Quantcast

Cap Number 9 Mounting Screw Cover

White Electric | Cap Number 9 Mounting Screw Cover

Cap Number 9 Mounting Screw Cover

Item Number: 9-WE

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Sustainable offer status

Green Premium product

Range of product

Standard Series

Product brand

Clipsal

Physical

REACh Regulation

Reference contains Substances of Very High Concern above the threshold

EU RoHS Directive

Compliant

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

Product out of China RoHS scope. Substance declaration for your information

Environmental Disclosure

ENVPEP120506EN

Others

Diameter

8 mm cap:

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Weight

0.25 g

Package 1 Height

0.3 cm

Package 1 width

0.6 cm

Package 1 Length

0.6 cm

Unit Type of Package 2

BB1

Number of Units in Package 2

100

Package 2 Weight

2.56 kg

Package 2 Height

4.5 cm

Package 2 width

5.7 cm

Package 2 Length

11.7 cm

Unit Type of Package 3

CAR

Number of Units in Package 3

5000

Package 3 Weight

5.0 kg

Package 3 Height

23.7 cm

Package 3 width

20.3 cm

Package 3 Length

30 cm
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • Product Brochures

  • Technical Data Catalogues

Frequently Asked Questions

hide show

Can Multi-9 C60 breakers be continuously loaded to 100% of their rating?

Issue:
Can Multi-9 C60 breakers be continuously loaded to 100% of their rating?

Product Line:
Multi 9 C60 MCB's

Resolution:
UL 489 Listed Multi 9 C60 circuit breakers may be loaded to no more than 80% if used with continuous loads.
UL 1077 recognized supplementary protectors may be operated at 100% of their rating.
IEC 60947-2 C60 breakers may be operated at 100% of their rating.

Is it possible to defeat or disable ground fault on Masterpact NW with Micrologic 6.0A trip units for primary injection testing?

Issue:  
Is there a way to defeat or disable ground fault on a Masterpact NW breaker for primary injection testing?  

Product line:  
Power circuit breakers

Resolution:  
There are two ways to defeat ground fault on the NW breaker for primary injection testing.  You can use the hand held test kit, S33594, or the full function test kit, S33595. Or you can use the looping method to counter the single phase current during primary injection testing. See the attached data bulletin 0600DB9901, page 35, for the looping method, or FAQ Looping Method for Testing Breakers with Ground Fault Trip Units
 

Do the Micrologic 6.0A, 6.0P, and 6.0H trip units have a ground fault test button? If so, where is it?

Issue:
Does the MICROLOGIC 6.0A / 6.0P / 6.0H trip unit have a ground fault test button and where is it?

Product Line:
Circuit Breakers

Resolution:
The Micrologic 6.0A, 6.0P and 6.0H trip units have a ground fault test button on the front of the trip unit that can be used to satisfy NEC230-95(c). The button is white with a ``T`` in the center of it, and is located between the Ii Instantaneous adjustment dial and the port for the secondary injection test kit cable. See the picture below showing the test button and the instructions below for the testing procedure to meet NEC230-95 (c). The latest requirements may require primary injection testing to verify the operation of the ground fault circuit. Your local inspector will indicate if this is required.

Equipment Ground-Fault Trip Functions Testing
Paragraph 230-95 (c) of the National Electrical Code requires that all equipment ground fault protection systems be tested when first installed. With the circuit breaker closed, test the ground fault trip functions. For instructions on how to close circuit breaker, refer to the circuit breaker installation instructions shipped with the circuit breaker. As of the 2017 NEC230-95(c), the ground fault system needs to primary injection tested. The Test button as described below is no longer accepted for the initial acceptance testing. However, if subsequent testing is desired, the Test button can be used.

Testing ground fault trip with the T test button
1. Make sure the trip unit is powered (it is powered when the trip unit screen shows a display). This can be done by either of the following methods:
  • Apply 24 Vdc to terminals F1 and F2 on the green terminal strip on top of the trip unit (F2 positive). The trip unit will be powered all the time.
  • Connect the trip unit to the Full Funciton Test Kit or Hand Held Test Kit. When the test kit is turned on, the trip unit is powered. 
2. Press the T ground fault test button. Circuit breaker should trip.
3. If circuit breaker does not trip, contact the local field office. 

Trip unit picture showing test button

What is the difference between a shunt trip and shunt close device on a Masterpact breaker?

Issue:  
What is the difference between a shunt trip and shunt close module on a Masterpact NW or NT breaker?  

Product Line:  
Power circuit breakers

Resolution:  
There is no difference in the accessory and they are marked to be used as either. Their function is determined by which position they occupy in the breaker. When used as a shunt trip, the coil trips the breaker when the rated voltage (Vn) is applied. When used as a shunt close, the coil closes the breaker when Vn is applied as long as there is nothing preventing the breaker from closing (an open command, the open button being pressed, and engaged padlock attachment, etc.) See attached instruction bulletin 48049-146-01 for more information.

What can prevent the drive tripping on input phase fault?

Issue:
The drive does not trip when an input phase is removed.

Product Line:
Altivar Drives

Environment:
All models and serial numbers

Cause:
1.  Parameter IPL is set to no
Depending on the device type:
1)  Input phase loss works by detecting the ripple in the DC Bus. If the load is not high enough, it can't detect an input phase fault. 
2)  Input phase loss works with the input phase detection on the rectifier circuit (ATV61/71/600/900/MX eco/MX pro) if the rectifier is thyristor controlled (power approximately >22kW).
       
Resolution:
1. Set Parameter IPL to yes
2. Provide additional motor load.


 

Troubleshooting: Micrologic 5.0P or 6.0P or H trip unit will not allow adjustment of the settings on the screen

Issue:
Micrologic Power or Harmonic trip unit won't let me change the on-screen settings.  What is the problem?

Product Line:
Masterpact, Powerpact

Resolution:
The trip unit settings cannot be adjusted via the menu buttons on the trip unit screen unless the trip unit cover (the cover that goes over th dials) is open.
Show More