Acti 9 Din-Rail Kwh Meter, Iem3555 Meter, 1 DI, 1 DO, Rogowski coil

Catalogue Number: A9MEM3555
iEM3000 Series iEM3455 Product Image
PB113599.eps iEM33xx Dimensions Drawing
Generic_iEM3000_Product_Image
iEM3000 Series iEM3455 Product Image
PB113599.eps iEM33xx Dimensions Drawing
Generic_iEM3000_Product_Image
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Range
Acti 9
Product name
Acti 9 iEM3000
Device short name
iEM3555
Product or component type
energy meter
Market segment
Poles description
  • 3P
  • 3P + N
  • 1P + N
    • Type of measurement
    • active and reactive energy
    • active and reactive power
    • current
    • voltage
      • Metering type
        active, reactive, apparent energy (signed, four quadrant)
        Device application
      • multi-tariff
      • partial meter
      • sub billing
        • Accuracy class
        • class 0.5S active energy conforming to IEC 62053-22
        • class 0.5S active energy conforming to ANSI C12.20
          • Analogue input type
            Rogowski coil 50...5000 A
            Rated voltage
          • 100-277 V +/- 20 %
          • 173-480 V +/- 20 %
            • Network frequency
            • 50 Hz
            • 60 Hz
              • Technology type
                electronic
                Display type
                LCD display
                Sampling rate
                32 samples/cycle
                Measurement current
                50-5000 A
                Maximum value measured
              • 99999999.9 kWh
              • 99999999 MWh
                • Information displayed
                  tariff (4)
                  Communication port protocol
                  Modbus RTU at 9.6, 19.2 and 38.4 kbauds even/odd or none
                  Communication port support
                  screw terminal block: RS485
                  Local signalling
                • green indicator light: power ON
                • yellow flashing LED: accuracy checking
                • alarm: overload
                • yellow indicator light: communications are active on the Modbus port (Modbus)
                  • Number of inputs
                    1 digital 0...5 V/11...40 V 24 V DC
                    Number of outputs
                    1 digital (static)
                    Output voltage
                    5...40 V DC@50 mA
                    Mounting mode
                    clip-on
                    Mounting support
                    DIN rail
                    Connections - terminals
                  • current circuit: screw terminals 6-6 mm² cable(s)
                  • voltage circuit: screw terminals 2.5-2.5 mm² cable(s)
                  • input/output circuit: screw terminals 1.5-1.5 mm² cable(s)
                  • communication: screw terminals 2.5-2.5 mm² cable(s)
                    • Tightening torque
                    • input/output circuit: 0.5-0.5 N.m Philips screwdriver
                    • voltage circuit: 0.5-0.5 N.m Philips screwdriver
                    • current circuit: 0.8-0.8 N.m pozidriv screwdriver
                    • communication: 0.5-0.5 N.m Philips screwdriver
                      • Wire stripping length
                      • input/output circuit: 6 mm
                      • voltage circuit: 8 mm
                      • current circuit: 8 mm
                      • communication: 7 mm
                        • Standards
                        • UL 61010-1
                        • IEC 62053-21
                        • IEC 61036
                        • IEC 61557-12
                        • IEC 62053-23
                        • IEC 61010
                          • Product certifications
                          • CE conforming to IEC 61010 (safety)
                          • CE conforming to EN 61557-12 (power monitor)
                          • CE conforming to IEC 61326-1 (EMC)
                          • cULus conforming to UL 61010 (safety)
                          • cULus conforming to ANSI C12.20 (sub-meter)
                          • EAC (sub-meter)
                          • RCM conforming to NMI M 6-1 (sub-meter)
                          • UL
                            • Compatibility code
                              iEM3555
                              IP degree of protection
                            • IP40 front panel: conforming to IEC 60529
                            • IP20 body: conforming to IEC 60529
                              • IK degree of protection
                                IK08
                                Pollution degree
                                2
                                Relative humidity
                                5-95 % at 36-36 °C
                                Ambient air temperature for operation
                              • -25-70 °C - MID
                              • -25-70 °C - NMI
                              • -25-70 °C - IEC
                                • Ambient air temperature for storage
                                  -40-85 °C
                                  Operating altitude
                                  < 3000 m
                                  9 mm pitches
                                  10
                                  Width
                                  90 mm
                                  Height
                                  87 mm
                                  Depth
                                  69 mm
                                  EU RoHS Directive
                                  Compliant
                                  Mercury free
                                  Yes
                                  RoHS exemption information
                                  Yes
                                  China RoHS Regulation
                                  X
                                  WEEE
                                  The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                                  California proposition 65
                                  WARNING: This product can expose you to chemicals including: Carbon-black extracts and Bisphenol A (BPA) which is known to the State of California to cause Carcinogen and Reproductive harm. For more information go to www.p65warnings.ca.gov

                                  Documents & downloads

                                  hide show
                                  Filter items
                                  • All

                                  • CAD Files and Packs

                                  • Product Brochures

                                  • Movies

                                  • Technical Data Catalogues

                                  • Technical Leaflet

                                  • Product Environmental

                                  • End of Life Manual

                                  • Installation Instruction

                                  • Handout

                                  • Data Bulletin

                                  • Operating Manuals

                                  • Specifications

                                  • Case Studies

                                  • Certificates (MSDS)

                                  • White Paper

                                  • Declaration of Conformity

                                  • Software - Released

                                  • Firmware - Updates

                                  • Software - Updates

                                  Frequently Asked Questions

                                  hide show

                                  What size cables will the termninals in the Energy Meters , A9MEM3155 & the A9MEM3355 allow?

                                  A9MEM3155 - 16mm
                                  A9MEM3355 - 50mm
                                  For further information , visit links below:-
                                  https://www.schneider-electric.com.au/en/search/A9MEM3155
                                  https://www.schneider-electric.com.au/en/search/A9MEM3355
                                  User-added image

                                  Can you retrieve data from the A9MEM3155 modbus meter wireless using a Modbus to WiFi converter?

                                  We recommend to use  standard tested SE solution like using COM'X with Wifi dongle, which can be connected to iEM3155 over Modbus RTU and COM'X will sendthe data of meter over Wifi.

                                   

                                  Which KWH meter will measure Solar inputs with Modbus connections?

                                  Is the Acti 9 A9MEM3110 3 phase?

                                  Yes, the iEM3110 kWh meter with pulse output, is a 3 phase digital meter for direct connection up to 63Amps.

                                  What is the alternate part number for 17072

                                   Replacement is a A9MEM3210

                                  Do you have a Bacnet, NMI approved kilowatt hour meter with CT's?

                                  The part number for a Bacnet, NMI approved kilowatt-hour meter with CT's is a - A9MEM3265.


                                   

                                  What is the alternative code for 17072?

                                  A9MEM3210

                                  Can the IEM3000 series read energy output from a Solar Panel?

                                  To be able to measure the energy out from a Solar Panel a meter needs to be able to do Four Quadrant Calculation.

                                  This means it is capable of Identification of imported and exported active and reactive energy allows you to monitor energy flow in both directions: delivered from the utility and produced on-site.

                                  In the iEM3000 series the following meters are capable of Four Quadrant Calculation.

                                  iEM31** range - iEM3135, iEM3155, iEM3165, and iEM3175
                                  iEM32** range - iEM3235, iEM3255, iEM3265, and iEM3275
                                  iEM33** range - iEM3335, iEM3355, iEM3365, and iEM3375
                                  iEM34** range - iEM3455, iEM3465, iEM3555, and iEM3565


                                   

                                  Power Meter Communication issue, registers not reading the correct value.

                                  The Power meters, based on the manufacturing location may have an offset. 

                                  In some meters the registers starts from Zero and some it is taken account from 1. So the published register list varies accordingly. 

                                  For Ex: If Register 2017 is for Frequency of the meters it will read 50 HZ. 
                                  But for the meter with offset the the Register 2016 will read 50HZ. 

                                  So it is good to check if the meter has got an Offset before proceeding with the communication issue. 

                                  ETSNZ - What Single Phase Check Meter does not Require a Neutral Through Connection

                                  The New range of Acti9  A9MEM2150 for example only needs a N connection  - it does not require to pass the N current through it.

                                  On the PowerTag A9 F63 model, ref. A9MEM1562 if I try to be consistent with the flat cable position, the LED of the module is upwards. Should I twist the flat cable to have the LED down?

                                  This has no impact on the operation but to be consistent with the rest of the range we favor the Led down, and in this case, the flat cable is twisted.

                                  What is the replacement for 15467 Power meter with 100/5 CTs?

                                  What is the part number for Single phase KWH meter?

                                  The part number for Single phase KWH meter will be a - A9MEM2105.
                                  Please refer the below link for more information,
                                  https://www.schneider-electric.com/en/product/A9MEM2105/modular-single-phase-power-meter-iem2105---230v---63a-with-pulse/
                                  Image result for a9mem2105 schneider



                                   

                                  Can Rogowski Coil Current Transformers (Rope Style CT's) Be Extended in the Field? How Far?

                                  Issue
                                  Rogowski Coil CT's may require secondary lead length extension.

                                  Product Line
                                  A9MEM3500 meters
                                  EM4200 meters
                                  EM3500 meters
                                  U018 Rogowski Coil Current Transformers

                                  Environment
                                  Metering & Power Monitoring

                                  Cause
                                  The load may be farther from the meter than the standard 8' or 12' secondary lead lengths may reach.

                                  Resolution
                                  Schneider Rogowski Coil Current Transformers come in primary lengths of 12", 18", 24", or 36". 
                                  This measurement only applies to the primary length only.
                                  This is the length that the current transformer has to connect back to itself around a conductor or set of conductors of the load to be monitored.

                                  The lead length refers to the 8' or 12' that connects from the current transformer to the meter itself.

                                  It is sometimes difficult to get the meter mounting location within 8' or 12' from an appropriate location to install the current transformer on the load conductors.
                                  Because of this, one may need to extend the length of the secondary leads from the current transformers.

                                  Either the 8' or the 12' secondary lead length version of Schneider's Rogowski Coil (U018-xxx) Current Transformers may be extended to a maximum of 20' total lead length (to include the original lead length of either 8' or 12').
                                  The conductors used must be a standard 24 gauge twisted cable.

                                  What is the replacement for a 17072

                                   The replacement is a A9MEM3210.

                                  What are the power terminal sizes on the A9MEM3100?

                                  The power terminal sizes of the iEM3100 meter will take 16mm cable
                                  see instruction sheet....https://eshop.schneider-electric.com/Download.aspx?infos=H808089_1.pdf;3

                                  What is the product code for the iEM2000 Acti9 230V 40A din rail mount energy monitor?

                                  The product code is A9MEM2000. Please see the attached datasheet for more information.
                                   

                                  What are the Dimensions for the A9MEM2000 single phase power meter?

                                    9 mm pitches 2  
                                   
                                   
                                    Width 18 mm  
                                   
                                   
                                    Height 95 mm  
                                   
                                   
                                    Depth 67 mm  
                                   
                                   
                                    Product weight 0.073 kg  

                                  Energy Meter Kit part number and cross comparison guide

                                  Issue
                                  Energy Meter Kit part numbers and cross comparison guide

                                  Product Line
                                  iEM3455 series meter

                                  Environment
                                  Handout, Meter kit Cross Reference

                                  Cause
                                  Need to find part numbers for the Energy Meter Kit

                                  Resolution
                                  See the attached documentation below:

                                  Install an energy meter kit for a fast and easy energy management solution. With an
                                  included meter, enclosure, and LVCT, the meter kit is customizable according to your
                                  needs and easily installed. This compact, energy management solution allows you to
                                  understand energy use, meet compliance codes, access tenant sub-metering and
                                  improve energy costs.​

                                   

                                  How to add the I-Line Smart Cell device into Power Monitoring Expert

                                  Issue
                                  Customer would like to incorporate the I-Line Smart Cell into their existing power monitoring system.

                                  Product Line
                                  I-Line Smart Cell

                                  Environment
                                  Power Monitoring Expert 8.x
                                  Power Monitoring Expert 7.2.2
                                  Struxureware Power Monitoring 7.0.1

                                  Resolution
                                  To add the I-Line Smart Cell into Power Monitoring Expert, first identify the communication component. Using the table below, find the corresponding communication device (ie. IFE, IFM, EM3555, or EM3560).
                                   
                                  Catalog Number Voltage Feature Additional Circuit Breaker Notes
                                  ICWL*2222E1M0 120 Vac - 240 Vac 1 IFE Ethernet Modbus TCP interface with basic Web pages Contains 1 IFE, with space for 6 additional IFMs
                                  ICWL*2422E1M0 277 Vac - 480 Vac
                                  ICWL*2222M01 120 Vac - 240 Vac 1 IFM Modbus serial interface Contains 1 IFM, optional 8 additional IFMs, for a total of 9 monitored circuit breakers
                                  ICWL*2422M01 277 Vac - 480 Vac
                                  ICWL*263X3555 120 Vac - 600 Vac EM3555 Meter Contains 1 power meter
                                  ICWL*263X3560 120 Vac - 600 Vac EM3560 Meter


                                  Adding the IFE as an Ethernet Device
                                  1. Open Management Console
                                  2. Click the Devices icon.
                                  3. Right-click the display window and select New > Ethernet Device.
                                  4. Fill in the Group, Name, Device Type and TCP/IP Address fields. Configure the other fields as you require.
                                   
                                  Adding the IFM as a Serial Device on Ethernet Gateway
                                  To set up devices for Ethernet gateway communications, first add and configure an Ethernet
                                  gateway site.
                                  1. Open Management Console
                                  2. Click the Sites icon.
                                  3. Right-click the display window and select New > Ethernet Gateway Site.
                                  4. Fill in these fields:
                                  • Name
                                  • TCP/IP Address
                                  • TCP/IP Port: The TCP/IP Port identifies which communications port is used to connect to the serial devices. The port you use depends on the type of Ethernet gateway you want to set up (i.e., use 7801 for an EtherGate gateway via COM1 or use port 502 for a Modbus gateway).
                                  1. Click the Devices icon.
                                  2. Right-click the display window and select New > Serial Device on Ethernet Gateway Site.
                                  3. Fill in these fields:
                                  • Group: Type a name for the group or select an existing group from the list.
                                  • Name: Type the name you want to give the device.
                                  • Device Type: Select the type of Micrologic trip unit.
                                  • Unit ID: Type the Modbus address of the IFM, as specified by the IFM's two rotary address switches.
                                  • Site: Select the Ethernet gateway site you previously set up.
                                   
                                  NOTE: The Micrologic IFE/IFM devices are natively supported in PME 8.x. However, a device driver is required for PME 7.2.2.
                                  Micrologic IFE/IFM driver for PME 7.2.2 can be found here.

                                  Adding the EM3555 and EM3560 as Serial Device on Ethernet Gateway
                                  1. Open Management Console
                                  2. Click the Sites icon.
                                  3. Right-click the display window and select New > Ethernet Gateway Site.
                                  4. Fill in these fields:
                                  • Name
                                  • TCP/IP Address
                                  • TCP/IP Port: The TCP/IP Port identifies which communications port is used to connect to the serial devices. The port you use depends on the type of Ethernet gateway you want to set up (i.e., use 7801 for an EtherGate gateway via COM1 or use port 502 for a Modbus gateway).
                                  1. Click the Devices icon.
                                  2. Right-click the display window and select New > Serial Device on Ethernet Gateway Site.
                                  3. Fill in these fields:
                                  • Group: Type a name for the group or select an existing group from the list.
                                  • Name: Type the name you want to give the device.
                                  • Device Type: Select "EM3500 series".
                                  • Unit ID: Type the Modbus address of the EM3550 or EM3560
                                  • Site: Select the Ethernet gateway site you previously set up.
                                   
                                  NOTE: The EM3500 series is natively support in PME 7.2.2 and PME 8.x. However, a device driver is required for SPM 7.0.1.
                                  EM3500 Series driver for SPM 7.0.1 can be found here.