ACTc CT contactor auxiliary
iACTc 230 Vac double control inputs auxiliary
ACTc CT contactor auxiliary
iACTc 230 Vac double control inputs auxiliary

Acti 9 Double Control Input Auxiliary, iACTc, 230...240 V AC

Catalogue Number: A9C18308
ACTc CT contactor auxiliary
iACTc 230 Vac double control inputs auxiliary
ACTc CT contactor auxiliary
iACTc 230 Vac double control inputs auxiliary
Retail
$435.57
RRP (Inc. GST)

Specifications

hide show
Range of product
iCT
Range
Acti 9
Product or component type
double control input auxiliary
Device short name
iACTc
[Uc] control circuit voltage
  • 230...240 V AC 50/60 Hz impulse 250 ms
  • 230...240 V AC 50/60 Hz maintained
    • [Us] rated supply voltage
      220...240 V AC at 50/60 Hz
      Maximum output current
    • 0.2 A holding
    • 2 A inrush
      • Hold-in power consumption in VA
        3-3 VA
        Mounting mode
        fixed, on the left of CT
        Mounting support
        DIN rail
        9 mm pitches
        2
        Height
        81 mm
        Width
        18 mm
        Depth
        60 mm
        Overvoltage category
        III
        [Uimp] rated impulse withstand voltage
        4 kV
        [Ui] rated insulation voltage
        440 V
        Standards
        IEC/EN 61095
        Connections - terminals
      • control circuit: tunnel type terminals 2 cable(s) 2.5-2.5 mm² flexible
      • control circuit: tunnel type terminals 2 cable(s) 1.5-1.5 mm² rigid
      • control circuit: tunnel type terminals 1 cable(s) 1.5-2.5 mm² rigid
      • control circuit: tunnel type terminals 1 cable(s) 1.5-2.5 mm² flexible with ferrule
      • control circuit: yellow clips
        • Wire stripping length
          9 mm
          Tightening torque
          0.8-0.8 N.m
          Range compatibility
          Acti9 iCT
          Market segment
        • small commercial
        • residential
          • Compatibility code
            iACTc
            IP degree of protection
            IP20 conforming to IEC 60529
            Ambient air temperature for operation
            -5-50 °C
            Ambient air temperature for storage
            -40-70 °C
            EU RoHS Directive
            Compliant
            Mercury free
            Yes
            RoHS exemption information
            Yes
            China RoHS Regulation
            Product out of China RoHS scope. Substance declaration for your information
            WEEE
            The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
            Warranty
            18 months

            Frequently Asked Questions

            hide show

            What is the part code for a 3 phase indicator pilot light?

             The part code is A9E18327

            Are the A9N18359 and A9A26924 compatible?

            The ref A9N18359 is C120 MCB (Multi9 design in the white material).

            The ref A9A26924 is iOF auxiliary (Aciti9 design for iC60 MCB).

            I can confirm that the parts A9N18359 and A9A26924 are not compliant with each other

             

            What is the new code for the 18364?

            The new code is now A9N18364

            What is the dimensions of the load shedding device A9C15906 ?

            Height = 77 mm  Width = 145 mm Depth = 60 mm

            How many poles wide is the iC120 3 pole 80amp C/B - A9N18365?

            The A9N18365 is 3 pole wide but is 27mm per pole , thus meaning it will need a 4.5 pole wide enclosure 81mm
            For further information , visit link below:-
            https://www.schneider-electric.com.au/en/search/A9N18365
            User-added image

            Is it okay to terminate aluminium cables to the Acti 9 MCB's?

            Aluminium is more corrosive than copper and it can cause high resistance to the current flow over the period of time, So it is highly recommend to use the 27060 aluminium connection terminal if you are using Aluminium cables. 

            What is the part number for the 80 amp 3 pole and neutral 30mA RCBO, 10kA?

            The RCBO is made up with the 4 pole iC120N circuit breaker, part number A9N18372 plus add the 4 pole Vigi unit A9N18578

            https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=A9N18372 

            and
            https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=A9N18578

            User-added image    User-added image
             

            Are all motors to have a 90 degree phase difference between voltage and current when used with Altistart ATS23?

            Issue:   Are all motors to have a 90 degree phase difference between voltage and current when used with Altistart ATS23?
             
            Product Line:   ATS23
             
            Environment:  All

            Cause:   N/A
             
            Resolution:   Must have a .95 lagging power factor--current must lag voltage.