Specifications

hide show
Range of product
TeSys GV2
Range
TeSys
Product name
TeSys GV2
Device short name
GV2RT
Product or component type
circuit breaker
Device application
  • transformer
  • motor
    • Trip unit technology
      thermal-magnetic
      Poles description
      3P
      Network type
      AC
      Utilisation category
    • AC-3 conforming to IEC 60947-4-1
    • category A conforming to IEC 60947-2
      • Network frequency
        50/60 Hz conforming to IEC 60947-4-1
        Fixing mode
      • 35 mm symmetrical DIN rail: clipped
      • panel: screwed (with adaptor plate)
        • Operating position
          any position
          Motor power kW
        • 0.37-0.37 kW at 400/415 V AC 50/60 Hz motor protection high peak current
        • 0.37-0.37 kW at 440 V AC 50/60 Hz motor protection high peak current
        • 0.37-0.37 kW at 500 V AC 50/60 Hz motor protection high peak current
        • 0.18-0.18 kW at 220/230 V AC 50/60 Hz motor protection high peak current
        • 0.25-0.25 kW at 220/230 V AC 50/60 Hz motor protection high peak current
        • 0.55-0.55 kW at 400/415 V AC 50/60 Hz motor protection high peak current
        • 0.55-0.55 kW at 440 V AC 50/60 Hz motor protection high peak current
        • 0.55-0.55 kW at 500 V AC 50/60 Hz motor protection high peak current
        • 0.75-0.75 kW at 500 V AC 50/60 Hz motor protection high peak current
        • 0.75-0.75 kW at 690 V AC 50/60 Hz motor protection high peak current
        • 1.1-1.1 kW at 690 V AC 50/60 Hz motor protection high peak current
        • 0.4-0.4 kW at 230/240 V AC 50/60 Hz transformer protection
        • 0.63-0.63 kW at 400/415 V AC 50/60 Hz transformer protection
        • 1-1 kW at 440 V AC 50/60 Hz transformer protection
        • 1-1 kW at 500 V AC 50/60 Hz transformer protection
          • Breaking capacity
          • 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
          • 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
          • 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
          • 100 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
          • 100 kA Icu at 220/230 V AC 50/60 Hz conforming to IEC 60947-2
            • Control type
              toggle
              [In] rated current
              1.6 A
              Trip unit rating
              1-1.6 A
              Magnetic tripping current
              33-33 A
              [Ue] rated operational voltage
              690 V AC 50/60 Hz conforming to IEC 60947-2
              [Ui] rated insulation voltage
              690 V AC 50/60 Hz conforming to IEC 60947-2
              [Ith] conventional free air thermal current
              1.6 A conforming to IEC 60947-4-1
              [Uimp] rated impulse withstand voltage
              Power dissipation per pole
              2.5 W
              Mechanical durability
              100000 cycles
              Electrical durability
              100000 cycles for AC-3 at 440 V
              Maximum operating rate
              25 cyc/h
              Rated duty
              continuous conforming to IEC 60947-4-1
              Direct connector
              without
              Connections - terminals
            • screw clamp terminals 2 cable(s) 1-6 mm² solid
            • screw clamp terminals 2 cable(s) 1.5-6 mm² flexible without cable end
            • screw clamp terminals 2 cable(s) 1-4 mm² flexible with cable end
              • Tightening torque
                1.7 N.m on screw clamp terminals
                Suitability for isolation
                yes conforming to IEC 60947-1
                Height
                89 mm
                Width
                45 mm
                Depth
                78.5 mm
                Compatibility code
                GV2RT
                Standards
              • EN/IEC 60947-2
              • EN/IEC 60947-4-1
              • UL 60947-4-1
              • CSA C22.2 No 60947-4-1
                • Product certifications
                • IECEE CB Scheme
                • UL
                • CSA
                • CCC
                • EAC
                • BV
                • LROS (Lloyds register of shipping)
                  • Protective treatment
                    TH
                    IP degree of protection
                    IP20 conforming to IEC 60529
                    IK degree of protection
                    IK04
                    Ambient air temperature for operation
                    -20-60 °C
                    Ambient air temperature for storage
                    -40-80 °C
                    Fire resistance
                    960 °C conforming to IEC 60695-2-1
                    Operating altitude
                    2000 m
                    Sustainable offer status
                    Green Premium product
                    REACh Regulation
                    Reference contains Substances of Very High Concern above the threshold
                    EU RoHS Directive
                    Compliant
                    Mercury free
                    Yes
                    RoHS exemption information
                    Yes
                    China RoHS Regulation
                    Product out of China RoHS scope. Substance declaration for your information
                    Environmental Disclosure
                    ENVPEP121004EN
                    WEEE
                    The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                    California proposition 65
                    WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov
                    Warranty
                    18 months

                    Documents & downloads

                    hide show
                    Filter items
                    • All

                    • CAD Files and Packs

                    • Product Brochures

                    • Technical Data Catalogues

                    • Product Environmental

                    • Installation Instruction

                    • Data Bulletin

                    • eTechPub

                    Frequently Asked Questions

                    hide show

                    Can the GV* starters be used on 50 hertz applications?

                    Issue:
                    GV* Starter for 50/60hz application

                    Product Line:
                    Motor Starters and Protectors

                    Environment:
                    PowerPact™ Manual Starters

                    Resolution:
                    Yes, these starters are rated for 50/60 hertz.

                    This applies to all GV2M, GV2ME, GV2P, GV3M, GV3ME devices.

                    Is a padlocking device available for the GV2MC** type enclosures?

                    Issue:
                    Padlocking device for GV2MC Enclosures

                    Product Line:
                    TeSys GV2 Manual Starters and Protectors

                    Environment:
                    n/a

                    Resolution:
                    Yes, use the GV2V01. When this is padlocked, the starter is automatically in and will remain in the OFF position.

                    Can a GV2AF3 or GV2AF4 interconnection block work on a contactor with a DC coil?

                    Issue:
                    Mounting adaptor for GV2 and LC1D contactor

                    Product Line:
                    Motor Starters and Protectors

                    Environment:
                    TeSys GV Manual Starter and Protectors
                    Tesys D Contactors
                     
                    Resolution:
                    The GV2AF3 clip has to be moved to the DC position to accommodate the contactor with a DC coil.

                    Are explosion proof enclosures available for GV manual motor starters.

                    Issue:
                    NEMA 7/9 rated enclosure for GV manual motor starters

                    Product Line:
                    Tesys GV Motor Starters and Protectors

                    Environment:
                    TeSys™ GV Manual Starters and Protectors

                    Resolution:
                    No hazardous duty enclosures are available for the GV product line.
                    For explosion proof applications consider the Class 2510 Type M or Type T offering.

                    What is the replacement for a GV2M06

                    Use a GV2ME06.

                    What is the part number for the spacer used with the LC*D09 through LC*D32 Contactor and the GV2AF3 combination block when the GV2 Motor Circuit Protector is mounted on din rail and the contactor hangs below it?

                    Issue:
                    Identifying the spacer part number for use with a LC*D, GV2AF3, and GV2 device combination

                    Product Line:
                    Contactors and Starters IEC

                    Environment:
                    Tesys D contactors and GV manual starters

                    Cause:
                    Spacer required

                    Resolution:
                    Compensation plate catalog number GV1F03, requires 2 pieces snap together.

                    GV2P disconnect options

                    Issue:
                    What is the product number for a complete through-the-door disconnect device for a GV2P

                    Product Line:
                    GV2P Manual Starters and Protectors

                    Environment:
                    US product

                    Cause:
                    Digest 176 is unclear as to what is a complete mechanism with shaft and handle

                    Resolution:
                    There are three devices which include mechanism, shaft and handle:
                    GV2APN01 has a NEMA 1, 12 rating and is black
                    GV2APN02 has a NEMA 1, 12 rating and is red/yellow
                    GV2APN04 has a NEMA 3R, 4, 4X rating and is red/yellow

                    What is the equivalent of GV2AP01 and GV2AP02 rotary handle

                    The equivalent of GV2AP01 and GV2AP02 rotary handles are GV2APN01          
                     and GV2APN02 respectively.Refer attached file for more details

                    Protection Rating for GV2E01

                    Issue:
                    What rating does the GV2E01 give when used with the GV2MC01 or GV2MP01 enclosure

                    Product Line:
                    GV2 Enclosure Accessories

                    Environment:
                    US Product

                    Cause:
                    The IP rating is not specified in the Digest 176

                    Resolution:
                    When used with the GV2MC01 or GV2MP01, this kit will give a IP55 rating.

                    What is the difference between the GV2MC01 and the GV2MC02 enclosures?

                    Product Line:
                     
                    GV Manual Motor Starters and Protectors
                     
                    Resolution:
                    The GV2MC01 has an IP41 rating ( similar to Nema Type 1 ), whereas the GV2MC02 has an IP55 rating (similar to the Nema Type 12 ).

                     

                    What is the replacement for the GV1M06?

                    GV2ME06 is the replacement range.

                    What is the tripping class of the GV2 ME, GV2 P and GV2 RT?

                    The tripping class for GV2MExx, GV2Pxx, GV2RTxx circuit-breakers is class 10. Class 10 corresponds to a direct on-line motor starting time between 4 and 10 sec. Example of a tripping curve:




                     
                    Show More