Specifications

hide show
Range of product
TeSys GV2
Range
TeSys
Product name
TeSys GV2
Device short name
GV2RT
Product or component type
circuit breaker
Device application
  • motor
  • transformer
    • Trip unit technology
      thermal-magnetic
      Poles description
      3P
      Network type
      AC
      Utilisation category
    • AC-3 conforming to IEC 60947-4-1
    • category A conforming to IEC 60947-2
      • Network frequency
        50/60 Hz conforming to IEC 60947-4-1
        Fixing mode
      • 35 mm symmetrical DIN rail: clipped
      • panel: screwed (with adaptor plate)
        • Operating position
          any position
          Motor power kW
        • 0.06-0.06 kW at 220/230 V AC 50/60 Hz motor protection high peak current
        • 0.09-0.09 kW at 400/415 V AC 50/60 Hz motor protection high peak current
        • 0.09-0.09 kW at 440 V AC 50/60 Hz motor protection high peak current
        • 0.12-0.12 kW at 440 V AC 50/60 Hz motor protection high peak current
          • Breaking capacity
          • 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
          • 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
          • 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
          • 100 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
          • 100 kA Icu at 220/230 V AC 50/60 Hz conforming to IEC 60947-2
            • Control type
              toggle
              [In] rated current
              0.4 A
              Trip unit rating
              0.25-0.4 A
              Magnetic tripping current
              8-8 A
              [Ue] rated operational voltage
              690 V AC 50/60 Hz conforming to IEC 60947-2
              [Ui] rated insulation voltage
              690 V AC 50/60 Hz conforming to IEC 60947-2
              [Ith] conventional free air thermal current
              0.4 A conforming to IEC 60947-4-1
              [Uimp] rated impulse withstand voltage
              Power dissipation per pole
              2.5 W
              Mechanical durability
              100000 cycles
              Electrical durability
              100000 cycles for AC-3 at 440 V
              Maximum operating rate
              25 cyc/h
              Rated duty
              continuous conforming to IEC 60947-4-1
              Direct connector
              without
              Connections - terminals
            • screw clamp terminals 2 cable(s) 1-6 mm² solid
            • screw clamp terminals 2 cable(s) 1.5-6 mm² flexible without cable end
            • screw clamp terminals 2 cable(s) 1-4 mm² flexible with cable end
              • Tightening torque
                1.7 N.m on screw clamp terminals
                Suitability for isolation
                yes conforming to IEC 60947-1
                Height
                89 mm
                Width
                45 mm
                Depth
                78.5 mm
                Compatibility code
                GV2RT
                Standards
              • EN/IEC 60947-2
              • EN/IEC 60947-4-1
              • UL 60947-4-1
              • CSA C22.2 No 60947-4-1
                • Product certifications
                • IECEE CB Scheme
                • UL
                • CSA
                • CCC
                • EAC
                • BV
                • LROS (Lloyds register of shipping)
                  • Protective treatment
                    TH
                    IP degree of protection
                    IP20 conforming to IEC 60529
                    IK degree of protection
                    IK04
                    Ambient air temperature for operation
                    -20-60 °C
                    Ambient air temperature for storage
                    -40-80 °C
                    Fire resistance
                    960 °C conforming to IEC 60695-2-1
                    Operating altitude
                    2000 m
                    Sustainable offer status
                    Green Premium product
                    REACh Regulation
                    Reference contains Substances of Very High Concern above the threshold
                    EU RoHS Directive
                    Compliant
                    Mercury free
                    Yes
                    RoHS exemption information
                    Yes
                    China RoHS Regulation
                    Product out of China RoHS scope. Substance declaration for your information
                    Environmental Disclosure
                    ENVPEP121004EN
                    Circularity Profile
                    N/A
                    WEEE
                    The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                    California proposition 65
                    WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov
                    Warranty
                    18 months

                    Documents & downloads

                    hide show
                    Filter items
                    • All

                    • CAD Files and Packs

                    • Product Brochures

                    • Movies

                    • Technical Data Catalogues

                    • Catalog Page

                    • Technical Leaflet

                    • Installation Instruction

                    • Product Environmental

                    • Data Bulletin

                    • Handout

                    • Specification for Tender

                    • eTechPub

                    • Marine Certificate

                    • White Paper

                    • Certificates (MSDS)

                    • Declaration of Conformity

                    • Software - Released

                    Frequently Asked Questions

                    hide show

                    What is the part number for the spacer used with the LC*D09 through LC*D32 Contactor and the GV2AF3 combination block when the GV2 Motor Circuit Protector is mounted on din rail and the contactor hangs below it?

                    Issue:
                    Identifying the spacer part number for use with a LC*D, GV2AF3, and GV2 device combination

                    Product Line:
                    Digest 177 Section 18 : Contactors and Starters IEC

                    Environment:
                    Products sold and used in the United States

                    Cause:
                    Spacer required

                    Resolution:
                    Compensation plate catalog number GV1F03, requires 2 pieces snap together.
                     

                    Can the GV* starters be used on 50 hertz applications?

                    Issue:
                    GV* Starter for 50/60hz application

                    Product Line:
                    Motor Starters and Protectors

                    Environment:
                    PowerPact™ Manual Starters

                    Resolution:
                    Yes, these starters are rated for 50/60 hertz.

                    This applies to all GV2M, GV2ME, GV2P, GV3M, GV3ME devices.

                    Can I get the front membrane for a GV2MC03

                     The part code is a GV2E02

                    GV2P disconnect options

                    Issue:
                    What is the product number for a complete through-the-door disconnect device for a GV2P

                    Product Line:
                    GV2P Manual Starters and Protectors

                    Environment:
                    US product

                    Cause:
                    Digest 176 is unclear as to what is a complete mechanism with shaft and handle

                    Resolution:
                    There are three devices which include mechanism, shaft and handle:
                    GV2APN01 has a NEMA 1, 12 rating and is black
                    GV2APN02 has a NEMA 1, 12 rating and is red/yellow
                    GV2APN04 has a NEMA 3R, 4, 4X rating and is red/yellow

                    What is the equivalent of GV2AP01 and GV2AP02 rotary handle

                    The equivalent of GV2AP01 and GV2AP02 rotary handles are GV2APN01          
                     and GV2APN02 respectively.Refer attached file for more details

                    Protection Rating for GV2E01

                    Issue:
                    What rating does the GV2E01 give when used with the GV2MC01 or GV2MP01 enclosure

                    Product Line:
                    GV2 Enclosure Accessories

                    Environment:
                    US Product

                    Cause:
                    The IP rating is not specified in the Digest 176

                    Resolution:
                    When used with the GV2MC01 or GV2MP01, this kit will give a IP55 rating.

                    What is the difference between the GV2MC01 and the GV2MC02 enclosures?

                    Product Line:
                     
                    GV Manual Motor Starters and Protectors
                     
                    Resolution:
                    The GV2MC01 has an IP41 rating ( similar to Nema Type 1 ), whereas the GV2MC02 has an IP55 rating (similar to the Nema Type 12 ).

                     

                    What is the tripping class of the GV2 ME, GV2 P and GV2 RT?

                    The tripping class for GV2MExx, GV2Pxx, GV2RTxx circuit-breakers is class 10. Class 10 corresponds to a direct on-line motor starting time between 4 and 10 sec. Example of a tripping curve:




                     

                    Which enclosures can the GV2E01 sealing kit be used on?

                    Issue:
                    Which enclosures can the GV2E01 sealing kit be used on?

                    Product Line:
                    IEC Manual Starters/Protectors - GIC Product

                    Environment:
                    US Product

                    Cause:
                    Product Application

                    Resolution:
                    GV2MC01 and GV2MP01.

                    What is the hole size of the padlock provision for a GV2P starter?

                    ISSUE
                    What is the hole size of the padlock provision for a GV2P starter?

                    PRODUCT LINE
                    Integral starters

                    ENVIRONMENT
                    UL508E IEC starter

                    CAUSE
                    Fit

                    RESOLUTION
                    The padlock hole size is approximately 6mm on the GV2P starter. There are provisions for one padlock only. However, they can add a GV2V03 padlock attachment that will allow up to 6 padlocks for Lock out TAG out applications.

                    What would be the part number for an enclosure for the GV2ME20

                    What is the replacement for the GV1M06?

                    GV2ME06 is the replacement range.

                    Can a GV2/GV3 device be used on the output of a drive?

                    Issue:
                    Can a GV2/GV3 device be used on the output of a drive?
                     
                    Product Line:
                    Altivar drives

                    Environment:
                    All

                    Cause:
                    Installation

                    Resolution:
                    When the application is done with multi motors in parallel, it must use a thermal relay type TeSys LRD or LR3D (Class 10).
                    It is not recommended to use GV2's because the range frequency is only for 50/60Hz.
                    The TeSys LRD or LR3D work on the range frequency 0 to 400Hz.

                     

                    In regards to LAD5C11 LAD5C31 LAD5C12 LAD5C32 What is the maximum kW range that TeSys SoLink can be used with motor starter combination?

                    TeSys SoLink is the connection module to connect GV2/GV3 motor circuit breakers to associated contactors and can be used with GV2 / GV3 breakers up to 30kW.
                    For more information please visit the Link provided
                    https://www.schneider-electric.com.au/australia/en/products-services/offer-updates/news-viewer.page?c_filepath=/templatedata/Content/News/data/en/local/automation_control/general_information/2014/10/20141024_tesys_solink_integration_system.xml

                    What is the part number for a left side mount contact block with 1 N/C & 1 N/O contacts to go with motor start C/B ,GV2ME08?

                    The part  number for a left side mount contact block with 1 N/C & 1 N/O contacts to go with motor start C/B , GV2ME08 is - GVAN11
                    For further information , visit link below:-
                    https://www.schneider-electric.com.au/en/search/GVAN11
                    User-added image

                    What are the wire or cable sizes required for the GV7RE and GV7RS starters?

                    Issue:
                    What are the wire or cable sizes required for the GV7RE and GV7RS starters?

                    Product Line:
                    Manual starters and protectors

                    Environment:
                    Tesys GV2,GV3 and GV7

                    Cause:
                    Wiring and installation of starters

                    Resolution:
                    For the GV7R*20 thru R*150 use a mechanical lug kit / clip-on connectors for 1 #14-3/0 GV7AC021 (sold in lots of 3) . For the GV7R*220 use a kit for 1 #14-350mcm GV7AC022 (sold in lots of 3).

                    What is the part number for the side mount Auxiliary 1NO + 1NC contacts to fit GV2P10?

                    The part number for the 1NO+1NC side mount Auxiliary Contact Block to fit GV2 Motor Circuit Breakers is "GVAN11"

                    https://www.schneider-electric.com.au/en/search/GVAN11

                    Does the GV2MC02 include the sealing cover GV2E01?

                    Issue:
                    Determining contents of the GV2MC02 

                    Product Line:
                    GV type Tesys  manual starters.

                    Environment:
                    Tesys manual starters

                    Resolution:
                    Yes it does.