MSC18 CHASSIS ASSY 250A 48 POL

Msc18 Chassis Assy 250A 48 Pol

Catalogue Number: C325483
MSC18 CHASSIS ASSY 250A 48 POL
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Product brand
Clipsal
EU RoHS Directive
Not applicable, out of EU RoHS legal scope

Documents & downloads

hide show
Filter items
  • All

  • Technical Data Catalogues

  • Specifications

Frequently Asked Questions

hide show

What is the PAN assembly for C120 MCCB's

 The part code is C125123

How many 3 pole C120 breakers can be supplied from the C125123?

That is a 3 phase, 12 pole supply with 27mm spcaing. It will supply up to 4x 3 pole breakers.

What distribution board is required for the CH25843 chassis?

For the customized distribution board for 72 pole (18 mm) and 12 pole (27 mm) chassis, you need to submit request for a quote to "au.estimating@schneider-electric.com". Our Standard distribution board only goes up to 60 pole (18 mm) and 12 pole (27 mm).

Are there Fan/Light/Heat labels for the mechs in the Iconic range?

No, but we do have labeled Dolly Rockers i.e

40FR-VW = Fan,
40LR-VW = Light and
40HR-VW = Heat.

 

What is the maximum cable length allowed between PC and TeSys T for connection via PowerSuite.

The maximum cable length allowed between PC and TeSys T connection via PowerSuite depends on the system and the converter used.

If the standard converter, from PCP offer which comes with VW3A8106 Kit, is used then the maximum recommended cable length is 10 meters.

In case of using a RS 232/485 converter with an external power supply, the maximum cable length can be 1000 meters.

What are the A, B, C, D, E, F, G, H, and J ground fault ampere values for the Micrologic 6.0A, 6.0P, and 6.0H on the 1600A Masterpact breaker NW16H2?

Product Line:
Circuit Breakers

Environment:
Electrical Distribution Equipment.

Resolution:
For all 1200A sensors and greater they are 500A, 640A, 720A, 800A, 880A, 960A, 1040, 1120A, and 1200A respectively.

What is the meaning of "PLC Returned error code 02H" for Magelis Targets HMIGTO ?

The error  "PLC  Returned error code 02H", means that you are trying to access an address in the slave device which is not defined  or inaccessible  or there can be issue with communication card , cable, or communication settings done inside IOmanager communication equipment channels must be checked. Mostly the issue observed is related to register mismatch between target and slave device.  Correcting this will resolve the issues.

Can I add programmable contacts to a Powerpact P or R frame breaker in the field?

Product Line:
Circuit Breakers
PowerPact P and R
Micrologic Trip Units

Environment:
Electrical Distribution Equipment

Resolution:
Yes. An externally mounted field installable M2C kit for Powerpact P and R breakers is available. Cat #: S64273

NOTE: You need a ``P`` or ``H`` trip unit to use this module, or an ``A`` trip unit with the BCM installed. BCM part number is S64205

What is the Communication Port configuration on an ION 8600A meter with the C1 Comms option?

On an ION 8600A with the C1 communication option, the ports will be configured as:
Com1: RS 232/485 (selectable)
Com2: Modem
Com3: IR
Com4: RS 485
Network: Ethernet

Please note that, if the meter is RMICAN sealed, then the COM4 is going to be blank.




Last Revised: November 13, 2007
Applies To: ION 8600
Public
All content © 1992-2007 Schneider Electric


Legacy KB System (APS) Data: RESL189171 V1.0, Originally authored by KBAdPM on 11/14/2007, Last Edited by KBAdPM on 11/14/2007
Related ranges: ION8600

What are the coil voltage codes for the LC1D09 / LC2D09 through LC1D38 / LC2D38 TeSys contactors?

Issue:
What are the coil voltage codes for the LC1D09 / LC2D09through LC1D38 / LC2D38 TeSys contactors?

Product Line:
IEC Contactors

Environment:
Ordering

Cause:
Selection

Resolution:
The following lists the more common voltage suffix codes for these product lines.  For a more comprehensive list and to determine compatibility with a given product, refer to the catalog below.

AC Volts ___Code     AC Volts ___Code
12 ___ J7                   208 ___ LE7
21 ___ Z7                   220 ___ M7
24 ___ B7                  230 ___ P7
32 ___ C7                  240 ___ U7
36 ___ CC7               277 ___ W7
42 ___ D7                  380 ___ Q7
48 ___ E7                   400 ___ V7
60 ___ EE7                415 ___ N7
100 ___ K7                440 ___ R7
110 ___ F7                480 ___ T7
115 ___ FE7              575 ___ SC7
120 ___ G7                600 ___ X7
127 ___ FC7              690 ___ Y7
200 ___ L7                
               
Standard Coil                Low Consumption
DC Volts ___Code          DC Volts ___Code
12 ___ JD                           5 ___ AL
24 ___ BD                         12 ___ JL
36 ___ CD                         20 ___ ZL
48 ___ ED                         24 ___ BL
60 ___ ND                         48 ___ EL
72 ___ SD                         72 ___ SL
110 ___ FD                       96 ___ DL
125 ___ GD                     110 ___ FL
220 ___ MD                    220 ___ ML
250 ___ UD                     250 ___ UL
440 ___ RD                

Are EasyPact CVS circuit breakers for sale in the USA or Canada?

Product Line:
EasyPact CVS circuit breakers

Cause:
This breaker is popular overseas and there is interest in the US

Resolution:
There are no plans for a general release of the EasyPact CVS circuit breaker line in North America.