Thermal-magnetic motor circuit-breakers TeSys GV2ME  screw clamp terminals or lugs
TeSys motor circuit breaker GV2-ME
Thermal-magnetic motor circuit-breakers TeSys GV2ME  screw clamp terminals or lugs
TeSys motor circuit breaker GV2-ME

TeSys GV2 Circuit Breaker Thermal Magnetic, 0.1...0.16 A, Screw Clamp Terminals

Catalogue Number: GV2ME01
Thermal-magnetic motor circuit-breakers TeSys GV2ME  screw clamp terminals or lugs
TeSys motor circuit breaker GV2-ME
Thermal-magnetic motor circuit-breakers TeSys GV2ME  screw clamp terminals or lugs
TeSys motor circuit breaker GV2-ME
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Range of product
TeSys GV2
Range
TeSys
Product name
TeSys GV2
Device short name
GV2ME
Product or component type
circuit breaker
Device application
motor
Trip unit technology
thermal-magnetic
Poles description
3P
Network type
AC
Utilisation category
  • AC-3 conforming to IEC 60947-4-1
  • category A conforming to IEC 60947-2
    • Network frequency
      50/60 Hz conforming to IEC 60947-4-1
      Fixing mode
    • 35 mm symmetrical DIN rail: clipped
    • panel: screwed (with adaptor plate)
      • Operating position
        any position
        Breaking capacity
      • 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
      • 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
      • 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
      • 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
      • 100 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
        • [Ics] rated service short-circuit breaking capacity
        • 100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
        • 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
        • 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
        • 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
        • 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
          • Control type
            push-button
            [In] rated current
            0.16 A
            Trip unit rating
            0.1-0.16 A
            Magnetic tripping current
            1.5-1.5 A
            [Ue] rated operational voltage
            690 V AC 50/60 Hz conforming to IEC 60947-2
            [Ui] rated insulation voltage
            690 V AC 50/60 Hz conforming to IEC 60947-2
            [Ith] conventional free air thermal current
            0.16 A conforming to IEC 60947-4-1
            [Uimp] rated impulse withstand voltage
            Power dissipation per pole
            2.5 W
            Mechanical durability
            100000 cycles
            Electrical durability
            100000 cycles for AC-3 at 440 V
            Maximum operating rate
            25 cyc/h
            Rated duty
            continuous conforming to IEC 60947-4-1
            Direct connector
            without
            Connections - terminals
          • screw clamp terminals 2 cable(s) 1-6 mm² solid
          • screw clamp terminals 2 cable(s) 1.5-6 mm² flexible without cable end
          • screw clamp terminals 2 cable(s) 1-4 mm² flexible with cable end
            • Tightening torque
              1.7 N.m on screw clamp terminals
              Suitability for isolation
              yes conforming to IEC 60947-1
              Phase failure sensitivity
              yes conforming to IEC 60947-4-1
              Height
              89 mm
              Width
              45 mm
              Depth
              78.5 mm
              Net weight
              0.26 kg
              Compatibility code
              GV2ME
              Standards
            • EN/IEC 60947-2
            • EN/IEC 60947-4-1
            • CSA C22.2 No 60947-4-1
            • UL 60947-4-1
              • Product certifications
              • IECEE CB Scheme
              • UL
              • CSA
              • CCC
              • EAC
              • ATEX
              • BV
              • LROS (Lloyds register of shipping)
              • DNV-GL
              • RINA
                • Protective treatment
                  TH
                  IP degree of protection
                  IP20 conforming to IEC 60529
                  IK degree of protection
                  IK04
                  Ambient air temperature for operation
                  -20-60 °C
                  Ambient air temperature for storage
                  -40-80 °C
                  Fire resistance
                  960 °C conforming to IEC 60695-2-1
                  Operating altitude
                  2000 m
                  Sustainable offer status
                  Green Premium product
                  REACh Regulation
                  Reference contains Substances of Very High Concern above the threshold
                  EU RoHS Directive
                  Compliant
                  Mercury free
                  Yes
                  RoHS exemption information
                  Yes
                  China RoHS Regulation
                  Product out of China RoHS scope. Substance declaration for your information
                  Environmental Disclosure
                  ENVPEP121004EN
                  Circularity Profile
                  N/A
                  WEEE
                  The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                  California proposition 65
                  WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov
                  Warranty
                  18 months

                  Documents & downloads

                  hide show
                  Filter items
                  • All

                  • CAD Files and Packs

                  • Product Brochures

                  • Movies

                  • Technical Data Catalogues

                  • Catalog Page

                  • Technical Leaflet

                  • Installation Instruction

                  • Data Bulletin

                  • Product Environmental

                  • Handout

                  • Specification for Tender

                  • Certificates (MSDS)

                  • eTechPub

                  • Marine Certificate

                  • White Paper

                  • Declaration of Conformity

                  • Software - Released

                  Frequently Asked Questions

                  hide show

                  Can the GV* starters be used on 50 hertz applications?

                  Issue:
                  GV* Starter for 50/60hz application

                  Product Line:
                  Motor Starters and Protectors

                  Environment:
                  PowerPact™ Manual Starters

                  Resolution:
                  Yes, these starters are rated for 50/60 hertz.

                  This applies to all GV2M, GV2ME, GV2P, GV3M, GV3ME devices.

                  What is the part number for the spacer used with the LC*D09 through LC*D32 Contactor and the GV2AF3 combination block when the GV2 Motor Circuit Protector is mounted on din rail and the contactor hangs below it?

                  Issue:
                  Identifying the spacer part number for use with a LC*D, GV2AF3, and GV2 device combination

                  Product Line:
                  Digest 177 Section 18 : Contactors and Starters IEC

                  Environment:
                  Products sold and used in the United States

                  Cause:
                  Spacer required

                  Resolution:
                  Compensation plate catalog number GV1F03, requires 2 pieces snap together.
                   

                  Protection Rating for GV2E01

                  Issue:
                  What rating does the GV2E01 give when used with the GV2MC01 or GV2MP01 enclosure

                  Product Line:
                  GV2 Enclosure Accessories

                  Environment:
                  US Product

                  Cause:
                  The IP rating is not specified in the Digest 176

                  Resolution:
                  When used with the GV2MC01 or GV2MP01, this kit will give a IP55 rating.

                  Will the accessories used for the GV3ME06 through GV3ME63 work with the GV3ME80?

                  Product Line:
                  GV3 manual motor starters, IEC

                  Resolution:
                  The standard GV3 accessories will work on this device.

                  Which enclosures can the GV2E01 sealing kit be used on?

                  Issue:
                  Which enclosures can the GV2E01 sealing kit be used on?

                  Product Line:
                  IEC Manual Starters/Protectors - GIC Product

                  Environment:
                  US Product

                  Cause:
                  Product Application

                  Resolution:
                  GV2MC01 and GV2MP01.

                  What is the difference between the GV2MC01 and the GV2MC02 enclosures?

                  Product Line:
                   
                  GV Manual Motor Starters and Protectors
                   
                  Resolution:
                  The GV2MC01 has an IP41 rating ( similar to Nema Type 1 ), whereas the GV2MC02 has an IP55 rating (similar to the Nema Type 12 ).

                   

                  What is the replacement for a GV2M06

                  Use a GV2ME06.

                  Can I get the front membrane for a GV2MC03

                   The part code is a GV2E02

                  Can GVAE1, GVAE11 or GVAE20 be used with GV3 starters?

                  Issue:
                  Are the front mount auxiliary contacts GVAE1, GVEA11 and GVAE20 be used for GV3M devices?
                   
                  Product Line:

                  Tesys GV Manual Starter and Protectors

                  Environment:
                  TeSys GV, GVA, GV2, GV3P

                  Resolution:
                  These auxiliary contacts can only be used with the rotary handled GV3P devices. They cannot be applied with the pushbutton GV3M devices.

                  What would be the part number for an enclosure for the GV2ME20

                  GV2P disconnect options

                  Issue:
                  What is the product number for a complete through-the-door disconnect device for a GV2P

                  Product Line:
                  GV2P Manual Starters and Protectors

                  Environment:
                  US product

                  Cause:
                  Digest 176 is unclear as to what is a complete mechanism with shaft and handle

                  Resolution:
                  There are three devices which include mechanism, shaft and handle:
                  GV2APN01 has a NEMA 1, 12 rating and is black
                  GV2APN02 has a NEMA 1, 12 rating and is red/yellow
                  GV2APN04 has a NEMA 3R, 4, 4X rating and is red/yellow

                  What is the part number for a left side mount contact block with 1 N/C & 1 N/O contacts to go with motor start C/B ,GV2ME08?

                  The part  number for a left side mount contact block with 1 N/C & 1 N/O contacts to go with motor start C/B , GV2ME08 is - GVAN11
                  For further information , visit link below:-
                  https://www.schneider-electric.com.au/en/search/GVAN11
                  User-added image

                  What is the equivalent of GV2AP01 and GV2AP02 rotary handle

                  The equivalent of GV2AP01 and GV2AP02 rotary handles are GV2APN01          
                   and GV2APN02 respectively.Refer attached file for more details

                  What is the replacement for the GV1M06?

                  GV2ME06 is the replacement range.

                  Does the GVAE11 auxilliary contact block fit the GV2ME?

                  The GVAE11 auxilliary contact block fits in the top of the GV2ME and GV2P/L

                  What is the part number for the side mount Auxiliary contact block 1NO+1NC to suit GV2ME20?

                  The part number for the side mount Auxiliary Contact Block 1NO+1NC is "GVAN11"

                  https://www.schneider-electric.com.au/en/search/GVAN11

                   

                  Is there a Nema 1 enclosure for GV2ME14?

                  Issue:
                  What is the Nema 1 enclosure for GV2ME14?

                  Product Line:
                  Motor CBS & Overl. Relay

                  Environment:
                  CTR Optimum - IEC

                  Cause:
                  Enclosure

                  Resolution:
                  GV2MC01, Manual Starter Enclosure Type 1  IP41   answer

                  Does the GV2MC02 include the sealing cover GV2E01?

                  Issue:
                  Determining contents of the GV2MC02 

                  Product Line:
                  GV type Tesys  manual starters.

                  Environment:
                  Tesys manual starters

                  Resolution:
                  Yes it does.
                   

                  What does GV2MCK04 come with?

                  Enclosure GV2 MCK04 is fitted with a GV2 K04 mushroom head Emergency stop pushbutton as standard.

                  What is the code for a side AUX NO/NC for GV3ME80

                  GV3A01

                  Is there a thru the door external operator for the GV2ME and GV2P manual starters?

                  Issue:
                  What is the through-the-door operating mechanism for a GV2 Manual starter?

                  Product Line: 
                  Digest 177 Section 18 : Contactors and Starters - IEC

                  Environment:
                  North American Products

                  Cause:
                  Needs  the through-the-door operating mechanism for a GV2P Manual starter

                  Resolution:
                  There are no available kits for the GV2ME devices, only the GV2P devices (as listed below)
                  GV2APN01 - Nema 1 Black
                  GV2APN02 - Nema 1, 12 Red/Yellow
                  GV2APN04 - Nema 3R, 4, 4X Red/Yellow
                   

                  What is the replacement for the GV3ME40 motor starter?

                  The replacement code is the GV3P40
                  see link for data sheet:
                  https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=GV3P40
                   

                  What is the replacement for GV1M10?

                  The replacement for GV1M10 is GV2ME10.

                  GV2ME10 
                  TeSys GV2-Circuit breaker-thermal-magnetic - 4...6.3 A - screw clamp terminals 
                  For more information see: https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=GV2ME10

                  what's the difference between the GV3P50 and GV3P501

                  they are the same Device but the P50 has everlink terminals on top and bottom and the P501 has everlink terminals on top and direct connection on the bottom 

                  Do the GV manual motor starters have repair parts?

                   

                  Issue:     
                  Do the GV manual motor starters have repair parts?
                  Product Line:
                  GV manual motor protectors
                  Environment:
                  Products sold and used in the United States
                  Cause:
                  Need replacement parts for a GV2P GV2ME or GV3P starter

                  Resolution:

                  The GV line of manual starters does not have repair parts, the manual motor protector will have to be replaced in it's entirety.

                  How many auxiliary contact modules can be installed on the GV3ME__ manual starter?

                  Issue:
                  GV2 and GV3 number of aux switches?

                  Product Line:
                  Manual Starters

                  Environment: 
                  GV2 GV3 manual motor starters, IEC

                  Resolution:
                  One right side mount instantaneous auxiliary module and one internal mount fault signaling auxiliary module.

                  GV3ME80: How do you remove this device or take it off the DIN track?

                  Issue:
                  GV3ME80:  How do you remove this device or take it off the DIN track?

                  Product Line:
                  GV3 GV2 manual motor starter IEC

                  Environment:
                  North American Products

                  Resolution:
                  There are two springs in the top back portion of the device that you push down and at the same pull the bottom of the starter away from the track.


                   

                  What is the tripping class of the GV2 ME, GV2 P and GV2 RT?

                  The tripping class for GV2MExx, GV2Pxx, GV2RTxx circuit-breakers is class 10. Class 10 corresponds to a direct on-line motor starting time between 4 and 10 sec. Example of a tripping curve:




                   

                  Can I use a GV2 on a Altivar drive output?

                  Issue: 
                  Can I use a GV2 on a Altivar drive output?    

                  Product Line:
                  Alitvar Drives

                  Environment: 
                  ATV61, ATV212, ATV71, ATV630, ATV930, ATV32, ATV320, ATV312, ATV12, ATV660, ATV340  

                  Cause
                  Application has 2 motors on one drive wants separate disconnects.

                  Resolution: 
                  Not recommended on Altivar drives.
                  The GV2 have a fixed frequency range 50 to 60hz.
                  Possible intermittent trips used with the drive's PWM output.
                   

                  What is the part number for the side mount Auxiliary 1NO + 1NC contacts to fit GV2P10?

                  The part number for the 1NO+1NC side mount Auxiliary Contact Block to fit GV2 Motor Circuit Breakers is "GVAN11"

                  https://www.schneider-electric.com.au/en/search/GVAN11

                  What is included in the SR2PACKFU?

                  Issue:
                  What is included in the SR2PACKFU?

                  Product Line:
                  Zelio Smart Relays

                  Environment:
                  All Products

                  Cause:
                  Product Features

                  Resolution:

                  1 SR2B121FU Zelio logic relay
                  1 SR2USB01 cable
                  1 CD containing the latest version of ZelioSoft