Acti9 iC60H Earth Leakage Circuit Breaker, 1P + N, C Curve, 16A, 30mA, 110V

Acti9 iC60H Earth Leakage Circuit Breaker, 1P + N, C Curve, 16A, 30mA, 110V

Acti9 iC60H Earth Leakage Circuit Breaker, 1P + N, C Curve, 16A, 30mA, 110V

Item Number: A9D19816

Retail
$674.67
RRP (Inc. GST)

Product Dimensions

Width icon

Width18 mm

Height icon

Height110 mm

Depth icon

Depth77.5 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

Acti 9

Range of product

Acti 9

Product or component type

residual current breaker with overcurrent protection (RCBO)

Sustainable offer status

Green Premium product

Physical

[In] rated current

16 A at 50 °C

[Ue] rated operational voltage

110 V AC 50/60 Hz

Control type

toggle

Local signalling

ON/OFF indication

Mounting mode

clip-on

Mounting support

DIN rail

Height

110 mm

Width

18 mm

Depth

77.5 mm

Net weight

205 g

Mechanical durability

20000 cycles

Electrical durability

5000 cycles

Connections - terminals

  • screw clamp terminal (top) 1-25 mm² rigid without cable end
  • screw clamp terminal (top) 1-16 mm² flexible
  • screw clamp terminal (bottom) 1-16 mm² rigid without cable end
  • screw clamp terminal (bottom) 1-10 mm² flexible
    • Wire stripping length

    • power circuit: 13 mm for bottom connection
    • power circuit: 14 mm for top connection
      • Standards

      • BS EN 61009-1
      • IEC 61009-1
      • IEC 61009-2-2
      • AS/NZS 61009.1
        • IP degree of protection

          IP20

          Relative humidity

          95-95 % at 55-55 °C

          Ambient air temperature for operation

          -15-60 °C

          Ambient air temperature for storage

          -40-85 °C

          EU RoHS Directive

          Compliant

          Mercury free

          Yes

          RoHS exemption information

          Yes

          China RoHS Regulation

          Product out of China RoHS scope. Substance declaration for your information

          Environmental Disclosure

          ENVPEP121008EN

          Circularity Profile

          ENVEOLI121005EN

          Others

          Circuit breaker application

          distribution

          Product name

          Acti 9 iC60 RCBO

          Device short name

          iC60H RCBO

          Poles description

          1P + N

          Earthing system

          TN

          Curve code

          C

          Earth-leakage sensitivity

          30 mA

          Breaking capacity

          10000 A Icn at 110 V AC 50/60 Hz

          Neutral position

          left

          Number of protected poles

          1

          Device location in system

          outgoer

          Network type

          AC

          Network frequency

          50 Hz

          Trip unit technology

          thermal-magnetic

          Breaking capacity code

          H

          Residual current tripping technology

          voltage dependent

          Earth-leakage protection time delay

          instantaneous

          Earth-leakage protection class

          type A

          [Icw] rated short-time withstand current

          Icw: 250 A during 8/20 µs impulse withstand

          [Ics] rated service breaking capacity

          7500 A at 110 V AC 50/60 Hz

          Limitation class

          3

          [Ui] rated insulation voltage

          400 V AC 50/60 Hz

          [Uimp] rated impulse withstand voltage

          4 kV

          Surge current

          250 A

          Suitability for isolation

          yes

          Contact position indicator

          yes

          Comb busbar and distribution block compatibility

          NO

          9 mm pitches

          2

          Provision for padlocking

          padlockable with padlock Ø 4 mm

          Locking options description

          ON/OFF locking facilities

          Tightening torque

        • power circuit: 3.5-3.5 N.m top
        • power circuit: 2-2 N.m bottom
          • Earth-leakage protection

            integrated

            Tropicalisation

            2

            Package 1 Weight

            211 g

            Package 1 Height

            75 mm

            Package 1 width

            95 mm

            Package 1 Length

            18 mm

            WEEE

            The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
            Show all specifications

            Documents & downloads

            hide show
            Filter items
            • All

            • Product Brochures

            • CAD Files and Packs

            • Technical Data Catalogues

            • Installation Instruction

            • Product Environmental

            • End of Life Manual

            • Declaration of Conformity

            Frequently Asked Questions

            hide show

            What is the part number for 2 pole 16amp RCBO 2 modules wide?

            The part name is A9D11216

            Does the A9D61816 RCBO have a neutral tail?

            Yes the A9D61816 and all that range have a neutral tail and also an Earth reference point.

            Does the A9D61816 RCBO have a neutral tail?

            Yes, the A9D61816 and all that range have a neutral tail and also an Earth reference point
            for more information see data sheet https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=a9d61816
            User-added image

            What is the part number for an A9D11810 but in "D" curve?

            need to build up with "D" curve circuit breaker A9F55110 and vigi unit A9V02663
            for more details see ....... https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=A9F55110
            and ............... https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=A9V02663
            User-added image    User-added image

            What is the alternative to the 4RCBE210/30?

            Within the Schneider Electric range, the alternative for the 4RCBE210/30 is A9D11210

            What is the difference between A9D32620 and A9D33620 RCBO Acti 9 devices?

             
             

            A9D33620 = SI (Super Immunised)
            A9D32620 = Type A (AC or pulsating DC)

            Type A RCBO = Tripping is ensured for residual sinusoidal alternating currents and residual pulsating direct currents, whether suddenly applied or slowly rising.
            Type Si RCBO = With all the features of a Type A device, “Si” type Super Immunised earth leakage protection range has been specially developed to be used with loads or in environments causing disturbances. Examples are lightning or switching surges, harmonics generated by increasing number of loads and constant load leakage current from electronic ballasts, speed drives, computers, etc. The Si increases safety and allows improved continuity of supply.
             

            What is the replacement part for a 26896 RCB?

            The replacement part is a A9D61820.
            A9D11220 is best solution
            A9D11820 is an alternative 1 pole wide but no Neutral switching
            A9D61820 is an alternative 1 pole wide but no Neutral switching and only 6kA
             

            Which RCBO can ben used in hospitals?

            The only range of RCBO's that can be used in hospitals are:
            Electronic Models -
            4RCBE206/10 4RCBE206/10S
            4RCBE210/10  4RCBE210/10S
            4RCBE220/10 4RCBE220/10S
            4RCBE225/10 4RCBE225/10S
            4RCBE232/10 4RCBE232/10S
            4RCBE240/10  

            Unfortunately you cannot use Schneider A9D108** range as it doesnt switch the neutral.


            For further information see attached PDF or visit https://www.clipsal.com/Trade/search-results?q=4RCBE%20range&t=documentation