Blank plate
ACTMPBP
Blank plate
ACTMPBP

Snap in Blank Module Plate

Catalogue Number: ACTMPBP
Blank plate
ACTMPBP
Blank plate
ACTMPBP
Retail
$21.93
RRP (Inc. GST)

Specifications

hide show
Range
Actassi
Product or component type
blank plate
Accessory / separate part destination
optic cassette
Fixing mode
snap-in
Package 1 Weight
18.7 g
Package 1 Height
15 cm
Package 1 width
4.7 cm
Package 1 Length
4.7 cm
EU RoHS Directive
Pro-active compliance (Product out of EU RoHS legal scope)
China RoHS Regulation
Product out of China RoHS scope. Substance declaration for your information

Frequently Asked Questions

hide show

Where are your NetworkAIR ACFM manuals?

Issue:
Where are your NetworkAIR ACFM manuals?
 
Product line:
FM, ACFM
 
Environment:
Data Center Cooling
 
Cause:
 
Resolution:
The NetworkAIR ACFM has been discontinued and is not featured on our website as a current product.  Below you will find archived manuals that should be able to assist you.  If you require more assistance, please call our technical support office at 888-695-6500 and hit option 2 three times.

The modular, Floor Mount computer room air-conditioning system offers efficient, effective and economical cooling for a variety of spaces.  Computer room environmental requirements now reach far beyond the confines of the traditional data center or computer room to encompass a larger suite of applications,  referred to as technology rooms.  Critical environment applications include:
  • Computer rooms
  • Telecommunication facilities
  • Clean rooms
  • Power equipment
  • Medical equipment rooms
  • Archives
  • LAN/WAN environments

An Explanation on FM Dew point temperature to control humidity

Issue:
An Explanation on FM Dew point temperature to control humidity

Product line:
ACFM

Environment:
DataCenter Room Cooling

Cause:

Resolution:
" When the FM systems belong to a group the FM uses the dew point temperature to control humidity. Dew point is a function of both temperature and humidity so you must take temperature into account when calculating humidification demand.

The dew point temperature setpoint for humidification is calculated from the humidification setpoint and the reheat setpoint (use cooling setpoint if reheat is not present). The dew point of the room is calculated from the return humidity and the return temperature.
The dew point temperature setpoint for dehumidification is calculated from the dehumidification setpoint and the cooling setpoint.
For example, if the reheat setpoint is 68 F and the humidification setpoint is 50%, the dew point setpoint is 49 F. If the room temperature is 74 F and the return humidity is 40% the dew point of the room is 48 F.

The humidifier demand is calculated as the difference between the actual room dew point and the desired room dew point divided by the sensitivity. So in this example;
Demand = (49 - 48) / 2 = 0.5 or 50% demand. So the humidifier output will be about 50%.

There is one other note. Versions of the FM controller firmware v6.7.0 and earlier do not calculate low and high humidity alarms correctly. This has been corrected in version 6.11.0 which has been released.

I.E.:
COOL SETPOINT / DEHUMID SETPOINT = DEWPOINT HIGH LEVEL
REHEAT SETPOINT / HUMID SETPOINT = DEWPOINT LOW LEVEL"