Acti 9 iC60N 1P 1A…63A Miniature Circuit Breaker
Acti9 iDPN VigiARC - System Image - Closed - New Zealand
Acti 9 iC60N 1P 1A…63A Miniature Circuit Breaker
Acti9 iDPN VigiARC - System Image - Closed - New Zealand

Acti9 Ic60n, 1P, 20A, C Miniature Circuit Breaker

Catalogue Number: A9F44120
Acti 9 iC60N 1P 1A…63A Miniature Circuit Breaker
Acti9 iDPN VigiARC - System Image - Closed - New Zealand
Acti 9 iC60N 1P 1A…63A Miniature Circuit Breaker
Acti9 iDPN VigiARC - System Image - Closed - New Zealand
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Range
Acti 9
Range of product
Acti 9
Product name
Disbo iC60
Product or component type
miniature circuit-breaker
Device short name
iC60N
Poles description
1P
Number of protected poles
1
[In] rated current
20 A
Network type
AC
Trip unit technology
thermal-magnetic
Curve code
C
Breaking capacity code
N
Breaking capacity
  • 15 kA Icu at 12...48 V DC conforming to EN/IEC 60947-2
  • 6 kA Icu at 72 V DC conforming to EN/IEC 60947-2
  • 6000 A Icn at 240 V AC 50/60 Hz conforming to EN/IEC 60898-1
  • 36 kA Icu at 10...60 V AC 50/60 Hz conforming to EN/IEC 60947-2
  • 20 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2
  • 10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2
    • Utilisation category
      category A conforming to EN/IEC 60947-2
      Network frequency
      50/60 Hz
      [Ue] rated operational voltage
      240 V AC 50/60 Hz
      Magnetic tripping limit
      8 x In +/- 20 %
      [Ics] rated service breaking capacity
    • 27 kA 75 % conforming to EN/IEC 60947-2 - 10...60 V AC 50/60 Hz
    • 15 kA 75 % conforming to EN/IEC 60947-2 - 100...133 V AC 50/60 Hz
    • 7.5 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz
    • 6000 A 100 % conforming to EN/IEC 60898-1 - 240 V AC 50/60 Hz
    • 15 kA 100 % conforming to EN/IEC 60947-2 - 12...48 V DC
    • 6 kA 100 % conforming to EN/IEC 60947-2 - 72 V DC
      • Limitation class
        3 conforming to EN/IEC 60947-2
        [Ui] rated insulation voltage
        500 V AC 50/60 Hz
        [Uimp] rated impulse withstand voltage
        6 kV conforming to EN/IEC 60947-2
        Contact position indicator
        yes
        Control type
        toggle
        Local signalling
        trip indicator
        Mounting mode
        clip-on
        Mounting support
        rail
        Connection pitch
        9 mm pitches
        2
        Height
        85 mm
        Width
        18 mm
        Depth
        78.5 mm
        Net weight
        0.125 kg
        Mechanical durability
        20000 cycles
        Electrical durability
        10000 cycles
        Provision for padlocking
        padlockable
        Connections - terminals
      • single terminal (top or bottom) 1-25 mm² rigid
      • single terminal (top or bottom) 1-16 mm² flexible
        • Wire stripping length
          14 mm for top or bottom connection
          Tightening torque
          2-2 N.m top or bottom
          Earth-leakage protection
          separate block
          Compatibility code
          iC60
          Standards
        • EN/IEC 60947-2
        • EN/IEC 60898-1
          • IP degree of protection
            IP20 conforming to IEC 60529
            Pollution degree
            3 conforming to EN/IEC 60947-2
            Tropicalisation
            2 conforming to IEC 60068-1
            Relative humidity
            95-95 % at 55-55 °C
            Ambient air temperature for operation
            -35-70 °C
            Ambient air temperature for storage
            -40-85 °C
            Sustainable offer status
            Green Premium product
            REACh Regulation
            Free of Substances of Very High Concern above the threshold
            REACh free of SVHC
            Yes
            EU RoHS Directive
            Compliant
            Toxic heavy metal free
            Yes
            Mercury free
            Yes
            RoHS exemption information
            Yes
            China RoHS Regulation
             Pro-active China RoHS declaration (out of China RoHS legal scope)
            Environmental Disclosure
            ENVPEP1409009EN
            WEEE
            The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

            Frequently Asked Questions

            hide show

            What is the Acti 9 substitute for the Multi 9 25807?

            The A9F44140 is the Acti 9 substitute.

            Please see the attached datasheet for further information on the A9F44140.

            What is the part number for 2 pole 25amp Acti 9 C/B?

            A9F44225

            Is part number A9F44106 DC rated?

            Yes, part is DC rated up to 48 volts.

            What is a 2pole, 6A, C Curve, 6kA circuit breaker

             Part code 25815 Multi 9 - Acti 9 A9F44206

            What is the part number for a 3 phase 20amp MCB/RCD combo?

            The part number for a 3 phase 20amp MCB/RCD combo is - A9F44320 & A9V02763

            For further information visit links below:-
            https://www.schneider-electric.com.au/en/search/A9F44320
            https://www.schneider-electric.com.au/en/search/A9V02763
            User-added image

            User-added image

            What is the part number for a side mount auxiliary contact block to suit A9F44106 circuit breaker?

            Part number for the side mount auxiliar for the Acti 9 range of circuit breakers is A9A26924.
            See link for more details...
            https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=A9A26924

            User-added image

            Can the A9F44210 be used with 110v AC?

            Yes it can, the only difference between a 100v and 230v is that you will get 36kA breaking capacity as opposed to 20kA (230v).



             

            What is the part number for a 3 pole 40amp RCBO?

            The part number for a 3 pole 40amp RCBO is - A9F44340 & A9V02763
            For further information , visit link below:-
            https://www.schneider-electric.com.au/en/search/A9F44340
            https://www.schneider-electric.com.au/en/search/A9V02763
             

            Do you have a C60H Circuit breaker single phase 10A?

            In the Schneider range we have the Acti 9 IC60H circuit breakers. The part number for a single phase, 10A is a A9F54110.

             

            What is the DC rating of A9F44210?

            Acti9 miniture circuit breakers, can handle upto 60VDC.

            What is the DC rating of A9F44210?

            Acti9 miniture circuit breakers, can handle upto 60VDC.

            What is the new code for 15005?

            The new code is A9S60120

            What is a 1 pole 20 amp "D" curve RCBO?

            Use a 1 pole 20 amp "D" curve breaker A9F55120 and add the vigi unit A9V02663 to make the Combo ...(now 3 poles wide)
            https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=A9F55120
            and vigi
            https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=A9V02663

            User-added image
             User-added image

            What is the part number for a 3 phase 10amp RCBO?

            The part number for a 3 phase 10amp RCBO is - A9F44310 & A9V02763

            For further information , visit links below:-
            https://www.schneider-electric.com.au/en/search/A9F44310
            https://www.schneider-electric.com.au/en/search/A9V02763
            User-added image

            User-added image

            What is the code for a 20A 10mA RCBO

            The code is A9D40620

            Data sheet for A9F54240 ?

            Data sheet attached

            What is the DC rating of the A9F44210?

            The DC rating of the Acti9 miniture circuit breakers is 60VDC.

            Please See attachment:

            What is the code for a 10kA 16A 1p C Curve MCB?

             The code is A9F54116

            What is the code for 10A 2P D Curve MCB - rated at 10kA ?

            Code = A9F45210   C60 MCB 

            what is size of the Cable that will fit into the MCB A9F54106 ?

            Cable = 25mm stranded
             

            What is the part code for a 32amp 3P 6kA C Curve MCB?

            The Code is A9F44332.

            What are the codes for a 20A 10mA 1pole rcbo ?

            4rcbe220/10
            or
            A9D40620

            What is the part number for a 2 pole 6amp C/B for 24VDC with right side padlocking device?

            The part number for a 2 pole 6amp C/B for 24VDC with right side padlocking device is - A9F44206 & A9A26831
            For further information , visit links below:-
            https://www.schneider-electric.com.au/en/search/A9F44206
            https://www.schneider-electric.com.au/en/search/A9A26831

            User-added image
             

            What is the socket to suit the Clipsal 492 492/32 492/32HD

            Socket to suit is 402 series

            402  402/32

            What is the Code for a 2 Pole 32A C curve MCB rated at 6 kA ?

            Code = A9F44232

            What is the part number for 20A 10kA D curve 3 pole circuit breaker?

            The part number for 20A 10kA D curve 3 pole circuit breaker is A9F55320.

            What code is the Acti9 equivalent of the Merlin Gerin 25817?

            The Acti9 A9F44216 is a 2p 16A C curve 6kA MCB.
             

            What is the part number for a 4 pole 32A circuit breaker?

            The part number is A9F54432.

            What items come with the KITWALLBOX7?

            A9Z51240 = Type B single phase RCCD
            A9F54240 = 2 pole, 40A, Curve MCB
            A9A26969 = Under voltage release

            What is the cable entry size of the iSW switch disconnectors?

            40-125A
            For Rigid Cable 50mm
            for flexible cable or with ferrule 35mm
            Wire stripping length 9 mm  
            Tightening torque 3.5 N.m  

            Do you do a 3 pole version of a 4RCBM232/30?

            Unfortunately we do not offer a 3 pole version of a 4RCBM230/30.

            However as an alternative we can offer a A9F54432 (4 Pole 32A Circuit Breaker) and a A9V06763 (Vigi Block).

            For further information please visit www.clipsal.com/Trade

            What is the replacement for 25804 MCB?

            The replacement is A9F44120.

            User-added image
            A9F44120
            Acti9 iC60N 1P 20A C Miniature Circuit breaker

            For further information see:https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=A9F44120

            What is the part number for a 3 phase 63amp MCB/RCD?

            The part number for a 3 phase 63amp MCB/RCD is - A9F44363 & A9V02763

            For further information, visit the link below:-
            https://www.schneider-electric.com.au/en/search/A9F44363
            https://www.schneider-electric.com.au/en/search/A9V02763
            User-added image

            What is the part number for an A9D11810 but in "D" curve?

            need to build up with "D" curve circuit breaker A9F55110 and vigi unit A9V02663
            for more details see ....... https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=A9F55110
            and ............... https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=A9V02663
            User-added image    User-added image

            What is the part number for a 1 pole 25amp D-Curve RCBO?

            The part number for a 1 pole 25amp D-Curve RCBO is - A9F55125 & A9V02663

            For further information , visit link below:-
            https://www.schneider-electric.com.au/en/search/A9F55125
            https://www.schneider-electric.com.au/en/search/A9V02663
            User-added image

            User-added image

            What is the part number for a 2 pole 20amp D-Curve RCBO?

            The part number for a 2 pole 20amp D-Curve RCBO is - A9F55220 & A9V51263

            For further information , visit links below:-
            https://www.schneider-electric.com.au/en/search/A9F55220
            https://www.schneider-electric.com.au/en/search/A9V51263
            User-added image
            User-added image

            How can I make 1 Pole 10 Amps B Curve 30mA RCBO?

            To make 1 Pole 10 Amps B Curve 30mA RCBO, you need the following:
            A9F53110 - 1 Pole 10 Amps B Curve Breaker (https://www.schneider-electric.com.au/en/search/A9F53110)
            +
            A9V02663 - 2 Pole 30mA 63 Amps Add-on Vigi to suit 1 Pole iC60 Breakers (https://www.schneider-electric.com.au/en/search/A9F53110)

            Please note the total width of this combination will be equal to 3 Poles standard RCBO (3 x 18mm)