TeSys D Rontrol Relay, 3 NO + 2 NC, <= 690V, 120VAC, Standard Coil

TeSys D Rontrol Relay, 3 NO + 2 NC, <= 690V, 120VAC, Standard Coil

TeSys D Rontrol Relay, 3 NO + 2 NC, <= 690V, 120VAC, Standard Coil

Item Number: CAD32G7

Retail
$384.45
RRP (Inc. GST)

Product Dimensions

Width icon

Width45 mm

Height icon

Height77 mm

Depth icon

Depth84 mm

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys D control relay

Range

TeSys

Product or component type

control relay

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

[Ue] rated operational voltage

<= 690 V AC 25...400 Hz

Mounting support

  • plate
  • rail
    • Connections - terminals

    • screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
    • screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
    • screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
    • screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
    • screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end
    • screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end
      • Mechanical durability

        30 Mcycles

        Insulation resistance

        > 10 MOhm

        Height

        77 mm

        Width

        45 mm

        Depth

        84 mm

        Net weight

        0.58 kg

        Standards

      • BS 4794
      • EN 60947-5
      • IEC 60947-5-1
      • NF C 63-140
      • VDE 0660
        • Product certifications

        • UL
        • CSA
          • IP degree of protection

            IP2x front face conforming to VDE 0106

            Ambient air temperature for operation

          • -40-60 °C
          • 60-70 °C with derating
            • Ambient air temperature for storage

              -60-80 °C

              REACh Regulation

              Free of Substances of Very High Concern above the threshold

              EU RoHS Directive

              Compliant

              Mercury free

              Yes

              RoHS exemption information

              Yes

              China RoHS Regulation

              Product out of China RoHS scope. Substance declaration for your information

              Environmental Disclosure

              ENVPEP110230EN

              Circularity Profile

              ENVEOLI1102030EN

              California proposition 65

              WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov

              Others

              Number of Units in Package 1

              1

              Number of Units in Package 2

              20

              Number of Units in Package 3

              320

              Package 1 Height

              5.1 cm

              Package 1 Length

              11.1 cm

              Package 1 width

              9.2 cm

              Package 2 Height

              15 cm

              Package 2 Length

              40 cm

              Package 2 width

              30 cm

              Package 3 Height

              77 cm

              Package 3 Length

              60 cm

              Package 3 width

              80 cm

              Unit Type of Package 1

              PCE

              Unit Type of Package 2

              S02

              Unit Type of Package 3

              P06

              Product name

              TeSys CAD

              Device short name

              CAD

              Contactor application

              control circuit

              Utilisation category

            • DC-13
            • AC-15
            • AC-14
              • Pole contact composition

                3 NO + 2 NC

                Control circuit type

                AC at 50/60 Hz

                [Uc] control circuit voltage

                120 V DC

                [Uimp] rated impulse withstand voltage

                6 kV conforming to IEC 60947

                [Ith] conventional free air thermal current

                10 A (at 60 °C)

                Irms rated making capacity

              • 140 A AC conforming to IEC 60947-5-1
              • 250 A DC conforming to IEC 60947-5-1
                • [Icw] rated short-time withstand current

                • 100 A - 1 s
                • 120 A - 500 ms
                • 140 A - 100 ms
                  • Associated fuse rating

                    10 A gG conforming to IEC 60947-5-1

                    [Ui] rated insulation voltage

                  • 600 V UL certified
                  • 600 V CSA certified
                  • 690 V conforming to IEC 60947-5-1
                    • Tightening torque

                    • 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2
                    • 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                      • Control circuit voltage limits

                      • 0.3...0.6 Uc (-40-70 °C):drop-out AC 50/60 Hz
                      • 0.8...1.1 Uc (-40-60 °C):operational AC 50 Hz
                      • 0.85...1.1 Uc (-40-60 °C):operational AC 60 Hz
                      • 1...1.1 Uc (60-70 °C):operational AC 50/60 Hz
                        • Operating time

                        • 12...22 ms coil energisation and NO closing
                        • 4...12 ms coil de-energisation and NO opening
                        • 4...19 ms coil energisation and NC opening
                        • 6...17 ms coil de-energisation and NC closing
                          • Maximum operating rate

                            180 cyc/mn

                            Inrush power in VA

                            70-70 VA 50 Hz (at 20 °C)

                            Hold-in power consumption in VA

                            8-8 VA 50 Hz (at 20 °C)

                            Minimum switching voltage

                            17 V

                            Minimum switching current

                            5 mA

                            Non-overlap time

                          • 1.5 ms on energisation between NC and NO contact
                          • 1.5 ms on de-energisation between NC and NO contact
                            • Mechanical robustness

                            • shocks control relay open: 10 Gn for 11 ms conforming to IEC 60068-2-27
                            • shocks control relay closed: 15 Gn for 11 ms conforming to IEC 60068-2-27
                            • vibrations control relay open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
                            • vibrations control relay closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
                              • Compatibility code

                                CAD

                                Protective treatment

                                TH conforming to IEC 60068

                                Operating altitude

                                0...3000 m

                                Package 1 Weight

                                352 g

                                Package 2 Weight

                                7.38 kg

                                Package 3 Weight

                                151.46 kg

                                WEEE

                                The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                                Show all specifications

                                Frequently Asked Questions

                                hide show

                                Are replacement contacts available for a CAD32 relay?

                                Issue:
                                Contacts need to be replaced in a CAD32** relay.

                                Product Line:
                                TeSys D IEC style relays

                                Environment:
                                CAD relays

                                Resolution:
                                The TeSys D IEC style relays do not offer replacement contacts.

                                Where are the control coil terminals for TeSys LC1D09 to LC1D38 contactor?

                                Issue:
                                Determine the control coil terminal marking and location on LC1D09 to LC1D38 contactor

                                Product Line: 
                                Tesys D Contactors

                                Environment:
                                IEC contactors

                                Resolution:
                                The coil terminals are marked A1 and A2, you can see them on the front of the contactor on the white part (control section).  They are next to the auxiliary contact (13/14, 21/22) terminals.
                                 

                                What is the replacement coil part number for the LC*D09 through LC*D32 and LC*DT20 through LC*DT40 TeSys contactors?

                                Issue:
                                Identifying replacement coils for tesys D non-reversing and reversing conactors

                                Product Line:
                                IEC Contactors and Starters

                                Environment:
                                Products sold and used in the United States

                                Cause:
                                Replacement coil is needed

                                Resolution:
                                DC replacement coils are not available.
                                AC Coils are 50/60 hertz for voltages as listed below:

                                Volts - Part Number
                                12 ____ LXD1J7
                                21 ____ LXD1Z7
                                24 ____ LXD1B7
                                32 ____ LXD1C7
                                36 ____ LXD1CC7
                                42 ____ LXD1D7
                                48 ____ LXD1E7
                                60 ____ LXD1EE7
                                100 ___ LXD1K7 ( never brought to North America )
                                110 ___ LXD1F7
                                115 ___ LXD1FE7
                                120 ___ LXD1G7
                                127 ___ LXD1FC7
                                200 ___ LXD1L7
                                208 ___ LXD1LE7
                                220 ___ LXD1M7
                                230 ___ LXD1P7
                                240 ___ LXD1U7
                                277 ___ LXD1W7
                                380 ___ LXD1Q7
                                400 ___ LXD1V7
                                415 ___ LXD1N7
                                440 ___ LXD1R7
                                480 ___ LXD1T7
                                575 ___ LXD1SC7
                                600 ___ LXD1X7
                                690 ___ LXD1Y7


                                Note: A contactor with an AC coil can be changed to a different AC voltage coil, IE you can take an LC1D09 with a 120VAC coil and put a 24VAC coil in it instead. An AC device cannot be switched to a DC coil, and a DC device cannot be switches to an AC coil. 

                                What is the equivalent for CS722E240 Sprecher & Schuh Relay?

                                The nearest equivalent for CS722E240 Sprecher Schuh Relay is a CAD32U7 (TeSys D control relay - 3 NO + 2 NC) or LC1D098U7 (TeSys D contactor - 4P(2 NO + 2 NC) 

                                Refer the following links for more details
                                CAD32U7 - https://www.se.com/eg/en/product/CAD32U7/tesys-d-control-relay---3-no-%2B-2-nc---%3C%3D-690-v---240-v-ac-standard-coil/

                                LC1D098U7 - https://www.se.com/ca/en/product/LC1D098U7/tesys-d-contactor---4p%282-no-%2B-2-nc%29---ac-1---%3C%3D-440-v-20-a---240-v-ac-coil/

                                What the DC current contact ratings for the CAD50, CAD32, CAD503, CAD323, CAD506, and CAD326 relay?

                                Issue:
                                Checking on the DC current contact ratings for the CAD50, CAD32, CAD503,  CAD323,  CAD506, and  CAD326 relay.

                                Product Line:
                                CAD Industrial Relays

                                Environment:
                                Relays and Timers

                                Resolution:
                                Inductive:
                                125V DC - 0.55 Amps make and break, 2.5 Amps cont.
                                250V DC - 0.27 Amps make and break, 2.5 amps cont.
                                600V DC - 0.10 Amps make and break, 2.5 Amps cont.

                                What does the "6" mean in a CAD326 control relay?

                                Issue:
                                What does the "6" form stand for

                                Product Line:
                                TeSys D IEC control relays 

                                Environment:
                                IEC Style control relays

                                Resolution:
                                The "6" means it has a binder head screw termination.
                                 