Rotary handle padlocking
                  with a lock accessory
                  Number of slots
                • 1 slot(s) for alarm switch for fault signalling contact, plug-in
                • 1 slot(s) for voltage release for electrical remote tripping, plug-in
                • 1 slot(s) for auxiliary switch for open/close contact, plug-in
                  • Local signalling
                    presence of auxiliary contacts: flag (green)
                    Standards
                  • CSA C22.2 No 60947-4-1
                  • EN/IEC 60947-2
                  • UL 60947-4-1
                  • EN/IEC 60947-4-1
                    • Product certifications
                      IEC
                      Quality labels
                      CE
                      Mounting mode
                    • by screws
                    • by clips
                      • Mounting support
                      • plate
                      • 35 mm symmetrical DIN rail
                      • 75 mm symmetrical DIN rail
                        • Connections - terminals
                          lugs-ring terminals
                          Connection pitch
                          27 mm
                          Tightening torque
                        • 9-9 N.m for 16-95 mm²
                        • 5-5 N.m for 1.5-10 mm²
                          • Width
                            81 mm
                            Height
                            155 mm
                            Depth
                            116 mm
                            Net weight
                            1.45 kg
                            Ambient air temperature for storage
                            -50-85 °C
                            Ambient air temperature for operation
                            -25-70 °C
                            Operating altitude
                          • 0...2000 m without derating
                          • 2000...5000 m with derating
                            • IP degree of protection
                              IP40 front face conforming to IEC 60529
                              IK degree of protection
                              IK07 conforming to IEC 62262
                              Pollution degree
                              3 conforming to IEC 60947-1
                              Tropicalisation
                              2 conforming to IEC 68-2
                              Mechanical robustness
                            • vibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6
                            • vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6
                            • shocks: 15 gn 11 ms conforming to IEC 60068-2-27
                              • Sustainable offer status
                                Green Premium product
                                REACh Regulation
                                Reference contains Substances of Very High Concern above the threshold
                                EU RoHS Directive
                                Pro-active compliance (Product out of EU RoHS legal scope)
                                Mercury free
                                Yes
                                RoHS exemption information
                                Yes
                                China RoHS Regulation
                                Product out of China RoHS scope. Substance declaration for your information
                                Environmental Disclosure
                                ENVPEP1704004EN
                                Circularity Profile
                                ENVEOLI1704004EN
                                WEEE
                                The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                                Warranty
                                18 months