Specifications

hide show
Range
Acti 9
Device short name
MSC 27
Product or component type
chassis
Device application
distribution
Range compatibility
Acti 9 Isobar B distribution board
[In] rated current
250 A
Short-circuit withstand
25 kA 0.1 s
[Icw] rated short-time withstand current
25 kA
Number of ways
  • 1 way (incomer) - 3P
  • 60 ways (outgoer)
    • Number of poles
      60 27 mm
      Length
      812 mm
      Width
      215 mm
      Busbar pitch
      27 mm
      Package 1 Weight
      6.7 kg
      Package 1 Height
      215 mm
      Package 1 width
      1 mm
      Package 1 Length
      1001 mm
      EU RoHS Directive
      Pro-active compliance (Product out of EU RoHS legal scope)
      China RoHS Regulation
      Product out of China RoHS scope. Substance declaration for your information

      Documents & downloads

      hide show
      Filter items
      • All

      • Technical Data Catalogues

      • Specifications

      Frequently Asked Questions

      hide show

      What is the PAN assembly for C120 MCCB's

       The part code is C125123

      How many 3 pole C120 breakers can be supplied from the C125123?

      That is a 3 phase, 12 pole supply with 27mm spcaing. It will supply up to 4x 3 pole breakers.

      Can you change the trip settings on a Micrologic trip unit with the breaker energized?

      Product Line:
      Circuit Breakers

      Environment:
      Electrical Distribution Equipment

      Resolution:
      We do not recommend doing making changes to trip unit while energized. We can not guarantee that the breaker will not trip and there are safety concerns working on energized equipment.
       

      What distribution board is required for the CH25843 chassis?

      For the customized distribution board for 72 pole (18 mm) and 12 pole (27 mm) chassis, you need to submit request for a quote to "au.estimating@schneider-electric.com". Our Standard distribution board only goes up to 60 pole (18 mm) and 12 pole (27 mm).

      What is the part number for the booted operator for the XY2CE and XY2CH botted operator cable pull switches?

      ZA2BP6

      Is it possible to see the fault current and fault type after tripping in Compact NSX with Micrologic 5 and Micrologic 6.

      Yes, it is possible to see the fault current and fault type after tripping in Compact NSX with Micrologic 5 and Micrologic 6. The external 24V DC must be provided to Micrologics. After Fault trip, the type of fault (Ir, Isd, Ii, Ig), the phase concerned and the interrupted current will be displayed by the Micrologic 5 and 6.

      What are the coil voltage codes for the LC1D09 / LC2D09 through LC1D38 / LC2D38 TeSys contactors?

      Issue:
      What are the coil voltage codes for the LC1D09 / LC2D09through LC1D38 / LC2D38 TeSys contactors?

      Product Line:
      IEC Contactors

      Environment:
      Ordering

      Cause:
      Selection

      Resolution:
      The following lists the more common voltage suffix codes for these product lines.  For a more comprehensive list and to determine compatibility with a given product, refer to the catalog below.

      AC Volts ___Code     AC Volts ___Code
      12 ___ J7                   208 ___ LE7
      21 ___ Z7                   220 ___ M7
      24 ___ B7                  230 ___ P7
      32 ___ C7                  240 ___ U7
      36 ___ CC7               277 ___ W7
      42 ___ D7                  380 ___ Q7
      48 ___ E7                   400 ___ V7
      60 ___ EE7                415 ___ N7
      100 ___ K7                440 ___ R7
      110 ___ F7                480 ___ T7
      115 ___ FE7              575 ___ SC7
      120 ___ G7                600 ___ X7
      127 ___ FC7              690 ___ Y7
      200 ___ L7                
                     
      Standard Coil                Low Consumption
      DC Volts ___Code          DC Volts ___Code
      12 ___ JD                           5 ___ AL
      24 ___ BD                         12 ___ JL
      36 ___ CD                         20 ___ ZL
      48 ___ ED                         24 ___ BL
      60 ___ ND                         48 ___ EL
      72 ___ SD                         72 ___ SL
      110 ___ FD                       96 ___ DL
      125 ___ GD                     110 ___ FL
      220 ___ MD                    220 ___ ML
      250 ___ UD                     250 ___ UL
      440 ___ RD