Universal Power Supply 20A
PF106454SE
Universal Power Supply 20A
PF106454SE

Catalogue Number: ABL8RPM24200

Phaseo Regulated SMPS, 1 or 2 Phase, 100..240V, 24V, 20A

Universal Power Supply 20A
PF106454SE
Universal Power Supply 20A
PF106454SE
Colour:
Colour: Per UOM Std.
  • 1 PCE
Added to cart
Successfully added, you can view your cart here

Key Features & Specifications

hide show
Range of product
Phaseo
Product or component type
power supply
Power supply type
regulated switch mode
Input voltage
  • 100...120 V AC single phase, terminal(s): N-L1
  • 200...240 V AC phase to phase, terminal(s): L1-L2
    • Output voltage
      24 V DC
      Rated power in W
      480 W
      Provided equipment
      power factor correction filter conforming to IEC 61000-3-2
      Power supply output current
      20 A
      Output protection type
    • against overload, protection technology: manual or automatic reset
    • against overvoltage, protection technology: 30...32 V, manual reset
    • against short-circuits, protection technology: manual or automatic reset
    • against undervoltage, protection technology: tripping if U < 21.6 V
    • thermal, protection technology: automatic reset
      • Ambient air temperature for operation
      • 50-60 °C (with derating factor)
      • -25-50 °C (without)
        • Input voltage limits
        • 85...132 V
        • 170...264 V
          • Network frequency
            47...63 Hz
            Inrush current
            30 A 2 ms
            Cos phi
          • 0.68-0.68 at 240 V
          • 0.69-0.69 at 120 V
            • Efficiency
              88 %
              Output voltage limits
              24...28.8 V adjustable
              Power dissipation in W
              57.6 W
              Line and load regulation
              1...3 %
              Holding time
            • >= 120 ms at 400 V
            • >= 20 ms at 100 V
            • >= 40 ms at 240 V
              • Permissible temporary current boost
                1.5 x In (for 4 s)
                Connections - terminals
              • for diagnostic relay: removable screw terminal block, connection capacity: 2 x 2.5 mm²
              • for input connection: screw type terminals, connection capacity: 3 x 0.5...3 x 4 mm² AWG 22...AWG 12
              • for input ground connection: screw type terminals, connection capacity: 1 x 0.5...1 x 4 mm² AWG 22...AWG 12
              • for output connection: screw type terminals, connection capacity: 4 x 0.5...4 x 4 mm² AWG 22...AWG 12
                • Marking
                  CE
                  Mounting support
                • 35 x 7.5 mm symmetrical DIN rail
                • 35 x 15 mm symmetrical DIN rail
                  • Operating position
                    vertical
                    Operating altitude
                    2000 m
                    Output coupling
                  • series
                  • parallel
                    • Name of test
                    • electrostatic discharges conforming to EN/IEC 61000-4-2
                    • induced electromagnetic field conforming to EN/IEC 61000-4-6
                    • magnetic field conforming to EN 61000-4-8
                    • primary outage conforming to IEC 61000-4-11
                    • radiated electromagnetic field conforming to EN/IEC 61000-4-3
                    • rapid transient conforming to IEC 61000-4-4
                    • surge conforming to EN/IEC 61000-4-5
                    • conducted emissions on the power line conforming to EN 55022 class B
                    • radiated emissions conforming to EN 55022 class B
                    • harmonic current emission conforming to EN/IEC 61000-3-2
                      • Status LED
                      • 1 LED (green and red)output voltage:
                      • 1 LED (green, red and orange)output current:
                        • Depth
                          145 mm
                          Height
                          125 mm
                          Width
                          146 mm
                          Net weight
                          1.6 kg
                          Anti-harmonic filter
                          low frequency harmonic currents
                          Compatibility code
                          ABL8R
                          MTBF reliability
                        • 717000 H at 100 V AC with UTE C80-810 calculation method
                        • 695000 H at 240 V AC with UTE C80-810 calculation method
                          • Product certifications
                          • cCSAus
                          • EAC
                          • KC
                          • RCM
                          • UL
                            • Standards
                            • CSA C22.2 No 60950-1
                            • UL 508
                              • Environmental characteristic
                              • EMC conforming to EN 61000-6-1
                              • EMC conforming to EN 61000-6-3
                              • EMC conforming to EN 55024
                              • EMC conforming to EN/IEC 61000-6-4
                              • EMC conforming to EN/IEC 61204-3
                              • safety conforming to EN/IEC 60950-1
                              • safety conforming to EN/IEC 61204-3
                              • safety conforming to SELV
                                • IP degree of protection
                                • IP20 conforming to EN/IEC 60529
                                • IP10
                                  • Ambient air temperature for storage
                                    -40-70 °C
                                    Relative humidity
                                  • 0-90 % during operation
                                  • 0-95 % in storage
                                    • Overvoltage category
                                      class I conforming to VDE 0106-1
                                      Dielectric strength
                                    • 2500 V between input and ground
                                    • 3000 V between input and output
                                    • 500 V between output and ground
                                      • Sustainable offer status
                                        Green Premium product
                                        REACh Regulation
                                        Free of Substances of Very High Concern above the threshold
                                        EU RoHS Directive
                                        Pro-active compliance (Product out of EU RoHS legal scope)
                                        Mercury free
                                        Yes
                                        RoHS exemption information
                                        Yes
                                        China RoHS Regulation
                                        X
                                        Environmental Disclosure
                                        ENVPEP061202EN
                                        Circularity Profile
                                        ENVEOLI0612002EN
                                        California proposition 65
                                        WARNING: This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov
                                        Warranty
                                        18 months

                                        Documents & downloads

                                        hide show
                                        Filter items
                                        • All

                                        • CAD Files and Packs

                                        • Product Brochures

                                        • Technical Data Catalogues

                                        • Installation Instruction

                                        • End of Life Manual

                                        • Product Environmental

                                        • Data Bulletin

                                        • Handout

                                        • Operating Manuals

                                        • eTechPub

                                        • Certificates (MSDS)

                                        • Declaration of Conformity

                                        Frequently Asked Questions

                                        hide show

                                        What is the mean time between failures (MTBF) for ABL8RPM24200?

                                        The 2 MTBF values for ABL8RPM24200 are;

                                        • 717000h for 100Vac
                                        • 695000h for 240Vac