c-bus ip66 infrascan learn

Passive Infrared Sensor, 110deg

Catalogue Number: 5750WPL
c-bus ip66 infrascan learn
Retail
$402.48
RRP (Inc. GST)
Colour Grey (GY)
  • Grey 1 PCE

Specifications

hide show
Range of product
  • Australian Series
  • C-Bus
    • Range
      C-Bus
      Product brand
      Clipsal
      Product or component type
      occupancy sensor
      Device application
      lighting
      Sensor type
      PIR
      Product specific application
      staircase monitoring
      [Ue] rated operational voltage
      15...36 V DC
      [In] rated current
      18 mA
      Communication network type
      C-Bus 100
      Number of channels
      1
      Type of setting
      light sensitivity adjustable
      Light intensity adjustment
      1-1 lux user selectable
      Data backed up
      non-volatile memory
      Local signalling
      LEDstatus:
      Resolution
      1 s
      Starting time
      5 s
      Horizontal detection angle
      0-110 °
      Time delay range
      0...1 s (switch-on)
      Duty cycle
      1090 min
      Detection face
    • lateral: 12 m
    • frontal: 18 m
      • Connections - terminals
        2 flying leads
        Material
        plastic
        Device mounting
        surface
        Mounting support
      • wall
      • ceiling
        • Mounting height
          2.4 m
          Fixing center
          84 mm
          Width
          74 mm
          Height
          111 mm
          Depth
          138 mm
          IP degree of protection
          IP66
          Ambient air temperature for operation
          0-45 °C
          Unit Type of Package 1
          PCE
          Number of Units in Package 1
          1
          Package 1 Weight
          340 g
          Package 1 Height
          12.6 cm
          Package 1 width
          17.6 cm
          Package 1 Length
          24.8 cm
          EU RoHS Directive
          Under investigation
          Circularity Profile
          ENVEOLI121002EN

          Documents & downloads

          hide show
          Filter items
          • All

          • Product Brochures

          • Technical Data Catalogues

          • Technical Leaflet

          • End of Life Manual

          • Operating Manuals

          • Corporate Marketing

          Frequently Asked Questions

          hide show

          What is the part code for a CBUS outdoor occupancy sensor

          The part code is 5750WPL

          Is the 750WPR Cbus compatible?

          No however the 5750WPL is the same sensor just cbus compatible

          Video: Program "Presence Detection" on C-Bus outdoor PIR sensor

          Video: Program "Presence Detection" on C-Bus outdoor PIR sensor

          Objective:
          Presence detection sets the sensor to trigger on motion. When motion is detected, the sensor sends a C-Bus command across C-Bus.
          this video will step through Program “Presence Detection”, it will cover those C-Bus sensors, 5751L, 5750WPL and 5753L with the old firmware v1.2.67.
          If having problem of programming Presence Detection please review FAQ “Program Presence Detection”

          Product Line:
          C-Bus Sensors: 5751L, 5750WPL and 5753L with the old firmware v1.2.67

          Environment:
          C-Bus Toolkit 1.15.5

          Resolution:
          • Open C-Bus Toolkit
          • Scan the Network
          • Double click the sensor to open its GUI
          • Select a control group from the “Key 4 Group” dropdown list, Presence Detection uses “Any Motion (AM)” function
          • Define the Expiry Time (5 minutes assigned by default) and click “OK”
          • Click “Apply” or “OK”
          • Save to Database and Physical Unit

          Top level --> Product category --> --> Building Automation and Control --> Building Management --> Building Management Systems --> C-Bus Automation system

          Video: Program "Absence Detection" on C-Bus outdoor PIR sensor

          Video: Program "Absence Detection" on C-Bus outdoor PIR sensor

          Objective:
          Absence detection sets the sensor to detect the absence of motion. If the lighting is on and the sensor detects the absence of motion, a timer is activated. When the timer expires and the sensor element still detects absence, a C-Bus command is sent to control lighting.
          This video will step through Program “Absence Detection”, it will cover those C-Bus sensors, 5751L, 5750WPL and 5753L with the old firmware v1.2.67.
          If having problem of programming Absence Dotation please review FAQ “Program Absence Detection”

          Product Line:
          C-Bus Sensors: 5751L, 5750WPL and 5753L with the old firmware v1.2.67

          Environment:
          C-Bus Toolkit 1.15.5

          Resolution:
          • Open C-Bus Toolkit
          • Scan the Network
          • Double click the sensor to open its GUI
          • Select a control group from the “Key 1 Group” dropdown list
          • Define the Expiry Time (5 minutes assigned by default) and click “OK”
          • Go to Key Functions tab and change the “On Key” on MD column for Short Press to “Idle”
          • A Confirm-21000 message will pop up
          • Click “YES” to accept the non-PIR functions
          • Click “Apply” or “OK”
          • Save to Database and Physical Unit
          Top level --> Product category --> --> Building Automation and Control --> Building Management --> Building Management Systems --> C-Bus Automation system

          My 750WPR Infrascan sensor has stopped switching the light on, but the red LED in the sensor is still flashing. What do I do?

          If the 750WPR Infrascan sensor was installed within the last five years it is covered under warranty. Please contact the Clipsal warranty department using the link to have the unit replaced free of charge.

          Alternatively contact your local electrician.

          For Clipsal warranty please visit https://www.clipsal.com/warranty
           

          How do I know if 750WPR Infrascans I have installed are affected by the batch related component issue?

          If movement is still being detected (shown by the flashing RED LED indicator behind the sensor lens), however the load does not switch on, then the unit is affected. If this is the case please contact the Clipsal warranty department using the link to have the unit replaced free of charge.
          Link: https://www.clipsal.com/warranty
           

          Which outdoor sensors have a sensitivity adjustment

          The  part codes are  100SA360, 750WP and 750WPR

          Can 750WP be connected in parallel to control the same load .

          No. Need to use the 750WPR, three wire device when connecting in parallel
          For more information on the 750 series please visit the Clipsal web site on the link provided . https://www.clipsal.com/Trade/search-results?q=750w

          What is the part number for the load correction device for the 750WP?

          The part number for the load correction device for the 750WP is - 31CAP

           

          Regarding the recent batch related component issue on the 750WPR Infrascan. I have installed a 750WPR Infrascan several months ago and its working fine so far, do i need to go back to replace it?

          No. Units only need to be replaced IF they become defective. If within 5 years from install the unit does however become defective, please contact the Clipsal warranty department using the link below to have the unit replaced free of charge.
          Link: https://www.clipsal.com/warranty
           

          Does the 96VH110/2 have a sensitivity adjustment

          No it does not only the 100SA360, 750WP and 750WPR do

          How do I know if I my stock of the 750WPR-GY Infrascan is possibly affected by the recent batch related component issue?

          Check the manufacturing date code on the bottom of the unit box or on the label under the mounting base. Products manufactured after May 2017 are not affected and are ok to use. If you have stock manufactured prior to this date, we are happy to provide free of charge replacements through our warranty process, by contacting Customer Care on email : CustomerCare.AU@schneider-electric.com or Telephone: 137328
          Show More