MASTER YOUR CASTLE with your new build or reno project
Enter competition
Soft start-soft stoft unit ATS U01N2
Soft start-soft stoft unit ATS U01N2
Soft start-soft stoft unit ATS U01N2
Soft start-soft stoft unit ATS U01N2

ATSU01N209LT

Soft-Start Stop 9A 200 480V

Soft start-soft stoft unit ATS U01N2
Soft start-soft stoft unit ATS U01N2
Soft start-soft stoft unit ATS U01N2
Soft start-soft stoft unit ATS U01N2
Colour:
Colour: Per UOM Std.
  • 1 PCE
Added to cart
Successfully added, you can view your cart here

Key Features & Specifications

hide show
Range of product
Altistart U01 and TeSys U
Product or component type
soft starter
Product destination
asynchronous motors
Product specific application
simple machine
Device short name
ATSU01
Network number of phases
3 phases
[Us] rated supply voltage
200...480 V - 10...10 %
Motor power kW
  • 4 kW, 3 phases at 400 V
  • 1.5 kW, 3 phases at 230 V
    • Motor power hp
    • 2 hp, 3 phases at 230 V
    • 5 hp, 3 phases at 460 V
      • IcL starter rating
        9 A
        Utilisation category
        AC-53B conforming to EN/IEC 60947-4-2
        Current consumption
        65 mA
        Type of start
        start with voltage ramp
        Power dissipation in W
      • 1.5 W at full load and at end of starting
      • 91.5 W in transient state
        • Assembly style
          with heat sink
          Function available
          integrated bypass
          Supply voltage limits
          180-528 V
          Supply frequency
          50...60 Hz - 5...5 %
          Network frequency
          47.5...63 Hz
          Output voltage
          <= power supply voltage
          [Uc] control circuit voltage
          24 V DC +/- 10 %
          Starting time
        • 1 s / 100
        • 5 s / 20
        • 10 s / 10
        • adjustable from 1 to 10 s
          • Deceleration time symb
            adjustable from 1 to 10 s
            Starting torque
            30...80 % of starting torque of motor connected directly on the line supply
            Discrete input type
            logic (LI1, LI2, BOOST) stop, run and boost on start-up functions <= 8 mA 27 kOhm
            Discrete input voltage
            24...40 V
            Input output isolation
            galvanic between power and control
            Discrete input logic
            positive LI1, LI2, BOOST at State 0: < 5 V and <= 0.2 mA at State 1: > 13 V, >= 0.5 mA
            Discrete output current
          • 2 A DC-13
          • 3 A AC-15
            • Discrete output type
            • open collector logic LO1 end of starting signal
            • relay outputs R1A, R1C NO
              • Discrete output voltage
                24 V (voltage limits: 6...30 V) open collector logic
                Minimum switching current
                10 mA at 6 V DC for relay outputs
                Maximum switching current
              • relay outputs: 2 A at 30 V DC cos phi = 0.5 and L/R = 20 ms inductive load
              • relay outputs: 2 A at 250 V AC AC-15 cos phi = 0.5 and L/R = 20 ms inductive load
                • Maximum switching voltage
                  440 V relay outputs
                  Display type
                • 1 LED (green) for starter powered up
                • 1 LED (yellow) for nominal voltage reached
                  • Tightening torque
                  • 0.5-0.5 N.m
                  • 1.9-2.5 N.m
                    • Electrical connection
                    • 4 mm screw clamp terminal - rigid 1 1...10 mm² AWG 8 power circuit
                    • screw connector - flexible without cable end 2 0.5...1.5 mm² AWG 16 control circuit
                    • screw connector - rigid 1 0.5...2.5 mm² AWG 14 control circuit
                    • 4 mm screw clamp terminal - rigid 2 1...6 mm² AWG 10 power circuit
                    • screw connector - rigid 2 0.5...1 mm² AWG 17 control circuit
                    • screw connector - flexible with cable end 1 0.5...1.5 mm² AWG 16 control circuit
                    • 4 mm screw clamp terminal - flexible without cable end 1 1.5...10 mm² AWG 8 power circuit
                    • screw connector - flexible without cable end 1 0.5...2.5 mm² AWG 14 control circuit
                    • 4 mm screw clamp terminal - flexible with cable end 2 1...6 mm² AWG 10 power circuit
                    • 4 mm screw clamp terminal - flexible without cable end 2 1.5...6 mm² AWG 10 power circuit
                      • Marking
                        CE
                        Operating position
                        vertical +/- 10 degree
                        Height
                        234 mm
                        Width
                        45 mm
                        Depth
                        150 mm
                        Net weight
                        0.34 kg
                        Power range
                      • 1.1-2 kW at 200-240 V 3 phases
                      • 2.2-3 kW at 380-440 V 3 phases
                      • 4-6 kW
                        • Motor starter type
                          soft starter
                          Electromagnetic compatibility
                        • conducted and radiated emissions level B conforming to CISPR 11
                        • immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3
                        • voltage/current impulse level 3 conforming to IEC 61000-4-5
                        • conducted and radiated emissions level 3 conforming to IEC 61000-4-6
                        • immunity to conducted interference caused by radio-electrical fields conforming to IEC 61000-4-11
                        • conducted and radiated emissions level B conforming to IEC 60947-4-2
                        • damped oscillating waves level 3 conforming to IEC 61000-4-12
                        • electrostatic discharge level 3 conforming to IEC 61000-4-2
                        • EMC immunity conforming to EN 50082-1
                        • EMC immunity conforming to EN 50082-2
                        • harmonics conforming to IEC 1000-3-2
                        • harmonics conforming to IEC 1000-3-4
                        • immunity to electrical transients level 4 conforming to IEC 61000-4-4
                          • Standards
                            EN/IEC 60947-4-2
                            Product certifications
                          • UL
                          • C-Tick
                          • CSA
                          • CCC
                            • IP degree of protection
                              IP20
                              Pollution degree
                              2 conforming to EN/IEC 60947-4-2
                              Vibration resistance
                            • 1 gn (f= 13-150 Hz) conforming to EN/IEC 60068-2-6
                            • 1.5 mm peak to peak (f= 3-13 Hz) conforming to EN/IEC 60068-2-6
                              • Shock resistance
                                15 gn for 11 ms conforming to EN/IEC 60068-2-27
                                Relative humidity
                                5-95 % without condensation or dripping water conforming to EN/IEC 60068-2-3
                                Ambient air temperature for operation
                              • -10-40 °C (without)
                              • 40-50 °C (with current derating of 2 % per °C)
                                • Ambient air temperature for storage
                                  -25-70 °C conforming to EN/IEC 60947-4-2
                                  Operating altitude
                                • <= 1000 m without
                                • > 1000 m with current derating of 2.2 % per additional 100 m
                                  • REACh Regulation
                                    Reference contains Substances of Very High Concern above the threshold
                                    REACh free of SVHC
                                    Yes
                                    EU RoHS Directive
                                    Pro-active compliance (Product out of EU RoHS legal scope)
                                    Toxic heavy metal free
                                    Yes
                                    Mercury free
                                    Yes
                                    RoHS exemption information
                                    Yes
                                    China RoHS Regulation
                                    X
                                    Circularity Profile
                                    ENVEOLI100217EN
                                    WEEE
                                    The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                                    CALIFORNIA PROPOSITION 65
                                    WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
                                    Warranty
                                    18 months

                                    Documents & downloads

                                    hide show
                                    Filter items
                                    • All

                                    • CAD Files and Packs

                                    • Product Brochures

                                    • Technical Data Catalogues

                                    • End of Life Manual

                                    • Installation Instruction

                                    • Handout

                                    • Product Environmental

                                    • Data Bulletin

                                    • Certificates (MSDS)

                                    • eTechPub

                                    Frequently Asked Questions

                                    hide show

                                    What are the adjustment ranges for the dials on an ATSU01N2..LT?

                                    For both the START TIME and STOP TIME dials, setpoint A is 1second and setpoint E is 10seconds.  There is a linear relationship from A to E setpoints.
                                    For the INITIAL VOLTAGE dial, setpoint A is 30% and setpoint E is 80% of full voltage.  There is a linear relationship from A to E setpoints.



                                    CTA-ID : 2061385

                                    Does the ATS01 come with a shorting contactor?

                                    Issue:
                                    Does the ATS01 come with a shorting contactor?

                                    Product Line:
                                    Altistat 01

                                    Environment:
                                    All

                                    Cause:
                                    N/A

                                    Resolution:
                                    All of the ALTISTART 01 models, except the ATS01N103FT and ATS01N106FT, have an internal shorting contactor as standard.

                                    Is the LH4N still available?

                                    Issue:
                                    Is the LH4N still available?

                                    Product Line:
                                    LH4N

                                    Environment:
                                    All models and all serial numbers

                                    Cause:
                                    Customer was looking for purchasing the LH4N112RT7.

                                    Resolution:
                                    No, the LH4N soft starter is obsolete. Please replace with the appropriate ATS01 or ATS22 soft starter. Consider application needs and features of currently-offered products.


                                     

                                    Are Softstarters acceptable for use in a Fire Pump applications?

                                    Issue:
                                    Are Softstarters acceptable for use in a Fire Pump applications?

                                    Product line:
                                    Altistart 22 48 ATS22 ATS48

                                    Environment:
                                    all

                                    Cause:
                                    Fire pump systems typically require the motors to run until they fail, without faulting the controller

                                    Resolution:
                                    No. The softstarters are not rated for Fire pump requirements and does not meet the requirements.