TeSys GV4P - thermal magnetic motor breaker 2A to 115A - EverLink connection - rotary handle
GV4P07N
TeSys GV4P - thermal magnetic motor breaker 2A to 115A - EverLink connection - rotary handle
GV4P07N

Motor Breaker GV4P Thermal/Magnetic 7A 50kA Everlink Terminal

Catalogue Number: GV4P07N
TeSys GV4P - thermal magnetic motor breaker 2A to 115A - EverLink connection - rotary handle
GV4P07N
TeSys GV4P - thermal magnetic motor breaker 2A to 115A - EverLink connection - rotary handle
GV4P07N
Retail
$1,911.15
RRP (Inc. GST)

Specifications

hide show
Range
TeSys
Product name
TeSys GV4
Device short name
GV4P
Product or component type
circuit breaker
Device application
motor protection
Protection type
  • phase loss
  • overload
  • ground fault protection
  • phase unbalance
  • short time short-circuit protection
  • short-circuit
    • Utilisation category
      category A
      Suitability for isolation
      yes conforming to IEC 60947-1
      Poles description
      3P
      [Ue] rated operational voltage
      690 V AC 50/60 Hz conforming to IEC 60947-2
      [In] rated current
      7 A
      Trip unit technology
    • electronic
    • thermal-magnetic
      • Magnetic tripping current
        119-119 A
        [Isd] short-time pick-up adjustment range
        13 x Ir
        Thermal protection adjustment range
        2.9-7 A
        Motor tripping class
      • 10
      • 20
        • Phase failure sensitivity
          yes conforming to IEC 60947-4-1
          Breaking capacity
        • Icu 100 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
        • Icu 50 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
        • Icu 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
        • Icu 15 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
        • 65 kA at 208Y/120 V AC 50/60 Hz conforming to UL 60947
        • 65 kA at 240 V AC 50/60 Hz conforming to UL 60947
        • 35 kA at 480Y/277 V AC 50/60 Hz conforming to UL 60947
        • Icu 8 kA at 660...690 V AC 50/60 Hz conforming to IEC 60947-2
        • Icu 25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
        • 18 kA at 600Y/347 V AC 50/60 Hz conforming to UL 60947
          • [Ics] rated service breaking capacity
          • 100 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
          • 50 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
          • 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
          • 25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
          • 15 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
          • 2 kA at 660...690 V AC 50/60 Hz conforming to IEC 60947-2
            • [Uimp] rated impulse withstand voltage
              [Ui] rated insulation voltage
              800 V conforming to IEC 60947-2
              Mechanical durability
              40000 cycles
              Electrical durability
            • 40000 cycles for AC-3 at 440 V In/2
            • 40000 cycles for AC-3 at 440 V In
              • Motor power kW
              • 1.5-1.5 kW at 400...415 V AC 50/60 Hz
              • 2.2-2.2 kW at 400...415 V AC 50/60 Hz
              • 2.5-2.5 kW at 400...415 V AC 50/60 Hz
              • 3-3 kW at 400...415 V AC 50/60 Hz
              • 2.2-2.2 kW at 500 V AC 50/60 Hz
              • 2.5-2.5 kW at 500 V AC 50/60 Hz
              • 3-3 kW at 500 V AC 50/60 Hz
              • 4-4 kW at 500 V AC 50/60 Hz
              • 3-3 kW at 660...690 V AC 50/60 Hz
              • 4-4 kW at 660...690 V AC 50/60 Hz
              • 5.5-5.5 kW at 660...690 V AC 50/60 Hz
              • 7.5-7.5 kW at 660...690 V AC 50/60 Hz
                • Control type
                  rotary handle
                  Rotary handle padlocking
                  padlock in OFF or ON position
                  Number of slots
                • 1 slot(s) for alarm switch for fault signalling contact, plug-in
                • 1 slot(s) for voltage release for electrical remote tripping, plug-in
                • 1 slot(s) for auxiliary switch for open/close contact, plug-in
                  • Local signalling
                  • flashing LED (green)ready:
                  • LED (red)alarm (T° >95%):
                  • green indicatorpresence of auxiliary contacts:
                    • Standards
                    • UL 60947-4-1
                    • CSA C22.2 No 60947-4-1
                    • EN/IEC 60947-2
                    • EN/IEC 60947-4-1
                      • Product certifications
                      • IEC
                      • UL
                      • CSA
                      • CCC
                      • EAC
                      • ATEX
                      • EU-RO MR
                        • Quality labels
                          CE
                          Mounting mode
                        • by screws
                        • by clips
                          • Mounting support
                          • 35 mm symmetrical DIN rail
                          • 75 mm symmetrical DIN rail
                          • plate
                            • Connections - terminals
                            • top 1 EverLink BTR screw connectors wire size 1.5-70 mm², solid
                            • top 1 EverLink BTR screw connectors wire size 1.5-50 mm², flexible
                            • bottom 1 EverLink BTR screw connectors wire size 2.5-95 mm², solid
                            • bottom 1 EverLink BTR screw connectors wire size 2.5-70 mm², flexible
                              • Connection pitch
                                27 mm
                                Wire stripping length
                                20 mm
                                Tightening torque
                              • 9-9 N.m for 16-95 mm²
                              • 5-5 N.m for 1.5-10 mm²
                                • Width
                                  81 mm
                                  Height
                                  155 mm
                                  Depth
                                  165 mm
                                  Net weight
                                  1.6 kg
                                  Ambient air temperature for storage
                                  -50-85 °C
                                  Ambient air temperature for operation
                                  -25-70 °C
                                  Operating altitude
                                • 0...2000 m without derating
                                • 2000...5000 m with derating
                                  • IP degree of protection
                                    IP40 front face conforming to IEC 60529
                                    IK degree of protection
                                    IK07 conforming to IEC 62262
                                    Pollution degree
                                    3 conforming to IEC 60947-1
                                    Tropicalisation
                                    2 conforming to IEC 68-2
                                    Mechanical robustness
                                  • vibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6
                                  • vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6
                                  • shocks: 15 gn 11 ms conforming to IEC 60068-2-27
                                    • Package 1 Weight
                                      1.95 kg
                                      Package 1 Height
                                      12.5 cm
                                      Package 1 width
                                      20.8 cm
                                      Package 1 Length
                                      22 cm
                                      Sustainable offer status
                                      Green Premium product
                                      EU RoHS Directive
                                      Compliant
                                      Mercury free
                                      Yes
                                      RoHS exemption information
                                      Yes
                                      China RoHS Regulation
                                      Product out of China RoHS scope. Substance declaration for your information
                                      Environmental Disclosure
                                      ENVPEP1704004EN
                                      Circularity Profile
                                      ENVEOLI1704004EN
                                      WEEE
                                      The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                                      PVC free
                                      Yes
                                      Halogen content performance
                                      Halogen free plastic parts product
                                      Warranty
                                      18 months

                                      Frequently Asked Questions

                                      hide show

                                      GV2P disconnect options

                                      Issue:
                                      What is the product number for a complete through-the-door disconnect device for a GV2P

                                      Product Line:
                                      GV2P Manual Starters and Protectors

                                      Environment:
                                      US product

                                      Cause:
                                      Digest 176 is unclear as to what is a complete mechanism with shaft and handle

                                      Resolution:
                                      There are three devices which include mechanism, shaft and handle:
                                      GV2APN01 has a NEMA 1, 12 rating and is black
                                      GV2APN02 has a NEMA 1, 12 rating and is red/yellow
                                      GV2APN04 has a NEMA 3R, 4, 4X rating and is red/yellow

                                      Can the GV* starters be used on 50 hertz applications?

                                      Issue:
                                      GV* Starter for 50/60hz application

                                      Product Line:
                                      Motor Starters and Protectors

                                      Environment:
                                      PowerPact™ Manual Starters

                                      Resolution:
                                      Yes, these starters are rated for 50/60 hertz.

                                      This applies to all GV2M, GV2ME, GV2P, GV3M, GV3ME devices.

                                      What is the part number for the spacer used with the LC*D09 through LC*D32 Contactor and the GV2AF3 combination block when the GV2 Motor Circuit Protector is mounted on din rail and the contactor hangs below it?

                                      Issue:
                                      Identifying the spacer part number for use with a LC*D, GV2AF3, and GV2 device combination

                                      Product Line:
                                      Contactors and Starters IEC

                                      Environment:
                                      Tesys D contactors and GV manual starters

                                      Cause:
                                      Spacer required

                                      Resolution:
                                      Compensation plate catalog number GV1F03, requires 2 pieces snap together.

                                      Can a GV2AF3 or GV2AF4 interconnection block work on a contactor with a DC coil?

                                      Issue:
                                      Mounting adaptor for GV2 and LC1D contactor

                                      Product Line:
                                      Motor Starters and Protectors

                                      Environment:
                                      TeSys GV Manual Starter and Protectors
                                      Tesys D Contactors
                                       
                                      Resolution:
                                      The GV2AF3 clip has to be moved to the DC position to accommodate the contactor with a DC coil.

                                      Are explosion proof enclosures available for GV manual motor starters.

                                      Issue:
                                      NEMA 7/9 rated enclosure for GV manual motor starters

                                      Product Line:
                                      Tesys GV Motor Starters and Protectors

                                      Environment:
                                      TeSys™ GV Manual Starters and Protectors

                                      Resolution:
                                      No hazardous duty enclosures are available for the GV product line.
                                      For explosion proof applications consider the Class 2510 Type M or Type T offering.

                                      Will the Compact NSX breaker be for sale in the USA or Canada?

                                      Issue:
                                      Where can I buy a Compact NSX breaker?

                                      Product Line:
                                      Circuit Breakers

                                      Cause:
                                      This breaker is popular overseas and there is interest in the US

                                      Resolution:
                                      There are no plans for a general release of the Compact NSX breaker line in North America, since the NSX is not UL Listed to UL489. (UL 489 is the standard commonly required in the US.) In the US, the Powerpact Circuit Breakers should be used (Powerpact breakers are UL, CSA and IEC-rated).

                                      If an existing piece of equipment has an NSX breaker which needs replacing, we have made a few catalog numbers available for sale in the US. The list of numbers will vary based upon need. Contact your local authorized Schneider Electric distributor for assistance on your specific NSX catalog number.

                                      For support on these breakers, Please see the following link to Global Operations where you can select other Countries:
                                      https://www2.schneider-electric.com/sites/corporate/en/support/operations/local-operations/local-operations.page