Acti9 iC60H, 4P, 16A, D Miniature Circuit Breaker

Acti9 iC60H, 4P, 16A, D Miniature Circuit Breaker

Acti9 iC60H, 4P, 16A, D Miniature Circuit Breaker

Item Number: A9F55416

Retail
$479.67
RRP (Inc. GST)

Product Dimensions

Width icon

Width72 mm

Height icon

Height85 mm

Depth icon

Depth78.5 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

Acti 9

Range of product

Acti 9

Product or component type

miniature circuit-breaker

Sustainable offer status

Green Premium product

Physical

[In] rated current

16 A

[Ue] rated operational voltage

440 V AC 50/60 Hz

Control type

toggle

Local signalling

trip indicator

Mounting mode

clip-on

Mounting support

rail

Height

85 mm

Width

72 mm

Depth

78.5 mm

Net weight

0.5 kg

Mechanical durability

20000 cycles

Electrical durability

10000 cycles

Connections - terminals

  • single terminal (top or bottom) 1-25 mm² rigid
  • single terminal (top or bottom) 1-16 mm² flexible
    • Wire stripping length

      14 mm for top or bottom connection

      Standards

    • EN/IEC 60898-1
    • EN/IEC 60947-2
      • IP degree of protection

        IP20 conforming to IEC 60529

        Relative humidity

        95-95 % at 55-55 °C

        Ambient air temperature for operation

        -35-70 °C

        Ambient air temperature for storage

        -40-85 °C

        REACh free of SVHC

        Yes

        EU RoHS Directive

        Compliant

        Toxic heavy metal free

        Yes

        Mercury free

        Yes

        RoHS exemption information

        Yes

        China RoHS Regulation

         Pro-active China RoHS declaration (out of China RoHS legal scope)

        Environmental Disclosure

        ENVPEP1409009EN

        Others

        Product name

        Disbo iC60

        Device short name

        iC60H

        Poles description

        4P

        Number of protected poles

        4

        Network type

        AC

        Trip unit technology

        thermal-magnetic

        Curve code

        D

        Breaking capacity code

        H

        Breaking capacity

      • 10 kA Icu at 100...133 V DC conforming to EN/IEC 60947-2
      • 10000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1
      • 42 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2
      • 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2
      • 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2
      • 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
        • Utilisation category

          category A conforming to EN/IEC 60947-2

          Network frequency

          50/60 Hz

          Magnetic tripping limit

          12 x In +/- 20 %

          [Ics] rated service breaking capacity

        • 21 kA 50 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz
        • 15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz
        • 7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz
        • 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz
        • 7500 A 75 % conforming to EN/IEC 60898-1 - 415 V AC 50/60 Hz
        • 10 kA 100 % conforming to EN/IEC 60947-2 - 100...133 V DC
          • Limitation class

            3 conforming to EN/IEC 60947-2

            [Ui] rated insulation voltage

            500 V AC 50/60 Hz conforming to EN/IEC 60947-2

            [Uimp] rated impulse withstand voltage

            6 kV conforming to EN/IEC 60947-2

            Contact position indicator

            yes

            Connection pitch

            9 mm pitches

            8

            Provision for padlocking

            padlockable

            Tightening torque

            2-2 N.m top or bottom

            Earth-leakage protection

            separate block

            Compatibility code

            iC60

            Pollution degree

            3 conforming to EN/IEC 60947-2

            Tropicalisation

            2 conforming to IEC 60068-1

            Unit Type of Package 1

            PCE

            Number of Units in Package 1

            1

            Package 1 Weight

            447 g

            Package 1 Height

            7.2 cm

            Package 1 width

            7.5 cm

            Package 1 Length

            9 cm

            Unit Type of Package 2

            BB1

            Number of Units in Package 2

            3

            Package 2 Weight

            1.389 kg

            Package 2 Height

            8.5 cm

            Package 2 width

            9.8 cm

            Package 2 Length

            22 cm

            Unit Type of Package 3

            S03

            Number of Units in Package 3

            33

            Package 3 Weight

            15.899 kg

            Package 3 Height

            30 cm

            Package 3 width

            30 cm

            Package 3 Length

            40 cm

            WEEE

            The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
            Show all specifications

            Frequently Asked Questions

            hide show

            Is there an alternative for a 1 module RCD-MCB part number 4RCBE116/30D?

            Yes, however it is larger in size as it requires 4 modules. The replacement part numbers are A9F55116 + A9V02663.

            What is the code for a 10kA 16A 1p C Curve MCB?

             The code is A9F54116

            what is size of the Cable that will fit into the MCB A9F54106 ?

            Cable = 25mm stranded
             

            What is the code for 4 pole 10kA 50A D curve MCB?

            Code = A9f55450  (iC60H) 

            What is the alternative Acti 9 part code for the discontinued Multi 9 24674?

            The alternative Acti 9 conversion is the A9F45316   3 Pole 16A 6kA MCB 

            How to make a 1 Pole 16 Amps 30mA D Curve RCBO?

            Use a 1 Pole 16 Amps D Curve Circuit Breaker Part # A9F55116 and clip it on the Add-on Vigi Block A9V02663

            https://www.schneider-electric.com.au/en/search/A9V02663



             

            What is the part number for a 6A D-Curve single pole breaker?

            The part number for a 6A D-Curve single pole breaker is a A9F55106.
            Some of the key features are:
            • ACTI9 IC60H Series
            • Single phase
            • Rated at 6 Amps
            • D- Curve Minitire circuit breaker
            For further information please visit Clipsal - A9F55106 - ACTI9 IC60H 1P 6A D MINIATURE CIRCUIT BR

             

            What is the part number for a 3 phase 10amp D-Curve RCBO?

            The part number for a 3 phase 10amp D-Curve RCBO is - A9F55310 & A9V02763

            For further information , visit link below:-
            https://www.schneider-electric.com.au/en/search/A9F55310
            https://www.schneider-electric.com.au/en/search/A9V02763

            Is part number A9F44106 DC rated?

            Yes, part is DC rated up to 48 volts.

            What is the part number for an A9D11810 but in "D" curve?

            need to build up with "D" curve circuit breaker A9F55110 and vigi unit A9V02663
            for more details see ....... https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=A9F55110
            and ............... https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=A9V02663
            User-added image    User-added image

            What is the code for 10A 2P D Curve MCB - rated at 10kA ?

            Code = A9F45210   C60 MCB 

            What is the part number for 20A 10kA D curve 3 pole circuit breaker?

            The part number for 20A 10kA D curve 3 pole circuit breaker is A9F55320.
            Show More