Quantcast

Max 4 Strip Connectors, 20A, 12 Terminal, Double Entry Bakelite

Max 4 Strip Connectors, 20A, 12 Terminal, Double Entry Bakelite

Max 4 Strip Connectors, 20A, 12 Terminal, Double Entry Bakelite

Item Number: BP2

Retail
N/A
RRP (Inc. GST)

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Product brand

Clipsal

Range of product

Blue Point

Physical

[In] rated current

20 A

Connector type

  • 1 screw terminals
  • 2 screw terminals
    • Number of poles

      12

      Mounting support

      panel

      Width

      17 mm grid pattern:

      Length

      122 mm

      Ambient air temperature for operation

      190 °C

      EU RoHS Directive

      Compliant

      Mercury free

      Yes

      RoHS exemption information

      Yes

      China RoHS Regulation

      Product out of China RoHS scope. Substance declaration for your information

      Material

      Material

      bakelite: insulation

      Others

      Cable cross section

      4-4 mm² fine stranded without cable end sleeve

      Minimum mounting height

      16 mm

      Package 1 Weight

      48 g

      Package 1 Height

      15 mm

      Package 1 width

      18 mm

      Package 1 Length

      121 mm
      Show all specifications

      Frequently Asked Questions

      hide show

      What are the Clipsal BPT2 Dimensions?

      • Dimensions: 58 x 40 x 40 mm
      https://www.clipsal.com/Trade/Products/ProductDetail?CatNo=BPT2

      What is a bPF fault on the ATS22 soft starter?

      Issue:
      bPF fault on the ATS22.

      Product Line:
      Altistart ATS22

      Environment:
      All

      Cause:
      Bypass contactor detected fault

      Resolution:
      Check for a welded bypass contactor or shorted SCR.
      If you find a shorted SCR or bypass contactor, you will need to replace the soft starter.
      Reference the ATS22 installation guide (BBV51330)

      What is the part number for a BPA sign in the Medilec range?

       The part number for a BPA sign in the Medilec range is SIGN/BPA.

      Some of the key features are:

      • Made from sturdy laminex
      • Adhesive on each corner for easy installation
      • Supplied with “test and date” stickers

       

      For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=SIGN/BPA

       

      Can BPH motors be used with the Lexiium 32 Servo drives?

      Yes, the BPH motors are compatible with Lexium 32 servo drives. They are to be characterized as third party motors.  If using a BPH motor with resolver, you will need to use a resolver option card P/N : VW3 M3 401. If using a BPH motor with encoder feedback, you will need to use an encoder option card.VW3 M3 403 (for hiperface encoder) along with a Lexum 32 modular drive (32M). The third party motor commissioning tool within SoMove helps calculate the offset to commutate the motor.

      What can prevent an OP2 fault code on an ATV212 drive?

      Issue:
      OP2 fault code on an ATV212 drive.

      Product Line:
      ATV21, ATV212

      Environment:
      All models and serial numbers

      Cause:
      The OP2 fault is caused by overvoltage during deceleration

      Resolution:
      1.  Increase the deceleration time (increase dEC).
      2.  Disable Auto Ramp Adaptation (Set AU1 to 0). Auto ramp adaptation can cause fluctuation on the line supply to the drive.
      3.  Measure drive DC bus (PA/+ to PC/-) with a meter.  
      4.  Check for load issue that can cause back feeding issue to DC bus such as stopping a load very quickly.
      Stopping one fan while another fan is pulling on it (such as in a wind tunnel) can cause back feeding into the DC bus.

      Note: A dynamic braking resistor cannot be added to the ATV212 drive. 

      MHDA1056N00 servo drive replacement

      Question:
      Replacement for the MHDA1056N00 drive

      Product Line:
      MHDA

      Resolution:
      The MHDA1056N00 servo drive is obsolete.
      The closest match is the LXM32MC10N4 (11kW instead of 14kW)
      The BPH motor will also have to be replaced.