TeSys GV4P - thermal magnetic motor breaker 2A to 115A - lug connection - rotary handle

Motor Breaker GV4P Thermal/Magnetic 50A 25kA Lug Terminal

Catalogue Number: GV4P50B6
TeSys GV4P - thermal magnetic motor breaker 2A to 115A - lug connection - rotary handle
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Range
TeSys
Product name
TeSys GV4
Device short name
GV4P
Product or component type
circuit breaker
Device application
motor protection
Protection type
  • overload
  • short time short-circuit protection
  • phase unbalance
  • phase loss
  • ground fault protection
  • short-circuit
    • Utilisation category
      category A
      Suitability for isolation
      yes conforming to IEC 60947-1
      Poles description
      3P
      [Ue] rated operational voltage
      690 V AC 50/60 Hz conforming to IEC 60947-2
      [In] rated current
      50 A
      Trip unit technology
    • thermal-magnetic
    • electronic
      • Magnetic tripping current
        850-850 A
        [Isd] short-time pick-up adjustment range
        13 x Ir
        Thermal protection adjustment range
        20-50 A
        Motor tripping class
      • 10
      • 20
        • Phase failure sensitivity
          yes conforming to IEC 60947-4-1
          Breaking capacity
        • Icu 50 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
        • Icu 25 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
        • Icu 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
        • Icu 10 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
        • 35 kA at 208Y/120 V AC 50/60 Hz conforming to UL 60947
        • 35 kA at 240 V AC 50/60 Hz conforming to UL 60947
        • 18 kA at 480Y/277 V AC 50/60 Hz conforming to UL 60947
        • 14 kA at 600Y/347 V AC 50/60 Hz conforming to UL 60947
          • [Ics] rated service breaking capacity
          • 50 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
          • 25 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
          • 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
          • 10 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
            • [Uimp] rated impulse withstand voltage
              [Ui] rated insulation voltage
              800 V conforming to IEC 60947-2
              Mechanical durability
              40000 cycles
              Electrical durability
            • 20000 cycles for AC-3 at 440 V In/2
            • 10000 cycles for AC-3 at 440 V In
              • Motor power kW
              • 11-11 kW at 400...415 V AC 50/60 Hz
              • 15-15 kW at 500 V AC 50/60 Hz
              • 18.5-18.5 kW at 660...690 V AC 50/60 Hz
              • 15-15 kW at 400...415 V AC 50/60 Hz
              • 18.5-18.5 kW at 400...415 V AC 50/60 Hz
              • 22-22 kW at 400...415 V AC 50/60 Hz
              • 18.5-18.5 kW at 500 V AC 50/60 Hz
              • 22-22 kW at 500 V AC 50/60 Hz
              • 30-30 kW at 500 V AC 50/60 Hz
              • 22-22 kW at 660...690 V AC 50/60 Hz
              • 30-30 kW at 660...690 V AC 50/60 Hz
              • 37-37 kW at 660...690 V AC 50/60 Hz
              • 45-45 kW at 660...690 V AC 50/60 Hz
                • Control type
                  rotary handle
                  Rotary handle padlocking
                  padlock in OFF or ON position
                  Number of slots
                • 1 slot(s) for alarm switch for fault signalling contact, plug-in
                • 1 slot(s) for voltage release for electrical remote tripping, plug-in
                • 1 slot(s) for auxiliary switch for open/close contact, plug-in
                  • Local signalling
                  • flashing LED (green)ready:
                  • LED (red)alarm (T° >95%):
                  • green indicatorpresence of auxiliary contacts:
                    • Standards
                    • EN/IEC 60947-2
                    • UL 60947-4-1
                    • EN/IEC 60947-4-1
                    • CSA C22.2 No 60947-4-1
                      • Product certifications
                      • IEC
                      • UL
                      • CSA
                      • CCC
                      • EAC
                      • ATEX
                      • EU-RO MR
                        • Quality labels
                          CE
                          Mounting mode
                        • by clips
                        • by screws
                          • Mounting support
                          • plate
                          • 75 mm symmetrical DIN rail
                          • 35 mm symmetrical DIN rail
                            • Connections - terminals
                              lugs-ring terminals
                              Connection pitch
                              27 mm
                              Tightening torque
                            • 9-9 N.m for 16-95 mm²
                            • 5-5 N.m for 1.5-10 mm²
                              • Width
                                81 mm
                                Height
                                155 mm
                                Depth
                                165 mm
                                Net weight
                                1.6 kg
                                Ambient air temperature for storage
                                -50-85 °C
                                Ambient air temperature for operation
                                -25-70 °C
                                Operating altitude
                              • 0...2000 m without derating
                              • 2000...5000 m with derating
                                • IP degree of protection
                                  IP40 front face conforming to IEC 60529
                                  IK degree of protection
                                  IK07 conforming to IEC 62262
                                  Pollution degree
                                  3 conforming to IEC 60947-1
                                  Tropicalisation
                                  2 conforming to IEC 68-2
                                  Mechanical robustness
                                • vibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6
                                • vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6
                                • shocks: 15 gn 11 ms conforming to IEC 60068-2-27
                                  • Sustainable offer status
                                    Green Premium product
                                    EU RoHS Directive
                                    Compliant
                                    Mercury free
                                    Yes
                                    RoHS exemption information
                                    Yes
                                    China RoHS Regulation
                                    Product out of China RoHS scope. Substance declaration for your information
                                    Environmental Disclosure
                                    ENVPEP1704004EN
                                    Circularity Profile
                                    ENVEOLI1704004EN
                                    WEEE
                                    The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                                    Warranty
                                    18 months

                                    Frequently Asked Questions

                                    hide show

                                    what's the difference between the GV3P50 and GV3P501

                                    they are the same Device but the P50 has everlink terminals on top and bottom and the P501 has everlink terminals on top and direct connection on the bottom