Specifications

hide show
Range of product
Altivar 32
Product or component type
variable speed drive
Product destination
  • asynchronous motors
  • synchronous motors
    • Product specific application
      complex machines
      Function available
      -
      Assembly style
      with heat sink
      Component name
      ATV32
      EMC filter
      Class C2 EMC filter integrated
      Network number of phases
      3 phases
      [Us] rated supply voltage
      380...500 V - 15...10 %
      Supply voltage limits
      323-550 V
      Supply frequency
      50...60 Hz - 5...5 %
      Network frequency
      47.5...63 Hz
      Motor power kW
      3 kW at 380...480 V
      Line current
    • 11.1 A for 380 V 3 phases 3 kW
    • 8.4 A for 500 V 3 phases 3 kW
      • Apparent power
        7.3 kVA at 500 V 3 phases 3 kW
        Prospective line Isc
        5 kA for 3 phases
        Nominal output current
        7.1 A at 4 kHz 500 V 3 kW
        Maximum transient current
        10.7 A for 60 s 3 kW
        Output frequency
        5.0E-4-0.599 kHz
        Nominal switching frequency
        4 kHz
        Switching frequency
        2...16 kHz adjustable
        Speed range
        1-100 for asynchronous motor in open-loop mode
        Speed accuracy
        +/- 10 % of nominal slip 0.2 Tn to Tn
        Torque accuracy
        +/- 15 %
        Transient overtorque
        170-200 %
        Braking torque
        <= 170 % with braking resistor
        Asynchronous motor control profile
      • voltage/frequency ratio, 5 points
      • voltage/frequency ratio, 2 points
      • flux vector control without sensor, standard
      • voltage/frequency ratio - Energy Saving, quadratic U/f
      • flux vector control without sensor - Energy Saving, NoLoad law
        • Synchronous motor control profile
          vector control without sensor
          Regulation loop
          adjustable PID regulator
          Motor slip compensation
        • automatic whatever the load
        • not available in voltage/frequency ratio (2 or 5 points)
        • adjustable 0...300 %
          • Local signalling
          • 1 LED red for drive voltage
          • 1 LED green for CANopen run
          • 1 LED red for CANopen error
          • 1 LED red for drive fault
            • Output voltage
              <= power supply voltage
              Noise level
              45 dB conforming to 86/188/EEC
              Insulation
              electrical between power and control
              Electrical connection
            • screw terminal, clamping capacity: 0.5...1.5 mm², AWG 18...AWG 14 (control)
            • removable screw terminals, clamping capacity: 1.5...2.5 mm², AWG 14...AWG 12 (motor/braking resistor)
            • screw terminal, clamping capacity: 1.5...4 mm², AWG 14...AWG 10 (power supply)
              • Tightening torque
              • 0.5 N.m, 4.4 lb/ft (control)
              • 0.7 N.m, 7.1 lb/ft (motor/braking resistor)
              • 0.6 N.m, 5.3 lb/ft (power supply)
                • Supply
                  internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection
                  Analogue input number
                  3
                  Analogue input type
                • AI1 voltage: 0...10 V DC, impedance: 30000 Ohm, resolution 10 bits
                • AI2 bipolar differential voltage: +/- 10 V DC, impedance: 30000 Ohm, resolution 10 bits
                • AI3 current: 0...20 mA (or 4-20 mA, x-20 mA, 20-x mA or other patterns by configuration), impedance: 250 Ohm, resolution 10 bits
                  • Sampling duration
                  • 2 ms (AI1, AI2, AI3) - analog input(s)
                  • 2 ms (AO1) - analog input(s)
                    • Response time
                    • LI1...LI6 8 ms, tolerance +/- 0.7 ms for logic output(s)
                    • R1A, R1B, R1C 2 ms for relay output(s)
                    • R2A, R2C 2 ms for relay output(s)
                      • Accuracy
                      • +/- 0.2 % (AI1, AI2, AI3) for a temperature of -10...60 °C
                      • +/- 0.5 % (AI1, AI2, AI3) for a temperature of 25 °C
                      • +/- 1 % (AO1) for a temperature of 25 °C
                      • +/- 2 % (AO1) for a temperature of -10...60 °C
                        • Linearity error
                        • +/- 0.2...0.5 % of maximum value (AI1, AI2, AI3)
                        • +/- 0.3 % (AO1)
                          • Analogue output number
                            1
                            Analogue output type
                          • AO1 software-configurable current 0...20 mA, impedance: 800 Ohm, resolution 10 bits
                          • AO1 software-configurable voltage 0...10 V, impedance: 470 Ohm, resolution 10 bits
                            • Discrete output number
                              3
                              Discrete output type
                            • configurable relay logic: (R1A, R1B, R1C) NO/NC - 100000 cycles
                            • configurable relay logic: (R2A, R2B) NO - 100000 cycles
                            • logic: (LO)
                              • Minimum switching current
                                5 mA at 24 V DC for configurable relay logic
                                Maximum switching current
                              • R1: 3 A at 250 V AC resistive load, cos phi = 1
                              • R1: 4 A at 30 V DC resistive load, cos phi = 1
                              • R1, R2: 2 A at 250 V AC inductive load, cos phi = 0.4
                              • R1, R2: 2 A at 30 V DC inductive load, cos phi = 0.4
                              • R2: 5 A at 250 V AC resistive load, cos phi = 1
                              • R2: 5 A at 30 V DC resistive load, cos phi = 1
                                • Discrete input number
                                  7
                                  Discrete input type
                                • programmable (sink/source) (LI1...LI4)24...30 V DC, with level 1 PLC
                                • programmable as pulse input 20 kpps (LI5)24...30 V DC, with level 1 PLC
                                • switch-configurable PTC probe (LI6)24...30 V DC
                                • safe torque off (STO)24...30 V DC - 1500 Ohm
                                  • Discrete input logic
                                  • negative logic (sink) (LI1...LI6), > 19 V (state 0), < 13 V (state 1)
                                  • positive logic (source) (LI1...LI6), < 5 V (state 0), > 11 V (state 1)
                                    • Acceleration and deceleration ramps
                                    • ramp switching
                                    • deceleration ramp automatic stop DC injection
                                    • S
                                    • linear
                                    • deceleration ramp adaptation
                                    • U
                                    • CUS
                                      • Braking to standstill
                                        by DC injection
                                        Protection type
                                      • input phase breaks: drive
                                      • overcurrent between output phases and earth: drive
                                      • overheating protection: drive
                                      • short-circuit between motor phases: drive
                                      • thermal protection: drive
                                        • Communication port protocol
                                        • CANopen
                                        • Modbus
                                          • Connector type
                                            1 RJ45 (on front face) for Modbus/CANopen
                                            Physical interface
                                            2-wire RS 485 for Modbus
                                            Transmission frame
                                            RTU for Modbus
                                            Type of polarization
                                            no impedance for Modbus
                                            Number of addresses
                                          • 1-127 for CANopen
                                          • 1-247 for Modbus
                                            • Method of access
                                              slave CANopen
                                              Electromagnetic compatibility
                                            • 1.2/50 µs - 8/20 µs surge immunity test, level 3 conforming to IEC 61000-4-5
                                            • conducted radio-frequency immunity test, level 3 conforming to IEC 61000-4-6
                                            • electrical fast transient/burst immunity test, level 4 conforming to IEC 61000-4-4
                                            • electrostatic discharge immunity test, level 3 conforming to IEC 61000-4-2
                                            • radiated radio-frequency electromagnetic field immunity test, level 3 conforming to IEC 61000-4-3
                                            • voltage dips and interruptions immunity test conforming to IEC 61000-4-11
                                              • Width
                                                60 mm
                                                Height
                                                325 mm
                                                Depth
                                                245 mm
                                                Net weight
                                                3 kg
                                                Option card
                                              • communication card for CANopen daisy chain
                                              • communication card for CANopen open style
                                              • communication card for DeviceNet
                                              • communication card for Ethernet/IP
                                              • communication card for Profibus DP V1
                                                • Functionality
                                                  mid
                                                  Specific application
                                                  other applications
                                                  Standards
                                                • EN/IEC 61800-3
                                                • EN/IEC 61800-5-1
                                                • EN 61800-3 environments 1 category C2
                                                • EN 61800-3 environments 2 category C2
                                                • EN 55011 class A group 1
                                                  • Product certifications
                                                  • UL
                                                  • NOM 117
                                                  • C-Tick
                                                  • CSA
                                                  • GOST
                                                    • Marking
                                                      CE
                                                      Pollution degree
                                                      2 conforming to EN/IEC 61800-5-1
                                                      IP degree of protection
                                                      IP20 conforming to EN/IEC 61800-5-1
                                                      Vibration resistance
                                                    • 1 gn (f = 13-200 Hz) conforming to EN/IEC 60068-2-6
                                                    • 1.5 mm peak to peak (f = 3-13 Hz) conforming to EN/IEC 60068-2-6
                                                      • Shock resistance
                                                        15 gn for 11 ms conforming to EN/IEC 60068-2-27
                                                        Relative humidity
                                                      • 5-95 % without condensation conforming to IEC 60068-2-3
                                                      • 5-95 % without dripping water conforming to IEC 60068-2-3
                                                        • Ambient air temperature for operation
                                                        • -10-50 °C without
                                                        • 50-60 °C with derating factor
                                                          • Ambient air temperature for storage
                                                            -25-70 °C
                                                            Operating altitude
                                                          • <= 1000 m without
                                                          • 1000...3000 m with current derating 1 % per 100 m
                                                            • Operating position
                                                              vertical +/- 10 degree
                                                              Warranty
                                                              18 months

                                                              Documents & downloads

                                                              hide show
                                                              Filter items
                                                              • All

                                                              • CAD Files and Packs

                                                              • Product Brochures

                                                              • Technical Data Catalogues

                                                              • Product Environmental

                                                              • End of Life Manual

                                                              • Installation Instruction

                                                              • Operating Manuals

                                                              • Certificates (MSDS)

                                                              • eTechPub

                                                              • EDS Files

                                                              • GSD files

                                                              Frequently Asked Questions

                                                              hide show

                                                              Do we have CAD drawings for the ATV312 drives?

                                                              Issue:
                                                              Do we have CAD drawings for the ATV312 drives?

                                                              Product Line:
                                                              Altivar ATV312 and ATV31

                                                              Environment:
                                                              All

                                                              Cause:
                                                              Cad drawings

                                                              Resolution:
                                                              Use the following link to the CAD Drawings Catalog.

                                                              https://www.schneider-electric.us/sites/us/en/support/product-support-resources/3d-cad.page


                                                              CTA-ID : 2061638

                                                              What should be checked if an Altivar 61 or 71 display is showing NLP?

                                                              Issue:
                                                              Wondering what should be checked if an Altivar 61 or 71 display is showing NLP?

                                                              Product Line:
                                                              ATV61/71 drives

                                                              Environment:
                                                              All

                                                              Cause:
                                                              Drive displays 'NLP'

                                                              Resolution:
                                                              NLP indicates that no line power is present on the L1, L2 & L3 input terminals of the drive controller.

                                                              Check voltage at the L1, L2 & L3 terminals.
                                                              Check for open circuits on line contactors, circuit breakers, disconnect switches, or fuses.

                                                              If NLP state does not change with correct voltage present on L1, L2, & L3, remove the control board and check for loose connections of ribbon cables inside the drive.
                                                              WARNING: This step should be performed while the drive is powered down, and proper personal protective equipment should be worn. 

                                                              For example: In an ATV71HC25N4 a customer found a loose X3 connector from the control board to the board behind and above the control board. This connector was on a ribbon cable that was about 1 inch by 1 inch. Drive ran OK after this was reseated.

                                                              Is there a problem using Altivar 61 or Altivar 71 drives delta power system?

                                                              Issue:
                                                              Wants to use Altivar 61 or Altivar 71 drives on delta power system.

                                                              Product Line:
                                                              Altivar ATV61 and ATV71

                                                              Environment:
                                                              All

                                                              Cause:
                                                              Needs to know if the RFI filter needs to be disabled when using a corner grounded delta system?

                                                              Resolution:
                                                              As long as the input voltage remains within the normal range there should not be a problem.
                                                              This should be treated the same way as an impedance grounded system.
                                                              Remove the jumper to the left of the power terminal.
                                                              See the section of the installation manual for Operation on an IT (Isolated or impedance grounded neutral) system for details.
                                                              See the drives installation manual for more information and location of the RFI's filter tab.

                                                              The figure 1 example below is for the low horsepower ATV61 and ATV71 drives.


                                                                                                                 Figure 1.

                                                               

                                                              Is there an offer for Nema 4X rated drives?

                                                              Issue:
                                                              Wondering if the ATV61 or ATV71 drives are available in type 4 or 4X enclosures?

                                                              Product Line:
                                                              Altivar ATV61 and ATV71 open type drives

                                                              Environment:
                                                              All

                                                              Cause:
                                                              Needs to get the ATV61 and ATV71 drive in a NEMA 4 or 4X stand alone enclosure.

                                                              Resolution:
                                                              There is not a standard offering for type 4 or 4X enclosures for our drives.
                                                              It may be possible to install the drive in a properly selected enclosure by a local panel builder or contractor.
                                                              Or, contact a local SquareD field office for assistance. They may be able to offer assistance with other options.

                                                              Can the analog output of the ATV61 or ATV71 be set up as 0-10 VDC instead of 4-20 mA?

                                                              Issue:
                                                              Needs to set up a analog output of the ATV61 or ATV71 drive, to be set up as 0-10 VDC instead of 4-20 mA.

                                                              Product Line:
                                                              ATV61 and ATV71

                                                              Environment:
                                                              All

                                                              Cause:
                                                              NA

                                                              Resolution:
                                                              Yes.
                                                              Go to the Input/Output menu (1.5) and set AO1 type to voltage (0-10v range). Set AO1 assignment to the proper setting. The minimum and maxim range can also be adjusted inside the 0-10 V or 4-20  mA ranges.


                                                               

                                                              Why is the keypad not included with ATV61 and ATV71 drives?

                                                              Issue:
                                                              The keypad is not included with ATV61 and ATV71 drives.

                                                              Product Line:
                                                              Altivar 61 and 71 drives

                                                              Environment:
                                                              All

                                                              Cause:
                                                              Customer concerned whether the HMI came with the drive

                                                              Resolution:
                                                              For all ATV61 and ATV71 drives without the letter Z at the end of the part number the keypad is included.
                                                              However, it is easy to not notice the keypad in the packaging material. The keypad is located inside folded cardboard that also functions as packing material. Check inside all folded cardboard packing materials. There is no sticker to indicate that the keypad is inside.

                                                              ATV61 & ATV71 drives with the letter Z at the end of the part number do not include the removable LCD HMI keypad display. These units do have a simplified LED display and programming keys on the face of the control board itself. The removable LCD HMI keypad display may be installed on these units.


                                                               

                                                              What is the part number for the remote keypad for the ATV31?

                                                              Issue:   What is the part number for the remote keypad for the ATV31?
                                                               
                                                              Product Line:   ATV31
                                                               
                                                              Environment:  All
                                                               
                                                              Cause:   Remote keypad kit
                                                               
                                                              Resolution:   The Altivar 31 remote mount keypad kit is VW3A31101.
                                                              The kit includes a keypad, mounting hardware and a 3 meter cable.


                                                               

                                                              Are the EMC filters for ATV31 drives UL or cUL listed?

                                                              Issue:   Are the EMC filters for ATV31 drives UL or cUL listed?
                                                               
                                                              Product Line:   ATV31
                                                               
                                                              Environment:  All
                                                               
                                                              Cause:   UL/CUL listing
                                                               
                                                              Resolution:   No. VW3A31401, VW3A31402, VW3A31403, VW3A31404, VW3A31405, VW3A31406, VW3A31407, VW3A31408 and VW3A31409 are not UL or CUL listed.

                                                               

                                                              What is the replacement fan for an ATV16, ATV18, ATV28, ATV31, ATV11?

                                                              Issue:
                                                              Replacement fans for ATV16, ATV18, ATV28, ATV31, ATV11?
                                                               
                                                              Product Line:
                                                              ATV16 ATV18 ATV28 ATV31 ATV11
                                                               
                                                              Environment:
                                                              All
                                                               
                                                              Cause:
                                                              Replacement parts for obsolete drives.
                                                               
                                                              Resolution: 
                                                              Field replacement parts were never offered for these drives.  The only solution is to replace the drive.
                                                               

                                                              What is the din rail mounting kit part number for the ATV312?

                                                              Issue:
                                                              What is the din rail mounting kit part number for the ATV312?

                                                              Product Line:
                                                              ATV312

                                                              Environment:
                                                              All

                                                              Cause:
                                                              Desire to utilize din mounting kit option

                                                              Resolution:
                                                              The part numbers need to order the mounting kit for this drive are VW3A9804 and VW3A9805.

                                                              VW3A9804 covers the following range of drives: ATV312....
                                                              018M2, H037M2, H055M2, H075M2, H018M3, H037M3, H055M3, H075M3

                                                              VW3A9805 covers the following range of drives: ATV312....
                                                              HU11M2, HU15M2, HU11M3, HU15M3, HU22M3, H037N4, H055N4, H075N4, HU11N4, HU15N4, H075S6, HU15S6
                                                              Note: The din rail mounting kits are only available for the above drives. 

                                                              Note: Other drives not list above do not have a din rail kit.

                                                              What input is designed for a bipolar -10v to +10v input on the ATV32 drives?

                                                              Issue:
                                                              What input is designed for a bipolar -10v to +10v input on the ATV32 drives?

                                                              Product Line:
                                                              Altivar ATV32

                                                              Environment:
                                                              All

                                                              Cause:
                                                              AI2 is default for -10v to +10v input.

                                                              Resolution:
                                                              IO menu AI2 set up

                                                               Bipolar analog input 0 ± 10 V (maximum voltage ± 30 V)

                                                              The + or - polarity of the voltage on AI2 affects the direction of the set point and therefore the direction of operation.

                                                              • Impedance 30 kÙ
                                                              • Resolution: 10 bits
                                                              • Precision ±0.5% in 50/60 Hz for 25 °C, ±0.2% in 50/60 Hz for –10 to +60 °C at Äè = 60°C,
                                                              • Linearity ± 0.2% (max. ± 0.5%), of max. value
                                                              • Sampling time 2 ms

                                                              What is the recommended Fuse or Circuit Breaker (OCPD) size for Altivar 61 drives?

                                                              Refer to the attached Quick Start Annex, document S1B86981. 
                                                               
                                                              Show More