clip mount pvc 1mm material

Mounting Clip, Moulded Front, 1mm

Catalogue Number: F30Z1
clip mount pvc 1mm material
Retail
$6.00
RRP (Inc. GST)
Colour White Electric (WE)
  • White Electric 1 PCE
  • Black 1 PCE

Specifications

hide show
Range of product
  • Standard
  • Sundry Series 30
    • Product brand
      Clipsal
      Mounting position
      horizontal and vertical
      Material
      PVC (polyvinyl chloride)
      Depth
      9 mm
      Length
      28 mm
      Width
      28 mm
      Unit Type of Package 1
      PCE
      Number of Units in Package 1
      1
      Package 1 Weight
      2 g
      Package 1 Height
      11 mm
      Package 1 width
      29 mm
      Package 1 Length
      29 mm
      Unit Type of Package 2
      BB1
      Number of Units in Package 2
      10
      Package 2 Weight
      0.036 kg
      Package 2 Height
      42 mm
      Package 2 width
      56 mm
      Package 2 Length
      118 mm
      Unit Type of Package 3
      CAR
      Number of Units in Package 3
      250
      Package 3 Weight
      1000 g
      Package 3 Height
      117 mm
      Package 3 width
      250 mm
      Package 3 Length
      310 mm
      Sustainable offer status
      Green Premium product
      EU RoHS Directive
      Pro-active compliance (Product out of EU RoHS legal scope)
      Mercury free
      Yes
      RoHS exemption information
      Yes
      China RoHS Regulation
      Product out of China RoHS scope. Substance declaration for your information
      Environmental Disclosure
      ENVPEP120506EN

      Documents & downloads

      hide show
      Filter items
      • All

      • Product Brochures

      • Technical Data Catalogues

      • Product Environmental

      • Corporate Marketing

      Frequently Asked Questions

      hide show

      What are the cutout dimensions of the F30Z4

      The F30Z4 suits 4mm thick steel of which any 30 series switch mechanism can be installed.
      the cut out is 25.4MM SQARED

      Is there a mounting clip to fit a 30 series mec to a panel?

      Yes, the F30Z1, F30Z1.5, or F30Z2 mounting clip suits 1, 1.5, or 2mm thick panels, or the B30GFZ will screw mount onto a surface.

      What parameter enables Catch on the Fly on the ATV21 and ATV212 series drives and how is it configured?

      Issue:
      What parameter enables Catch on the Fly on the ATV21 and ATV212 drives and how is it configured?

      Product Line:
      ATV21 and ATV212 drives.

      Environment:
      All models, All serial numbers.

      Cause:
      Clarification of function and how to configure it is needed.

      Resolution:

      Parameter F301 is used to configure the Catch on the Fly function. It has 5 possible settings:

      0 : Disabled
      1 : Enabled after brief power loss
      2: Enabled after run permissive is restored
      3: Enabled after a brief power loss or when run permissive is restored.
      4: Enabled at every startup.
       

      What is parameter F303 on the ATV212?

      Issue: 
      What is parameter F303 on the ATV212?
       
      Product Line:
      Altivar 212, Altivar 21
       
      Environment:
      All serial numbers
       
      Cause:
      N/A
       
      Resolution:
       F303 is the number of auto restarts the VFD will attempt, before locking on a fault.

      What is the meaning of OC1 fault in Altivar 21 Drive.

      The meaning of OC1 is over current during Acceleration. This fault appears when the motor is drawing excess current during acceleration. 

      Main probable causes of the fault:
       
      1         The acceleration time ACC is too short.
      2         The parameter Pt(Motor Control Mode) is incorrect.
      3         The drive is starting into a rotating load.
      4         A special motor (e.g. motor with small impedance) is used.
       
      Remedies:
       
      1         Increase the acceleration time
      2         Check the Pt (Motor Control Mode) parameter.
      3         Use F301 (Auto-Restart) and F302 (Coast Stop).
      4         Adjust the switching frequency F300.
      5         Set parameter F316(Switching Frequency Control Mode) to 1 or 3 (carrier frequency is decreased automatically).

      Is there an alternative to the 30RJ88SMA5 which will fit the F30Z1.5 clip?

      Yes it is the VDIB17735UWE.

      What is the part number for the adapter that lets 30 series mecs fit in a Prestige switch?

      The part number for the adapter that lets 30 series mecs fit in a Prestige switch is P30Z.

      What causes a OP3 fault on the ATV212 drive?

      Issue:
      What causes a OP3 fault on the ATV212 drive?

      Product Line:
      ATV21 ATV212 Altivar 212, Altivar 21 drives

      Environment:
      All models, All serial numbers

      Cause:
      OP3 fault is caused by overvoltage during constant speed operation.  This could be caused by abnormal fluctuation of the input voltage, Power networks greater than 200kVA, Power factor correction switching, SCR's switching on the Power network, the load regenerating into the drive or intermittent output phase loss. 

      Resolution:
      Confirm the motor nameplate information matches settings in the drive.  Confirm that the drive is sized correctly for the load and application.

      tYP = 2 (60Hz)
      tHr = motor FLA
      uLu = motor voltage
      F415 = motor FLA
      F417 = motor RPM

      Set F626 = 150% (increases the DC bus overvoltage threshold)
      Set AU1 = 0 (disables Auto ramp)

      Check the setting of Pt parameter (type of control) matches the application. 

      Check to make sure that the load is not spinning without drive's input (such as fan applications). If the load is spinning too fast in the wrong direction, the drive won't be able to catch it. If this is the case, try installing a mechanical brake to prevent this issue. 

      Check the setting of F301 Catch on the fly and try setting it to 4 (Each start)
       

      What is the part number for a 30 series switch mech , labelled ZONE 1 , 2 , 3 ?

      The part number for a 30 series switch mech , labelled ZONE 1 , 2 , 3 is - 30MZ1 , 30MZ2 , 30MZ3
      For further information , visit link below:-
      https://www.clipsal.com/Trade/search-results?q=30MZ1

      Can a 9001KA1 contact block be operated at 480V AC?

      Issue:
      Can a 9001KA1 contact block be operated at 480V AC?

      Product Line:
      Harmony Pushbuttons

      Environment:
      Harmony Pushbuttons

      Cause:
      Product Features

      Resolution:
      9001KA1 contact block rated up to 600V AC with continous ampere rating of 10 amps

       

      What can cause Err1 on ATV212 or ATV21 drive?

      Product Line:
      ATV212
      ATV21

      Environment:
      All environments

      Cause:
      Setting the Refrences to the same numer

      Resolution:
      This is a Speed Reference Fault.  It indicates an incorrect setting in F201, F202, F203, F204 OR F210, F211, F212, F213.

      Verify these parameters, and set them properly.
      Default settings are:
      F201 = 0%
      F202 = 0Hz
      F203 = 100%
      F204 = 50/60Hz

      F2010 = 0%
      F2011 = 0Hz
      F2012 = 100%
      F2013 = 50/60Hz
       

      Why does the ATV212 display a flashing StOP when changing from utility to generator power?

      Issue:
      Why does the ATV212 display a flashing StOP when changing from utility to generator power?

      Product Line:
      ATV21, ATV212

      Environment:
      All models and serial numbers.

      Cause:
      Momentary power loss removes output power to motor.

      Resolution:
      When F302, supply loss behavior, is enabled, then a brief loss of input power will cause the drive to remove power from the motor and display the flashing StOP alarm.  To restart operation, remove and reapply a new run command signal.  To disable this function and attempt to ride through the momentary loss of power, set F302 back to the factory default of 0.
      Show More