Quantcast

Acti9 iARC 1PN 25A AFDS

Acti9 iARC 1PN 25A AFDS

Acti9 iARC 1PN 25A AFDS

Item Number: A9TS1225

Retail
$360.13
RRP (Inc. GST)

Product Dimensions

Width icon

Width36 mm

Height icon

Height91 mm

Depth icon

Depth75 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

Acti9

Product or component type

arc fault detection switch

Sustainable offer status

Green Premium product

Physical

[Ue] rated operational voltage

230...240 V AC 50 Hz conforming to IEC 62606

Control type

toggle

Local signalling

ON, OFF, fault trip

Mounting mode

clip-on

Mounting support

DIN rail

Mechanical durability

20000 cycles

Electrical durability

10000 cycles 240 V AC 50 Hz conforming to IEC 62606

Connections - terminals

  • tunnel type terminal2 cable(s) 2.5-2.5 mm² rigid
  • tunnel type terminal1 cable(s) 16-16 mm² rigid
  • tunnel type terminal2 cable(s) 2.5-2.5 mm² flexible
  • tunnel type terminal1 cable(s) 10-10 mm² flexible
    • Cable entry

      top and bottom

      Wire stripping length

      14 mm

      Height

      91 mm

      Width

      36 mm

      Depth

      75 mm

      Net weight

      205 g

      IP degree of protection

      IP20 conforming to IEC 60529

      Relative humidity

      95-95 % at 55-55 °C

      Ambient air temperature for operation

      -25-60 °C

      Ambient air temperature for storage

      -40-80 °C

      Standards

      IEC 62606

      EU RoHS Directive

      Compliant

      Mercury free

      Yes

      RoHS exemption information

      Yes

      China RoHS Regulation

      Product out of China RoHS scope. Substance declaration for your information

      Environmental Disclosure

      ENVPEP1906001EN

      Circularity Profile

      ENVEOLI1906001EN

      Others

      Product specific application

      arc fault detection

      Product name

      Acti 9 iARC

      Device short name

      iARC

      Poles description

      1P + N

      Neutral position

      left

      Network type

      AC

      Rated breaking and making capacity

      Im = 500 A

      Rated conditional short-circuit current

    • upstream MCB 25A: Inc 10 kA
    • upstream RCBO 25A: Inc 10 kA
      • Device location in system

        outgoer

        Maximum [In] rated current

        25 A

        Network frequency

        50 Hz

        [Ui] rated insulation voltage

      • 250 V AC 50 Hz between phase and neutral
      • 400 V AC 50 Hz between phases
        • [Uimp] rated impulse withstand voltage

          4 kV conforming to IEC 62606

          Threshold tripping voltage

          275 V +/- 5 V

          Contact position indicator

          yes

          Heat dissipation

          4.38-4.38 W at 240 V - 25 A

          Locking options description

          padlocking device

          Tightening torque

          2-2 N.m

          9 mm pitches

          4

          Pollution degree

          2 conforming to IEC 62606

          Overvoltage category

          III

          Tropicalisation

          severity B conforming to IEC 60068-2-30 for 28 d

          Operating altitude

          2000 m

          Quality labels

          RCM
          Show all specifications

          Documents & downloads

          hide show
          Filter items
          • All

          • Installation Instruction

          • End of Life Manual

          • Product Environmental

          • Certificates (MSDS)

          Frequently Asked Questions

          hide show

          What is the part number for 2 pole 25amp Acti 9 C/B?

          A9F44225

          Can an AFDD replace an earth leakage current protection device?

          The new AFDD comes with different versions:
          - Without a protection against earth leakage current (Catalogue No. A9TS1225 for commercial applications). In this case, AFDD, can help to provide a protection against arc faults (serial arc faults, parallel arc faults and arc to earth). Indeed, even if it helps to protect against electrical arcs between phase and earth, because of its design and technology, monitoring and protection provided by arc detectors is not equivalent to the one provided by a traditional earth leakage protection device.
          - With a protection against earth leakage current. All Clipsal branded AFDD references for residential applications and remaining Schneider branded AFDD references for commercial applications come with protection against earth leakage current. in this case AFDD can provide a combined protection against overcurrent, overvoltage, arc faults (serial arc fault, parallel arc fault and arc to earth) and earth leakage.
           

          What is the replacement part for a 26896 RCB?

          The replacement part is a A9D61820.
          A9D11220 is best solution
          A9D11820 is an alternative 1 pole wide but no Neutral switching
          A9D61820 is an alternative 1 pole wide but no Neutral switching and only 6kA