Are the windings double insulated from each other in the ABL6TS250U transformer?

The protection class of a transformer always related to the primary side.
If a PE is used, the device is automatically class1!
 
All our transformers are conforming Protection class 1, because they have an internal shield that must be connected to EARTH and so this leads to Class1.
We don't have any transformers in the offer that are conforming Protection class 2 (according to VDE 0106 1).
 
Regarding “double insulation” relates to the max. voltage that the transformer can withstand, the so called “Dielectric strength - Primary/secondary”
Here I can say, that Class1 requires 2kV and Class2 requires 4kV (which conforms to “double insulation”).
 
Our transformer ABL6TS250U meets the 4kV! (so this can be considered as "double insulation" even though the device itself is "Class1")
 
And last the Class F - is the electrical insulation class - meaning that the used insulation material can withstand a temperature up to 155 degrees Celsius.

Video: How to create Web Users for the PM5500 web page?

Product Line
PowerLogic™ PM5500 Series Power Meters

Environment
Web Management Interface

Resolution
Only a user account with Product Master privileges can edit and create users for the web page. The default username and password with Product Master privileges is User Name: user2 and Password: pass2. To setup a Web User or other logins with Web Master or Product Master privileges watch the video or follow the steps below.

  1. Login to the web page by entering the meter's IP address in the browsers address bar.
  2. An "Authentication Required" popup will appear.
  3. Enter user2 as the User Name and pass2 as the Password.
​          
  1. Select Settings from the bar at the top.
  1. From this screen enter the Preferred User Name and Password in the Name and Password sections.
  2. Confirm the Password and select the Group to adjust the privileges to the desired level.
  3. Hit Save changes and the login will be created.