TeSys D Control Relay, 3 NO + 2 NC, <= 690V, 220VAC, Standard coil

TeSys D Control Relay, 3 NO + 2 NC, <= 690V, 220VAC, Standard coil

TeSys D Control Relay, 3 NO + 2 NC, <= 690V, 220VAC, Standard coil

Item Number: CAD32M7

Retail
$349.09
RRP (Inc. GST)

Product Dimensions

Width icon

Width45 mm

Height icon

Height77 mm

Depth icon

Depth84 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys D control relay

Range

TeSys

Product or component type

control relay

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

[Ue] rated operational voltage

<= 690 V AC 25...400 Hz

Mounting support

  • plate
  • rail
    • Connections - terminals

    • screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
    • screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
    • screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
    • screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
    • screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end
    • screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end
      • Mechanical durability

        30 Mcycles

        Insulation resistance

        > 10 MOhm

        Height

        77 mm

        Width

        45 mm

        Depth

        84 mm

        Net weight

        0.58 kg

        Standards

      • BS 4794
      • EN 60947-5
      • IEC 60947-5-1
      • NF C 63-140
      • VDE 0660
        • Product certifications

        • CSA
        • UL
          • IP degree of protection

            IP2x front face conforming to VDE 0106

            Ambient air temperature for storage

            -60-80 °C

            EU RoHS Directive

            Compliant

            Mercury free

            Yes

            RoHS exemption information

            Yes

            China RoHS Regulation

            Product out of China RoHS scope. Substance declaration for your information

            Environmental Disclosure

            ENVPEP110230EN

            Circularity Profile

            ENVEOLI1102030EN

            California proposition 65

            WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov

            Others

            Product name

            TeSys CAD

            Device short name

            CAD

            Contactor application

            control circuit

            Utilisation category

          • DC-13
          • AC-14
          • AC-15
            • Pole contact composition

              3 NO + 2 NC

              Control circuit type

              AC at 50/60 Hz

              [Uc] control circuit voltage

              220 V AC 50/60 Hz

              [Uimp] rated impulse withstand voltage

              6 kV conforming to IEC 60947

              [Ith] conventional free air thermal current

              10 A (at 60 °C)

              Irms rated making capacity

            • 140 A AC conforming to IEC 60947-5-1
            • 250 A DC conforming to IEC 60947-5-1
              • [Icw] rated short-time withstand current

              • 100 A - 1 s
              • 120 A - 500 ms
              • 140 A - 100 ms
                • Associated fuse rating

                  10 A gG conforming to IEC 60947-5-1

                  [Ui] rated insulation voltage

                • 600 V UL certified
                • 600 V CSA certified
                • 690 V conforming to IEC 60947-5-1
                  • Tightening torque

                  • 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2
                  • 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                    • Operating time

                    • 12...22 ms coil energisation and NO closing
                    • 4...12 ms coil de-energisation and NO opening
                    • 4...19 ms coil energisation and NC opening
                    • 6...17 ms coil de-energisation and NC closing
                      • Maximum operating rate

                        180 cyc/mn

                        Inrush power in VA

                        70-70 VA 50 Hz (at 20 °C)

                        Hold-in power consumption in VA

                        8-8 VA 50 Hz (at 20 °C)

                        Minimum switching voltage

                        17 V

                        Minimum switching current

                        5 mA

                        Non-overlap time

                      • 1.5 ms on energisation between NC and NO contact
                      • 1.5 ms on de-energisation between NC and NO contact
                        • Mechanical robustness

                        • shocks control relay open: 10 Gn for 11 ms conforming to IEC 60068-2-27
                        • shocks control relay closed: 15 Gn for 11 ms conforming to IEC 60068-2-27
                        • vibrations control relay open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
                        • vibrations control relay closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
                          • Compatibility code

                            CAD

                            Protective treatment

                            TH conforming to IEC 60068

                            Operating altitude

                            3000 m without derating

                            Unit Type of Package 1

                            PCE

                            Number of Units in Package 1

                            1

                            Package 1 Weight

                            351 g

                            Package 1 Height

                            5 cm

                            Package 1 width

                            9.2 cm

                            Package 1 Length

                            11.2 cm

                            Unit Type of Package 2

                            S02

                            Number of Units in Package 2

                            20

                            Package 2 Weight

                            7.46 kg

                            Package 2 Height

                            15 cm

                            Package 2 width

                            30 cm

                            Package 2 Length

                            40 cm

                            Unit Type of Package 3

                            P06

                            Number of Units in Package 3

                            320

                            Package 3 Weight

                            128.1 kg

                            Package 3 Height

                            77 cm

                            Package 3 width

                            80 cm

                            Package 3 Length

                            60 cm

                            WEEE

                            The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                            Show all specifications

                            Frequently Asked Questions

                            hide show

                            Are replacement contacts available for a CAD32 relay?

                            Issue:
                            Contacts need to be replaced in a CAD32** relay.

                            Product Line:
                            TeSys D IEC style relays

                            Environment:
                            CAD relays

                            Resolution:
                            The TeSys D IEC style relays do not offer replacement parts.  Replace entire device.

                            Where are the control coil terminals for TeSys LC1D09 to LC1D38 contactor?

                            Issue:
                            Determine the control coil terminal marking and location on LC1D09 to LC1D38 contactor

                            Product Line: 
                            Tesys D Contactors

                            Environment:
                            IEC contactors

                            Resolution:
                            The coil terminals are marked A1 and A2, you can see them on the front of the contactor on the white part (control section).  They are next to the auxiliary contact (13/14, 21/22) terminals.
                             

                            What is the replacement coil part number for the LC*D09 through LC*D32 and LC*DT20 through LC*DT40 TeSys contactors?

                            Issue:
                            Identifying replacement coils for tesys D non-reversing and reversing conactors

                            Product Line:
                            IEC Contactors and Starters

                            Environment:
                            Products sold and used in the United States

                            Cause:
                            Replacement coil is needed

                            Resolution:
                            DC replacement coils are not available.
                            AC Coils are 50/60 hertz for voltages as listed below:

                            Volts - Part Number
                            12 ____ LXD1J7
                            21 ____ LXD1Z7
                            24 ____ LXD1B7
                            32 ____ LXD1C7
                            36 ____ LXD1CC7
                            42 ____ LXD1D7
                            48 ____ LXD1E7
                            60 ____ LXD1EE7
                            100 ___ LXD1K7 ( never brought to North America )
                            110 ___ LXD1F7
                            115 ___ LXD1FE7
                            120 ___ LXD1G7
                            127 ___ LXD1FC7
                            200 ___ LXD1L7
                            208 ___ LXD1LE7
                            220 ___ LXD1M7
                            230 ___ LXD1P7
                            240 ___ LXD1U7
                            277 ___ LXD1W7
                            380 ___ LXD1Q7
                            400 ___ LXD1V7
                            415 ___ LXD1N7
                            440 ___ LXD1R7
                            480 ___ LXD1T7
                            575 ___ LXD1SC7
                            600 ___ LXD1X7
                            690 ___ LXD1Y7


                            Note: A contactor with an AC coil can be changed to a different AC voltage coil, IE you can take an LC1D09 with a 120VAC coil and put a 24VAC coil in it instead. An AC device cannot be switched to a DC coil, and a DC device cannot be switches to an AC coil. 

                            What is the equivalent for CS722E240 Sprecher & Schuh Relay?

                            The equivalent for CS722E240 Sprecher Schuh Relay is a CAD32U7 or LC1D098U7 can be used.

                             

                            What the DC current contact ratings for the CAD50, CAD32, CAD503, CAD323, CAD506, and CAD326 relay?

                            Issue:
                            Checking on the DC current contact ratings for the CAD50, CAD32, CAD503,  CAD323,  CAD506, and  CAD326 relay.

                            Product Line:
                            CAD Industrial Relays

                            Environment:
                            Relays and Timers

                            Resolution:
                            Inductive:
                            125V DC - 0.55 Amps make and break, 2.5 Amps cont.
                            250V DC - 0.27 Amps make and break, 2.5 amps cont.
                            600V DC - 0.10 Amps make and break, 2.5 Amps cont.

                             

                            What is the replacement for a CA3KN313BD needed

                             Use a CAD32BD

                            What is the altitude derating for a TeSys D-Line contactor?

                            Issue:​
                            What is the altitude derating for a TeSys D-Line contactor?

                            Product Line:
                            Digest 177 Section 18 : Contactors and Starters, IEC

                            Environment:
                            North American Products

                            Resolution:
                            The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

                            Voltage
                            3500m x 0.90
                            4000m x 0.80
                            4500m x 0.70
                            5000m x 0.60

                            Current
                            3500m x 0.92
                            4000m x 0.90
                            4500m x 0.88
                            5000m x 0.86

                            For example, an LC1D80 at 5000 meters:
                            - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
                            - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



                             

                            What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

                            Issue:
                            Identifying maximum voltage of an LC1D contactor

                            Product Line:
                            TeSys D Contactors

                            Environment:
                            IEC contactors and starters used in North America

                            Cause:
                            n/a

                            Resolution:
                            IThe maximum voltage per UL and CSA is 600VAC. 
                             

                            Will the LA4DC1U work with the new CAD32BD relay?

                            Issue:
                            Will the LA4DC1U work on the CAd32BD relay

                            Product Line:
                            IEC relays and accessories

                            Environment:
                            Products sold and used in the United States

                            Cause:
                            Identifying product compatibility

                            Resolution:
                            The CAD32BD with DC coil has built-in coil suppression protection as standard so the LA4DC1U is not needed.


                            CTA-ID : 2031917

                            Is the CAD32 Force guided? Are the contacts mechanically linked?

                            Issue:
                            How do the contacts on the CAD32 work

                            Product Line:
                            Relays and Timers

                            Environment:
                            North American Products
                                                              
                            Resolution:                                                                 
                            The CAD32 relays are force guided, and the contacts are mechanically linked.
                             

                            What is the replacement for the CA3DK22BD?

                            Issue:
                            What is the replacement for the CA3DK22BD?

                            Product Line:
                            Relays and Timers

                            Environment:
                            Obsolete Products

                            Cause:
                            Legacy Replacement

                            Resolution:
                            The CA3DK is Obsolete. To electrically replace it, use a CAD32BD & a LAD6K10B
                             

                            What is the 480V coil for a CA2DN31T6 IEC Relay?

                            Issue:
                            What is the 480V coil for a CA2DN31T6 IEC Relay?

                            Product Line:
                            Tesys Relays

                            Environment:
                            Obsolete relays

                            Cause:
                            Product selection

                            Resolution:
                            The LX1D2T6 coil is obsolete. Replace the contactor with the new TeSys product, CAD32T7. Note this is a functional equal only. Accessories for the old product may or may not fit the new design. Confirm dimensions.


                            CTA-ID : 2048217