Specifications

hide show
Range
Acti 9
Device short name
MSC DC
Product or component type
chassis
Device application
distribution
Range compatibility
Acti 9 Isobar A distribution board
[In] rated current
250 A
Short-circuit withstand
25 kA 0.1 s
Number of ways
  • 1 way (incomer) - 2P
  • 20 ways (outgoer)
    • Number of poles
      20 18 mm
      Width
      215 mm
      Length
      182 mm

      Documents & downloads

      hide show
      Filter items
      • All

      • Technical Data Catalogues

      • Specifications

      Frequently Asked Questions

      hide show

      What is the replacement AC coil for CAD32 and CAD50 relay?

      Issue:
      AC coil replacement for CAD32 and CAD50

      Product Line:
      Relays

      Environment:
      Tesys CAD Control Relays

      Cause:
      Product selection

      Resolution:
      Volt = coil part number
      12 = LXD1J7
      21 = LXD1Z7
      24 = LXD1B7
      32 = LXD1C7
      36 = LXD1CC7
      42 = LXD1D7
      48 = LXD1E7
      60 = LXD1EE7
      100 = LXD1K7
      110 = LXD1F7
      115 = LXD1FE7
      120 = LXD1G7
      127 = LXD1FC7
      200 = LXD1L7
      208 = LXD1LL7
      220/230 = LXD1M7
      230 595 21 LXD1P7
      230/240 = LXD1U7
      277 781 30 LXD1W7
      380/400 = LXD1Q7
      400 = LXD1V7
      415 = LXD1N7
      440 = LXD1R7
      480 = LXD1T7
      600 = LXD1X7
      690 = LXD1Y7

       

      What is the part number for the spacer used with the LC*D09 through LC*D32 Contactor and the GV2AF3 combination block when the GV2 Motor Circuit Protector is mounted on din rail and the contactor hangs below it?

      Issue:
      Identifying the spacer part number for use with a LC*D, GV2AF3, and GV2 device combination

      Product Line:
      Contactors and Starters IEC

      Environment:
      Tesys D contactors and GV manual starters

      Cause:
      Spacer required

      Resolution:
      Compensation plate catalog number GV1F03, requires 2 pieces snap together.

      What is the coil burden for the standard DC control coil for the LC*D09__ through LC*D38__ TeSys contactors?

      Issue:
      LC*D09-38 coil consumption

      Product Line:
      Contactors and Overload Relays

      Environment:
      TeSys™ D Contactors and Overload Relays

      Resolution:
      The standard DC coil is 5.4 watts of consumption.

      What is the color scheme of the Tesys D-Line contactors?

      Issue:
      Looking for different color scheme of the Tesys D-Line contactors.

      Product Line:
      Tesys D Contactors

      Environment:
      LC1D contactors

      Resolution:
      Beige and dark gray.
       

      Are the D-Line contactors rated to break DC voltages?

      Issue: 
      Can the TeSys D line be used to control DC loads? 

      Product Line:
      Tesys D contactors

      Environment:
      Products sold and used in the United States
       
      Cause:
       DC power circuit
       
      Resolution:
       
      Yes, 75 VDC (125 VDC for D115 & D150) per pole which means that through a four pole device breaking 300 VDC is possible by wiring all four power poles in series. However, be aware that the device current ratings will differ according to the number of poles in series and the type of application.

      Devices are suitable but not UL Listed for DC applications.

      More information on their DC ratings can be found in the current TeSys Motor Control and Protection Compentns catalog: https://www.schneider-electric.us/en/download/document/MKTED210011EN/


       

      What are the stand alone short circuit current ratings on the LC1D** contactors?

      Issue:
      Tesys D SCCR

      Product Line:
      Contactors and Overload Relays

      Environment:
      TeSys™ D Contactors and Overload Relays
       
      Resolution:
      The contactors have a stand alone withstand rating that has been established by UL and is based on the maximum horsepower rating for a given device. However, only combination type starters are supplied with short circuit protective devices having a short circuit current rating.

      They are as follows:
      Horsepower SCCR (A)

      0 thru 1 1,000
      1 thru 50 5,000
      51 thru 200 10,000
      201 thru 400 18,000
      401 thru 600 30,000
      601 thru 900 42,000
      901 thru 1600 85,000
      1601+ 100,000

      What are the coil voltage codes for the LC1D09 / LC2D09 through LC1D38 / LC2D38 TeSys contactors?

      Issue:
      What are the coil voltage codes for the LC1D09 / LC2D09through LC1D38 / LC2D38 TeSys contactors?

      Product Line:
      IEC Contactors

      Environment:
      Ordering

      Cause:
      Selection

      Resolution:
      The following lists the more common voltage suffix codes for these product lines.  For a more comprehensive list and to determine compatibility with a given product, refer to the catalog below.

      AC Volts ___Code     AC Volts ___Code
      12 ___ J7                   208 ___ LE7
      21 ___ Z7                   220 ___ M7
      24 ___ B7                  230 ___ P7
      32 ___ C7                  240 ___ U7
      36 ___ CC7               277 ___ W7
      42 ___ D7                  380 ___ Q7
      48 ___ E7                   400 ___ V7
      60 ___ EE7                415 ___ N7
      100 ___ K7                440 ___ R7
      110 ___ F7                480 ___ T7
      115 ___ FE7              575 ___ SC7
      120 ___ G7                600 ___ X7
      127 ___ FC7              690 ___ Y7
      200 ___ L7                
                     
      Standard Coil                Low Consumption
      DC Volts ___Code          DC Volts ___Code
      12 ___ JD                           5 ___ AL
      24 ___ BD                         12 ___ JL
      36 ___ CD                         20 ___ ZL
      48 ___ ED                         24 ___ BL
      60 ___ ND                         48 ___ EL
      72 ___ SD                         72 ___ SL
      110 ___ FD                       96 ___ DL
      125 ___ GD                     110 ___ FL
      220 ___ MD                    220 ___ ML
      250 ___ UD                     250 ___ UL
      440 ___ RD                

      Video: What auxiliary contact modules are available for the LC1D and LC2D contactors?

      Issue:
      Auxiliary contact modules for the LC1D and LC2D contactors

      Product Line: 
      Contactor and Starters - IEC

      Environment:
      North American Products

      Resolution:
      Select based on application requirements. Please note that the TeSys and Pre-TeSys auxiliary blocks are backward/forward compatible.
      Front Mounting; maximum of 1 block per contactor:

      N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
      --1-----------1---------LADN11-----------LA1DN11
      --1-----------1---------LADN11G---------LA1DN11G (See Footnote 1)
      --1-----------1---------LADN11P---------LA1DN11P (See Footnote 1)
      --2-----------0---------LADN20-----------LA1DN20
      --2-----------0---------LA1DX20---------LA1DX20 (See Footnote 2)
      --2-----------0---------LA1DY20---------LA1DY20 (See Footnote 3)
      --0-----------2---------LADN02-----------LA1DN02
      --2-----------2---------LADN22-----------LA1DN22
      --2-----------2---------LADN22G---------LA1DN22G (See Footnote 1)
      --2-----------2---------LADN22P---------LA1DN22P (See Footnote 1)
      --2-----------2---------LADC22------------LA1DC22 (See Footnote 4)
      --3-----------1---------LADN31------------LA1DN31
      --3-----------1---------LA1DZ31----------LA1DZ31 (See Footnote 5)
      --1-----------3---------LADN13------------LA1DN13
      --4-----------0---------LADN40------------LA1DN40
      --4-----------0---------LA1DZ40-----------LA1DZ40 (See Footnote 6)
      --0-----------4---------LADN04------------LA1DN04




      Front Mounting; maximum of 1 block per contactor: For use with D2 Series 25 amp through 80 amp contactors and TeSys Series 40 amp through 80 amp only.

      N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
      --1-----------0--------LADN10----------LA1DN10
      --0-----------1--------LADN01----------LA1DN01

      Side Mounting; maximum of 1 block on each side for D2 Series and Tesys Series 40 through 80 amp contactors. Tesys 9 through 32, 115, and 150 amps contactors will accept 1 block and is limited to left side only. (*) DC control devices will not accept side mount auxiliaries.
      (*) DC control exceptions that will accept one left side mounted auxiliary: LC1D115 & LC1D150.

      N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
      --1-----------1--------LAD8N11----------LA8DN11
      --2-----------0--------LAD8N20----------LA8DN20
      --0-----------2--------LAD8N02----------N/A

      Footnotes:
      {1} EN50 012 Machine Tool Terminal Markings
      {2} (2) NO Sealed Dust Tight Contacts
      {3} Gold Flash Contacts
      {4} (1) NO & (1) NC Standard and (1) NO & (1) NC Make Before Break
      {5} (2) NO Dust Tight Contacts & (1) NO & (1) NC Standard Contacts
      {6} (2) NO Dust Tight Contacts & (2) NO Standard Contacts