MSC Chassis for 6P of 27mm & 12P of 18mm

Msc Chassis For 6P Of 27mm & 12P Of 18mm

Catalogue Number: CH25183
MSC Chassis for 6P of 27mm & 12P of 18mm
Retail
$641.59
RRP (Inc. GST)

Specifications

hide show
Range
Acti 9
Device short name
MSC 18/27
Product or component type
chassis
Device application
distribution
Range compatibility
Acti 9 Isobar B distribution board
[In] rated current
250 A
Short-circuit withstand
25 kA 0.1 s
[Icw] rated short-time withstand current
25 kA
Number of ways
  • 1 way (incomer) - 3P
  • 18 ways (outgoer)
    • Number of poles
    • 6 27 mm
    • 12 18 mm
      • Length
        191 mm
        Width
        215 mm
        EU RoHS Directive
        Not applicable, out of EU RoHS legal scope

        Documents & downloads

        hide show
        Filter items
        • All

        • Technical Data Catalogues

        • Specifications

        Frequently Asked Questions

        hide show

        What is the PAN assembly for C120 MCCB's

         The part code is C125123

        How many 3 pole C120 breakers can be supplied from the C125123?

        That is a 3 phase, 12 pole supply with 27mm spcaing. It will supply up to 4x 3 pole breakers.

        What distribution board is required for the CH25843 chassis?

        For the customized distribution board for 72 pole (18 mm) and 12 pole (27 mm) chassis, you need to submit request for a quote to "au.estimating@schneider-electric.com". Our Standard distribution board only goes up to 60 pole (18 mm) and 12 pole (27 mm).

        Will the 755 base fit the new 755PSMA2 smoke alarm?

        No, the only bases that is compatible with each other is the 755PSMA, 755PSMA2, 755SMA, SD100

        How do you wire the Undervoltage Relay in a PowerPact H circuit breaker?

        Product Line:

        Circuit Breakers

        Environment:
        Electrical Distribution Equipment

        Resolution:

        Connect the control wires of proper voltage to the UVR terminals under the accessory cover. Route the wires out the top of the cover through knock-outs.

        Constant voltage at the correct level for the device (24V, 120V, AC, DC, etc) should be applied to terminals numbered D1 and D4. Designation for UV trip is MN.

        Link to instruction bulletin 48940-22-01

         

        What are the coil voltage codes for the LC1D09 / LC2D09 through LC1D38 / LC2D38 TeSys contactors?

        Issue:
        What are the coil voltage codes for the LC1D09 / LC2D09through LC1D38 / LC2D38 TeSys contactors?

        Product Line:
        IEC Contactors

        Environment:
        Ordering

        Cause:
        Selection

        Resolution:
        The following lists the more common voltage suffix codes for these product lines.  For a more comprehensive list and to determine compatibility with a given product, refer to the catalog below.

        AC Volts ___Code     AC Volts ___Code
        12 ___ J7                   208 ___ LE7
        21 ___ Z7                   220 ___ M7
        24 ___ B7                  230 ___ P7
        32 ___ C7                  240 ___ U7
        36 ___ CC7               277 ___ W7
        42 ___ D7                  380 ___ Q7
        48 ___ E7                   400 ___ V7
        60 ___ EE7                415 ___ N7
        100 ___ K7                440 ___ R7
        110 ___ F7                480 ___ T7
        115 ___ FE7              575 ___ SC7
        120 ___ G7                600 ___ X7
        127 ___ FC7              690 ___ Y7
        200 ___ L7                
                       
        Standard Coil                Low Consumption
        DC Volts ___Code          DC Volts ___Code
        12 ___ JD                           5 ___ AL
        24 ___ BD                         12 ___ JL
        36 ___ CD                         20 ___ ZL
        48 ___ ED                         24 ___ BL
        60 ___ ND                         48 ___ EL
        72 ___ SD                         72 ___ SL
        110 ___ FD                       96 ___ DL
        125 ___ GD                     110 ___ FL
        220 ___ MD                    220 ___ ML
        250 ___ UD                     250 ___ UL
        440 ___ RD                

        What is the coil consumption or burden for the Tesys LC*D** contactors?

        * 1 or 2
        ** 09 through 38

        Issue:
        Coil consumption or burden for the Tesys LC1D/2D contactors from 9A - 38A

        Product Line: 
        Contactors and Starters - IEC

        Environment:
        North American Products

        Resolution:
        All AC coils for the LC1D09 through LC1D38 3-pole contactors ( including ring tongue, quick connect and spring terminal versions ) have an inrush of 70 volt-amps for either 50 or 60 Hertz applications, and a sealed value of 7 volt-amps for 50Hertz applications or 7.5 volt-amps for 60 Hertz applications.

        What is the part number for the spacer used with the LC*D09 through LC*D32 Contactor and the GV2AF3 combination block when the GV2 Motor Circuit Protector is mounted on din rail and the contactor hangs below it?

        Issue:
        Identifying the spacer part number for use with a LC*D, GV2AF3, and GV2 device combination

        Product Line:
        Contactors and Starters IEC

        Environment:
        Tesys D contactors and GV manual starters

        Cause:
        Spacer required

        Resolution:
        Compensation plate catalog number GV1F03, requires 2 pieces snap together.

        What is the coil burden for the standard DC control coil for the LC*D09__ through LC*D38__ TeSys contactors?

        Issue:
        LC*D09-38 coil consumption

        Product Line:
        Contactors and Overload Relays

        Environment:
        TeSys™ D Contactors and Overload Relays

        Resolution:
        The standard DC coil is 5.4 watts of consumption.

        What is the color scheme of the Tesys D-Line contactors?

        Issue:
        Looking for different color scheme of the Tesys D-Line contactors.

        Product Line:
        Tesys D Contactors

        Environment:
        LC1D contactors

        Resolution:
        Beige and dark gray.
         

        Are the D-Line contactors rated to break DC voltages?

        Issue: 
        Can the TeSys D line be used to control DC loads? 

        Product Line:
        Tesys D contactors

        Environment:
        Products sold and used in the United States
         
        Cause:
         DC power circuit
         
        Resolution:
         
        Yes, 75 VDC (125 VDC for D115 & D150) per pole which means that through a four pole device breaking 300 VDC is possible by wiring all four power poles in series. However, be aware that the device current ratings will differ according to the number of poles in series and the type of application.

        Devices are suitable but not UL Listed for DC applications.

        More information on their DC ratings can be found in the current TeSys Motor Control and Protection Compentns catalog: https://www.schneider-electric.us/en/download/document/MKTED210011EN/


         

        What are the stand alone short circuit current ratings on the LC1D** contactors?

        Issue:
        Tesys D SCCR

        Product Line:
        Contactors and Overload Relays

        Environment:
        TeSys™ D Contactors and Overload Relays
         
        Resolution:
        The contactors have a stand alone withstand rating that has been established by UL and is based on the maximum horsepower rating for a given device. However, only combination type starters are supplied with short circuit protective devices having a short circuit current rating.

        They are as follows:
        Horsepower SCCR (A)

        0 thru 1 1,000
        1 thru 50 5,000
        51 thru 200 10,000
        201 thru 400 18,000
        401 thru 600 30,000
        601 thru 900 42,000
        901 thru 1600 85,000
        1601+ 100,000