socket swt sing b style s/s

Single Switch Socket Outlet, 250V, 10A, B Style, Flat Plate, Vertical

Catalogue Number: B15VA
socket swt sing b style s/s
Colour: White Electric
Colour: Per UOM Std.
  • Black 1 PCE
  • White Electric 1 PCE

Specifications

hide show
Product brand
Clipsal
Range of product
Metal Plate
Control type
ON/OFF button
Number of gangs
1 gang
Pin number
3
Number of power socket outlets
1
Actuator
  • rocker
  • switch
    • Mounting position
      vertical
      Fixing mode
      by screws
      Local signalling
      without light indicator
      Material
      stainless steel
      [Ue] rated operational voltage
      250 V AC
      [In] rated current
      10 A
      Depth
      35 mm
      Length
      115 mm
      Width
      70 mm
      Fixing center
      84 mm
      Standards
    • AS/NZS 3100
    • AS/NZS 3112
    • AS/NZS 3133:approval number S/1
      • Sustainable offer status
        Green Premium product
        EU RoHS Directive
        Compliant
        Mercury free
        Yes
        RoHS exemption information
        Yes
        China RoHS Regulation
        Product out of China RoHS scope. Substance declaration for your information
        Environmental Disclosure
        ENVPEP120506EN
        Circularity Profile
        N/A

        Frequently Asked Questions

        hide show

        What is part number for wall clip to suit B15V2A?

        The part number for wall clip to suit B15V2A is 154/2

        What is the part number for a BSL style double size plate double GPO?

        The part number is B15V2A.

        What is the inrush current of a LC1D40U7 Contactor?

        It is 160VA inrush and 15VA sealed at 50HZ for the LC1D40U7 Contactor.
        For more information see data sheet https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=lc1d40u7

        What is the part number of the wall clip to suit B15V2A, B style flat plate, Stainless Steel, double power outlet?

        154/2 is the part number of the wall clip to suit B15V2A. 154/2  accommodates up to 12mm thick plaster board or hardboard, vertical/horizontal mounting. Dimensions are 120mm(L) x 96mm(W) x 9mm(D). Mounting centres are 46mm x 84mm.
        For further information, please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=154/2

        What is the inrush of a K range contactor

         The inrush is 30VA but the holding is 4.5VA

        What is the part number for a 20A, 415V, contactor with a 240V coil?

        The part number for a 20A, 415V, contactor with a 240V coil is a LC1DT20U7.

        spare 415VAC coil for LC1D80 Contactor ?

        Code = LX1D6N7

        What is the part number for a 3 phase DOL starter for 2.2kW load with overload 4 amps and 415VAC coil??

        The part number for a 3 phase DOL starter with 415VAC coil and overload to cover 4amps is - LE1M35N712

        See attachment.

         

        What is the part number for a 3 pole 32amp 415VAC coil contactor and overload?

        The part number for a 3 pole 32amp 415VAC coil contactor and overload is - LC1D32N7 & LRD32

        For further information , visit links below:-
        https://www.schneider-electric.com.au/en/search/LC1D32N7
        https://www.schneider-electric.com.au/en/search/LRD32

        User-added image

        What are the part numbers of the 32A and 45A cooker switches that are unmarked?

        Below are the part numbers of the cooker switches that are unmarked.
        2031/45 Single-pole 250V, 45A - 2000 Series
        C2031/45 Single-pole 250V, 45A - C2000 Series
        2031D32 Double-pole 415V, 32A - 2000 Series
        C2031D32 Double-pole 415V, 32A - C2000 Series
        2031/45N Single-pole, includes Neon, 250V, 45A - 2000 Series
        C2031/45N Single-pole, includes Neon, 250V, 45A - C2000 Series
        2031D32N Double-pole, includes Neon, 415V, 32A - 2000 Series
        C2031D32N Double-pole, includes Neon, 415V, 32A - C2000 Series
        For further information, please visit https://updates.clipsal.com/ClipsalOnline/Files/Brochures/A0000272.pdf

        What is the code for a 415VAC coil for a LC1D40A Contactor?

        The 415V coil is LXD3N7

        What mounting brackets do you use for a BSL range?

        BSL25A can be mounted on standard accessories. However, B25SA, B25NA and BSL25XA require the 154B25 mounting bracket for installation (order separately)

        What is the part number for an adaptor that will convert 3 phase 415VAC to 240VAC?

        Unfortunately, Clipsal / Schneider do not make an adaptor that would do this.

        Does the 4CNT/63 have a 415VAC coil?

        No. The 4CNT/63 only comes with a 240VAC coil.

        Some of the key features are:
        • DIN rail mount
        • 4 pole
        • 3 module
        • 63 A at AC1

        For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=4CNT4/63
         

        Can you wire R2 relay on the ATV28 drive to a 115Vac light?

        Issue:   Can you wire R2 relay on the ATV28 drive to a 115Vac light?
         
        Product Line:   ATV28
         
        Environment:  All
         
        Cause:   N/A
         
        Resolution:   Yes. The R2 relay contacts are rated for 1.5A 250Vac and 30Vdc.


         

        What is the part number for a 3 phase DOL starter with 415VAC coil and overload that has range of 2.6-3.7amps?

        The part number for a 3 phase DOL starter with 415VAC coil and overload that has range of 2.6-3.7amp is - LE1M35N710

        For further information , visit link below:-
        https://www.schneider-electric.com.au/en/search/LE1M35N710
         

        Battery Discharge During Storage


        Issue:

        The shelf life of a UPS battery under storage conditions depends on battery ratings and ambient temperature.

        Product Line:

        All UPS products

        Environment:

        All models, All Serial Numbers

        Cause:

        Normal behavior.

        Resolution:

        The shelf life of a UPS battery under storage conditions depends on battery ratings and ambient temperature. For each APC UPS family the expected battery discharge rate is presented for various storage conditions.

        Temperature Effects:

        The type of battery used in all UPS products has a "self-discharge" characteristic. This is the amount of charge the battery will naturally lose even if it is disconnected. At 20° Celsius, a battery will lose 3% of its capacity per month. However, at 40° Celsius, a battery will lose 10% of its capacity per month.


        For Back-UPS, Back-UPS Office, Back-UPS AVR, Back-UPS Pro, Smart-UPS v/s:

        When any of these APC UPS models has been powered "off", the battery discharge is equal to the self-discharge rate.


        With Smart-UPS:
        There are two ways to turn off a Smart-UPS. When applicable, if the UPS is switched off by using the rear switch, then the battery discharge is equal to the self-discharge rate. However, if the UPS is switched off with the front panel button, then the self discharge rate at 20° Celsius will increase from the natural 3% to 5% per month. The lost power goes into a small micropower circuit which is needed in order for the UPS to "remember" if it is supposed to restart automatically when the AC power is restored.


        With SmartUPS RT (1kva to 10kva):

        Any time a SmartUPS RT (1kva to 10kva) will be turned off without input power present, or allowed to operate in bypass for over 24 hours, the battery modules should be disconnected to prevent unnecessary discharge. Depending on the health of the batteries, they can discharge below start-up voltage (approximately 85vDC) within 72 hours if the UPS is not operating normally.


        With SmartUPS RT (15kva to 20kva):

        Any time a SmartUPS RT (15kva to 20kva) will be turned off without input power present, the battery modules should be disconnected to prevent unnecessary discharge. However, unlike the smaller RT units, the 15kva and 20kva SmartUPS RT's are able to charge batteries while in bypass mode.


        With Matrix-UPS:

        There are two ways to turn off a Matrix-UPS. If the UPS is switched off using the rear switch, then the battery discharge rate is slightly higher than the natural self-discharge rate, which is 5% at 20° Celsius. The extra power goes into "bleeder" circuits which are required to discharge the large capacitors inside the unit in order to protect service personnel.

        However, if the UPS is switched off with the front touch switch, then the self discharge rate at 20° Celsius will increase from the natural 5% to 7% per month. The additional lost power goes into a small micropower circuit which is needed for the UPS to "remember" if it is supposed to restart automatically when the AC power is restored.

        If a Matrix-UPS is to be stored in this condition (i.e. off) for a long period of time, it is recommended that the batteries be detached from the Matrix-UPS Electronics Unit, as this will reduce the self-discharge rate to 3% per month.


        With Symmetra, Symmetra RM and Symmetra LX:

        Any time a Symmetra will be turned off or allowed to operate in bypass for over 24 hours, the battery modules should be disconnected/disabled to prevent unnecessary discharge. Depending on the Symmetra model in use, batteries can discharge below start-up voltage (approximately 90vDC) within 72 hours if the UPS is not operating normally.


        Bottom Line:

        APC Batteries should be charged to 100% within 6 months of purchase by the end user. If the batteries are to be stored for an extended period of time after that, the following procedures are strongly recommended in order to keep the batteries from discharging beyond the safe limit:
         

        • If the ambient temperature during storage is - 15°C to + 30°C (+ 5°F to + 86°F), perform a full recharge cycle at least every six months.
        • In environments where the ambient temperature is + 30°C to + 45°C (+ 86°F to + 113°F), perform a full recharge cycle at least every three months.
           

        What are the 9013FHG pressure switch contacts rated at?

        Issue:
        Contact Rating of 9013F Pressure Switches

        Product Line: 
        Pressure, vacuum and Float Switches 

        Environment:
        9013 Type F Pressure Switch 

        Resolution:
        Those contacts have a control circuit rating of A600.
        They are DC rated at 1/4 HP at 115V and 230V (Except form M4)
        They are Single Phase AC rated 1 1/2 HP at 115V, 2 HP at 230V
        They are Polyphase rated 2 HP at 115V, 3 HP at 230V, and 1 HP at 460/575V.

        This also applies to the 9013 FHG2, 9, 12, 13, 44, 49 9013 FSG, and FSW.

        What is the code for a complete LC1D95 with a 415vAC Coil?

           The code for the contactor is LC1D95N7

        Can I use 115VAC inputs with Twido?

        Yes, to do so it is necessary to use the new 115 VAC input expansion module TWDDAI8DT.


        Legacy KB System (APS) Data: RESL164091 V1.0, Originally authored by on , Last Edited by on
        Related ranges: Twido

        What is the rated coil consumption of the LC1D09 thru LC1D38 contactor, 50 or 60 hertz AC control?

        Issue:
        Identifying coil consumption

        Product Line:
        IEC Contactors and Starters

        Environment:
        Products sold and used in the United States

        Cause:
        Coil consumption data is required

        Resolution:
        70VA inrush, 7.5VA sealed.


         

        What is the part number of the replacement RCD to suit 56SC420RC, 500V, 20A RCD protected switched outlet?

        4RC425/30 is the part number of the RCD supplied with 56SC420RC. 4RC425/30 is 4 pole rated to 415V, 25A, 30mA.
        For further information, please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=4RC425/30
         

        What is the DC Bus Voltage Threshold at which the Brake IGBT operates in Altivar 71 Drive powered with 220VAC or 415VAC 3 Phase.

        The Altivar 71 Drive Braking IGBT operates when the value of DC Bus Voltage is higher than the DC Bus Threshold Voltage OBR. When the value of the DC Bus Voltage is lower than the threshold voltage (Unom_max + 10%), the Braking IGBT/Transistor is switched off.

        The Voltage Threshold Values for a Drive working on 220VAC or 415VAC, 3Phase is provided in the attachment.

        Note:

        OBR is the threshold point where the Braking Transistor switches ON and Unom_max + 10% is the threshold point where the Braking Transistor switches OFF.

        What is the maximum current draw (amps) at CL1 and CL2 at 115VAC for each ATS48 model?

        Goals and Symptoms

        What is the maximum current draw (amps) at CL1 and CL2 at 115VAC for each ATS48 model?

        Facts and Changes

        ATS48 CL1 and CL2 power with cooling fans working

        Causes and Fixes

        For each card without fan under 115 Vac: 220 mA

        With fans:

        D32 to C17 : 260 mA
        C21 to C32 : 440 mA
        C41 to M12 : 700 mA


        Legacy KB System (APS) Data: RESL160577 V1.0, Originally authored by on , Last Edited by on
        Related ranges: Altistart 48

        What is the coil consumption or burden for the Tesys LC*D** contactors?

        Issue:
        What is the coil consumption or burden for the Tesys LC*D** contactors?

        Product Line:
        Tesys Contactors and Overload Relays

        Environment:
        All Products

        Cause:
        Product Features

        Resolution:
        All AC coils for the LC1D40 through LC1D80 3 or 4-pole contactors have an inrush of 200VA for 50 Hertz applications or 220VA for 60Hz.
        Sealed values are 20VA for 50 Hertz applications or 22VA for 60 Hertz applications. For 50/60 Hertz coil inrush is 245VA and sealed is 26VA


        CTA-ID : 2029994

        Is there a 3 position marked "1, 0, 2" 2 pole cam switch 16A available?

        Yes, the part number for a 3 position marked "1, 0, 2" 2 pole cam switch 16A is a 7GN12/52/U.
        Brief :

         Rotary Cam Switches and Accessories, Rated Thermal Current (Ith) = 12A AC23A rating - 6kW at 415V. Rated Insulation Voltage Ui = 480V. Maximum 16A Fuse (gG/gL) for 3kA short circuit protection, 2 Pole 12A 60° changeover switch with Off marked 1-O-2.

        Some of the key features are:

        • Front mounting
        • AC23A Rating
        • Changeover switch with OFF marked 1-O-2
        For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=7GN12/52/U​

         

         

         

        What is the part number for a DOL starter for 7.5kW load with 415VAC coil and overload for 16amps?

        The part number for a DOL starter for 7.5kW load with overload for 16amps is - LE1D18N7 & LRD21

        For further information , visit link below:-
        https://www.schneider-electric.com.au/en/search/LE1D18N7
        https://www.schneider-electric.com.au/en/search/LRD21
         

        What are the differences between the AS-P810-000 and the AS-P810-001 power supplies?

        Issue:
        Suitable replacement for the P810 power supply.

        Product line:
        984 800 series

        Cause:
        No power on P810 power supply and no replacement.

        Resolution:
        Both models of the P810 operate from either a 115VAC or 230VAC power line. The P810-001 includes a power on/off keyswitch and a front accessible fuse. The P810-000 does not offer these two features. With the exception of the keyswitch and the front-mounted fuse, the two power supplies are identical.


        Where do I connect the Auto Start contacts on an 8839EFD with HOA switch?

        Issue:
        Where do I connect the Auto Start contacts on an 8839EFD with HOA switch?
         
        Product Line:
        8839 EFD
         
        Environment:
        Power Circuit Y (With Bypass): Hand-Off-Auto and Speed Potentiometer
         
        Cause:
        Remote start
         
        Resolution:


         

        Smart-UPS Stacking Height Limitations

        This document describes the acceptable stacking configurations of Smart-UPS products.  To achieve the minimum possible footprint, these products can be stacked following the guidelines below. It is important to consider the effect of extra weight on any raised floor environments.

        SU Products:

         The UPS and batteries can be stacked 25.5"" high. Possible configurations include:

        3 SU48XLBPs stacked together
        1 SU2200XL on bottom, 1 SU48XLBP on top
         

        SURT Products:

        1KVA to 10KVA SURT units are not designed to be stacked, but rather should be connected in a tower configuration as indicated in the users manual.
        15KVA and 20KVA units may be stacked to a total height of not more than 18U, which would be a main UPS enclosure and 2 battery enclosures.

         

        Do we offer a option to supply 120 volts for the logic inputs on the ATV61 and ATV71?

        Issue:
        Do we offer a option to supply 120 volts for the logic inputs on the ATV61 and ATV71?

        Product Line:
        Atlviar ATV61 and ATV71

        Environment:
        All

        Cause:
        Needs to have an option to supply 120 vac to turn on the logic inputs to start up the drive.

        Resolution:
        Yes,  The 115 VAC logic input adaptor is part number VW3A3101.

        Fuse and circuit breaker rating for LXM32

        Issue:
        What is the fuse or circuit breaker rating for LXM32 drives?

        Product Line:
        LXM32

        Resolution:
        For 115VAC and 230VAC drives, the maximum fuse to be connected upstream is 25 Amps, Class CC or J as per UL 248-4, alternatively circuit breakers with B or C characteristic.
        For 400VAC and 480VAC drives, the maximum fuse to be connected upstream is 30/32 Amps, Class CC or J as per UL 248-4, alternatively circuit breakers with B or C characteristic.

        What third party products are supported by the APC Netbotz SNMP Crawler?

        "The APC Netbotz product range has SNMP crawler support for APC products, MGE products, as well as third party manufacturers. Listed below are major manufacturers supported by the SNMP crawler with a list of common supported products broken down by manufacturer below.

        APC
        Alcatel
        Avaya
        Best Power
        Cisco Systems
        Compaq
        DMTF
        Dell
        Extreme Networks
        Foundry Networks
        IBM
        Juniper Networks
        Liebert
        MGE
        MIB2-UPS
        Mitsubishi
        NetBotz
        Powerware
        Sun Microsystems

        Liebert

        Info from: https://www.liebert.com/dynamic/displayproduct.asp?id=921&cycles=60hz
        And https://www.liebert.com/products/english/products/site/com_nic/comp.asp

        UPS
        AP 200 UPS
        Series 300/301 UPS
        AP 4300
        Series 600 System Control Cabinet
        Series 600 Single Module System UPS
        UPStation D/Select UPS
        UPStation G/GX/GRT/Gold
        UPStation GXT
        PowerSure Interactive
        UPStation S UPS
        UPStation S3 UPS
        NPower
        Hiross 7200 (Italy)
        Hiross HiPulse (Italy)

        Environmental Products
        Deluxe System 3
        Challenger
        MiniMate 2
        Level 00/05/10/15
        Himod

        3-Phase Power
        DataWave
        Static Switch
        Static Switch 2


        MGE

        Pulsar Evolution
        Pulsar EX
        Pulsar EX RT
        Comet EXtreme
        Comet EXt RT
        Comet 3000
        Comet S31
        Galaxy
        Galaxy 1000 PW
        Galaxy 3000
        Galaxy 4000
        Galaxy PW Harmony
        Galaxy PW
        EPS 6000
        EPS 8000


        Eaton Powerware

        Info from: https://www.powerware.com/ups/connectivity/connectups_snmp.asp
        And https://www.powerware.com/ups/connectivity/ConnectUPS_SL_SNMP.asp


        Powerware 9155
        Powerware 9315
        Powerware 5119
        Powerware 9 Prestige
        Powerware 9150


        Mitsubishi UPS
        Info from: https://www.meau.com/eprise/main/sites/public/PRODUCTS/Uninterruptible_Power_Supplies/NetCom/default

        2033A Series
        2033C Series
        2033D
        7011A Series (1kVA to 3kVA, 6kVA to 12kVA)
        9700 Series
        9800D Series

        Best
        Info from: https://www.powerware.com/UPS/BestPower/Products.asp

        Fortress
        Patriot Pro
        FERRUP
        Best Power 610"

        External Fusing Change for 24vdc Momentum I/O Modules

        Release Notice

        The purpose of this Resolution is to inform users of 24vdc Momentum I/O Bases that the fusing requirement has changed.

        Goals and Symptoms

        Using a 315ma fast blow fuse on a redesigned 24vdc Momentum base may cause the fuse to blow when powered up. Since the 24vdc Momentum I/O bases have been redesigned to meet the new EMC and power hold-up requirements, it was necessary to increase the size of the external fusing.

         

        Facts and Changes

        The external fusing is indicated in the User Manuals as follows. It does not affect the recommended fusing for the I/O power.


         

        Causes and Fixes

        The recommended size of the external fuse for all Momentum I/O modules that are powered by 24 VDC, has changed from a 315ma Fast Blow fuse to a 1Amp Slow Blow fuse (Bussmann GDC-1A or equivalent).

        The 1A Slow Blow fuse can be used on both new and old versions of 24vdc powered Momentum I/O bases listed below.

        DC Discrete Modules

        • 170ADI34000 24V DC - 16 Pt Input Module Base
          170ADI34000C 24V DC - 16 Pt Input Module Base Coated
          170ADI35000 24V DC - 32 Pt Input Module Base
          170ADI35000C 24V DC - 32 Pt Input Module Base -Coated
          170ADM35010 24V DC - 16 Pt Input/ 16 Pt Output Module Base
          170ADM35010C 24V DC - 16 Pt Input/ 16 Pt Output Module Base Coated
          170ADM35011 24V DC - 16 Pt Input/ 16 Pt Output - Fast Response Module Base
          170ADM35015 24V DC - 16 Pt Input/ 16 Pt Output Module Base - True Low Signals
          170ADM39010 24V DC - 16 Pt Input/ 12 Pt Output - Monitored Module Base
          170ADM39030 24V DC - 10 Pt Input/ 8 Pt Relay Output Module Base
          170ADM39030C 24V DC - 10 Pt Input/ 8 Pt Relay Output Module Base Coated
          170ADO34000 24V DC - 16 Pt Output Module Base
          170ADO34000C 24V DC - 16 Pt Output Module Base Coated
          170ADO35000 24V DC - 32 Pt Output Module Base
          170ADO35000C 24V DC - 32 Pt Output Module Base Coated
          170ADM85010 10 to 60 V DC - 16 Pt Input/ 16 Pt Output Module Base

        Analog Modules
        • 170AAI03000 Analog - 8 Ch Differential Input Module Base
          170AAI03000C Analog - 8 Ch Differential Input Module Base Coated
          170AAI14000 Analog - 16 Ch Single-Ended Input Module Base
          170AAI14000C Analog - 16 Ch Single-Ended Input Module Base Coated
          170AAI52040 Analog - 4 Ch RTD, Thermocouple, and Mv Input Module Base
          170AAI52040C Analog - 4 Ch RTD, Thermocouple, and Mv Input Module Base Coated
          170AAO12000 Analog - 4 Ch Output 0-20mA Module Base
          170AAO92100 Analog - 4 Ch Output 4-20mA Module Base
          170AAO92100C Analog - 4 Ch Output 4-20mA Module Base Coated
          170AMM09000 Analog - 4 Ch In/ 2 Ch Out Module Base, w/ 24V DC 4 In/2 Out Digital
          170AMM09000C Analog - 4 Ch In/ 2 Ch Out Module Base, w/ 24V DC 4 In/2 Out Digital Coated
          170AMM09001 Analog - 4 Ch In/ 2 Ch Out Module Base, w/ 12V DC 4 In/2 Out Digital

        Specialty Modules
        • 170AEC92000 High Speed Counter Module Base

        What replacement coils are available for the LC1F500?

        Issue:
        What replacement coils are available for the LC1F500?

        Product Line:
        TeSys F-Line Contactors

        Environment:
        All Product Lines

        Cause:
        Can not find it in the Digest

        Resolution:

        For LX1 standard style coils (most common):

        24VAC (40 - 400 hz) = Not Available
        48VAC (40 - 400 hz) = LX1FK048
        110VAC (40 - 400 hz) = LX1FK110
        120AC (40 - 400 hz) = LX1FK110
        208VAC (40 - 400 hz) = LX1FK200
        220VAC (40 - 400 hz) = LX1FK220
        240VAC (40 - 400 hz) = LX1FK240
        277VAC (40 - 400 hz) = LX1FK280
        380VAC (40 - 400 hz) = LX1FK380
        415VAC (40 - 400 hz) = LX1FK415
        440VAC (40 - 400 hz) = LX1FK415
        480VAC (40 - 400 hz) = LX1FK415
        600VAC (40 - 400 hz) = LX1FK600


        For LX9 special coils:


        24VAC (40 - 400 hz) = LX9FK910
        48VAC (40 - 400 hz) = LX9FK917
        110VAC (40 - 400 hz) = LX9FK925
        120AC (40 - 400 hz) = LX9FK925
        208VAC (40 - 400 hz) = LX9FK930
        220VAC (40 - 400 hz) = LX9FK931
        240VAC (40 - 400 hz) = LX9FK932
        277VAC (40 - 400 hz) = LX9FK932
        380VAC (40 - 400 hz) = LX9FK936
        415VAC (40 - 400 hz) = LX9FK936
        440VAC (40 - 400 hz) = LX9FK937
        480VAC (40 - 400 hz) = LX9FK937
        600VAC (40 - 400 hz) = Not Available







         

        Will my Smart-UPS RT UPS turn on without batteries?


        Issue:

        Will my Smart-UPS RT UPS turn on without batteries?

        Product Line:

        Smart-UPS Online

        Environment:

         All models beginning with "SURT" and having a capacity of 10Kva or less, All Serial Numbers

        Cause:

        No, the Smart-UPS SURT family (10Kva or less) requires working batteries to be connected in order to turn on.
        SURT 15Kva and 20Kva and all SRT models can turn on with or without functional batteries.

        Resolution:

        Allow the batteries to charge if there has been a recent outage. Otherwise, replace the batteries as needed. Contact APC Tech Support for further assistance if necessary.
         

        Is there a replacement for the Domestic Safety Switch C Curve 40A 4 pole 12225?

        No, there is no direct replacement. However, in a diffrent range there is a Resimax, 415V, 40A, 30mA, 4 pole, Domestic safety switch. It is four modules wide and the part number is RCD440/30.

        Key Features
        • Unique new white finish for a fresh modern look
        • Base module = 18 mm wide, compact standardised and consistent module dimensions
        • Lift-up terminals. Safer ‘no hot spot’ terminations and all cable strands are locked in
        • Cable automatically guided to the correct position: terminals with guard
        • Fast closure
        • The presence of the green strip guarantees physical opening of the contacts and allows operations to be performed on the downstream circuit in complete safety
        • Operating temperature: -5 to 40 deg C
        • 6 kV Rated impulse withstand voltage



        For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=RCD440/30

        How do I know which battery to replace in my SURT15K or SURT20K UPS?


        Issue:

        How do I know which battery to replace in my SURT15K or SURT20K UPS?

        Product Line:

        Smart-UPS Online

        Environment:

        All 15Kva and 20Kva models, All Serial Numbers

        Cause:

        Batteries in a Smart-UPS need to be replaced every 3-5 years based on useage and environment.

        Resolution:

        When the UPS alerts you that it has a bad battery, the red LED on the affected battery frame will illuminate. The UPS does not monitor the individual battery modules and is unable to tell you exactly which pair(s) of modules is bad. You should walways replace all of the modules in a frame at the same time. Each frame uses (Qty 4) APCRBC140 Replacement Battery Cartridges. Each APCRBC140 contains 2 modules, for a total of 8 modules in each battery frame. If you have other attached frames of a similar vintage, it is likely that they will need to be replaced as well. We do not reccomend mixing old and new batteries in the same UPS. On average your batteries should last 3-5 years. Environment and application can have a dramatic affect on the life cycle of your batteries.

        Note: The replacement battery for these models used to be RBC44. This model battery was replaced with part number APCRBC140. Runtime and battery life is exactly the same for both model batteries.