Quantcast

Acti 9 Miniature Circuit Breaker, C60H, 2 Poles, 16A, C Curve, 500V

Acti 9 Miniature Circuit Breaker, C60H, 2 Poles, 16A, C Curve, 500V

Acti 9 Miniature Circuit Breaker, C60H, 2 Poles, 16A, C Curve, 500V

Item Number: A9N61531

Retail
$207.98
RRP (Inc. GST)

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

C60

Range

Acti 9

Product or component type

miniature circuit-breaker

Device application

distribution

Product compatibility

  • C60 auxiliary
  • C60 accessories
    • Market segment

    • small commercial
    • residential
      • Sustainable offer status

        Green Premium product

        Warranty

        18 months

        Physical

        [In] rated current

        16 A at 25 °C

        [Ue] rated operational voltage

        500 V DC

        Control type

        toggle

        Local signalling

        ON/OFF indication

        Mounting mode

        fixed

        Mounting support

        35 mm symmetrical DIN rail

        Net weight

        0.256 kg

        Mechanical durability

        20000 cycles

        Electrical durability

        6000 cycles 500 V DC

        Standards

      • EN 60947-2
      • IEC 60947-2
        • Ambient air temperature for operation

          -25-70 °C

          Ambient air temperature for storage

          -40-85 °C

          REACh Regulation

          Free of Substances of Very High Concern above the threshold

          REACh free of SVHC

          Yes

          EU RoHS Directive

          Compliant

          Mercury free

          Yes

          RoHS exemption information

          Yes

          China RoHS Regulation

          Product out of China RoHS scope. Substance declaration for your information

          Environmental Disclosure

          ENVPEP120608EN_V0

          Others

          Product name

          Acti 9 C60H-DC

          Device short name

          C60H-DC

          Poles description

          2P

          Number of protected poles

          2

          Network type

          DC

          Trip unit technology

          thermal-magnetic

          Curve code

          C

          Breaking capacity code

          H

          Breaking capacity

        • 10 kA Icu at 440 V DC conforming to EN 60947-2
        • 10 kA Icu at 440 V DC conforming to IEC 60947-2
        • 6 kA Icu at 500 V DC conforming to EN 60947-2
        • 6 kA Icu at 500 V DC conforming to IEC 60947-2
        • 20 kA Icu at 220 V DC conforming to GB 14048.2
        • 20 kA Icu at 220 V DC conforming to IEC 60947-2
        • 20 kA Icu at 250 V DC conforming to GB 14048.2
        • 20 kA Icu at 250 V DC conforming to IEC 60947-2
          • Utilisation category

          • category A conforming to EN 60947-2
          • category A conforming to IEC 60947-2
            • Suitability for isolation

            • yes conforming to IEC 60947-2
            • yes conforming to EN 60947-2
              • Network frequency

                50/60 Hz

                [Ics] rated service breaking capacity

              • 15 kA 75 % conforming to EN 60947-2 - 220 V DC
              • 15 kA 75 % conforming to IEC 60947-2 - 220 V DC
              • 15 kA 75 % conforming to EN 60947-2 - 250 V DC
              • 15 kA 75 % conforming to IEC 60947-2 - 250 V DC
              • 4.5 kA 75 % conforming to EN 60947-2 - 500 V DC
              • 4.5 kA 75 % conforming to IEC 60947-2 - 500 V DC
              • 7.5 kA 75 % conforming to EN 60947-2 - 440 V DC
              • 7.5 kA 75 % conforming to IEC 60947-2 - 440 V DC
                • [Ui] rated insulation voltage

                • 500 V DC conforming to IEC 60947-2
                • 500 V DC conforming to EN 60947-2
                  • [Uimp] rated impulse withstand voltage

                  • 6 kV conforming to EN 60947-2
                  • 6 kV conforming to IEC 60947-2
                    • Contact position indicator

                      yes

                      Comb busbar and distribution block compatibility

                      top or bottom: standard

                      9 mm pitches

                      4

                      Provision for padlocking

                      padlockable

                      Locking options description

                      in position O

                      Tightening torque

                      power circuit: 2.5-2.5 N.m top or bottom

                      Earth-leakage protection

                      without

                      Compatibility code

                      C60H-DC

                      Pollution degree

                    • 3 conforming to EN 60947-2
                    • 3 conforming to IEC 60947-2
                      • Overvoltage category

                        IV

                        Tropicalisation

                        2 conforming to IEC 60068-2

                        Operating altitude

                        2000 m

                        Package 1 Weight

                        228 g

                        Package 1 Height

                        0.75 dm

                        Package 1 width

                        0.36 dm

                        Package 1 Length

                        0.85 dm
                        Show all specifications

                        Frequently Asked Questions

                        hide show

                        What is the part number of a 2 pole, 50A, 6KA, C curve DC circuit breaker?

                        A9N61538 is the part number of a 2 pole, 50A, 6KA, C curve C60H DC circuit breaker.
                        For further information, please visit https://www.schneider-electric.co.uk/en/product/A9N61538/miniature-circuit-breaker---c60h---2-poles---50-a---c-curve/
                        Schneider Eletric A9N61538 Picture
                         

                        What is the part code for SW60DC breaker for 275V dc 16Amp 2P

                         The part code is MGN61531

                        What is the part code for a Fuse Carrier STI, 1 pole.?

                         The Multi9 part code is 15636
                        The Acti9 part code is A9N15636

                        If a 3 pole 63A ,D curve 10kA MCB is no longer available in the C120 frame - what can I use instead?



                        Code = A9N18511  3 pole, 15kA, 63A, (27mm wide)   

                        What is the code for a 2 pole, 10A, MCB suitable for 300Vdc?

                        The code will be A9N61528. This is C curve, 6kA, and rated up to 500Vdc

                        For more information see below:
                        https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=A9N61528