c-bus ip66 infrascan learn

Passive Infrared Sensor, 110deg

Catalogue Number: 5750WPL
c-bus ip66 infrascan learn
Colour: Grey
Colour: Per UOM Std.
  • Grey 1 PCE

Specifications

hide show
Range of product
  • Australian Series
  • C-Bus
    • Range
      C-Bus
      Product brand
      Clipsal
      Product or component type
      occupancy sensor
      Device application
      lighting
      Sensor type
      PIR
      Product specific application
      staircase monitoring
      [Ue] rated operational voltage
      15...36 V DC
      [In] rated current
      18 mA
      Communication network type
      C-Bus 100
      Number of channels
      1
      Type of setting
      light sensitivity adjustable
      Light intensity adjustment
      1-1 lux user selectable
      Data backed up
      non-volatile memory
      Local signalling
      LEDstatus:
      Resolution
      1 s
      Starting time
      5 s
      Horizontal detection angle
      0-110 °
      Time delay range
      0...1 s (switch-on)
      Duty cycle
      1090 min
      Detection face
    • lateral: 12 m
    • frontal: 18 m
      • Connections - terminals
        2 flying leads
        Material
        plastic
        Device mounting
        surface
        Mounting support
      • wall
      • ceiling
        • Mounting height
          2.4 m
          Fixing center
          84 mm
          Width
          74 mm
          Height
          111 mm
          Depth
          138 mm
          IP degree of protection
          IP66
          Ambient air temperature for operation
          0-45 °C
          EU RoHS Directive
          Compliant
          Circularity Profile
          ENVEOLI121002EN

          Documents & downloads

          hide show
          Filter items
          • All

          • Product Brochures

          • CAD Files and Packs

          • Technical Data Catalogues

          • Technical Leaflet

          • End of Life Manual

          • Installation Instruction

          • Product Environmental

          • Operating Manuals

          • System User Guide

          • Specifications

          • Application Solutions

          • Certificates (MSDS)

          • Corporate Marketing

          • Software - Released

          Frequently Asked Questions

          hide show

          What is the part code for a CBUS outdoor occupancy sensor

          The part code is 5750WPL

          Is the 750WPR Cbus compatible?

          No however the 5750WPL is the same sensor just cbus compatible

          My 750WPR Infrascan has stopped switching the light on, but the red LED in the sensor is still flashing. What do I do?

          If installed within the last five years it is covered under warranty. Please contact the Clipsal warranty department using the link to have the unit replaced free of charge.
          Link: https://www.clipsal.com/warranty
           

          How do I know if 750WPR Infrascans I have installed are affected by the batch related component issue?

          If movement is still being detected (shown by the flashing RED LED indicator behind the sensor lens), however the load does not switch on, then the unit is affected. If this is the case please contact the Clipsal warranty department using the link to have the unit replaced free of charge.
          Link: https://www.clipsal.com/warranty
           

          Which outdoor sensors have a sensitivity adjustment

          The  part codes are  100SA360, 750WP and 750WPR

          Can 750WP be connected in parallel to control the same load .

          No. Need to use the 750WPR, three wire device when connecting in parallel
          For more information on the 750 series please visit the Clipsal web site on the link provided . https://www.clipsal.com/Trade/search-results?q=750w

          What is the part number for the load correction device for the 750WP?

          The part number for the load correction device for the 750WP is - 31CAP

           

          Regarding the recent batch related component issue on the 750WPR Infrascan. I have installed a 750WPR Infrascan several months ago and its working fine so far, do i need to go back to replace it?

          No. Units only need to be replaced IF they become defective. If within 5 years from install the unit does however become defective, please contact the Clipsal warranty department using the link below to have the unit replaced free of charge.
          Link: https://www.clipsal.com/warranty
           

          Does the 96VH110/2 have a sensitivity adjustment

          No it does not only the 100SA360, 750WP and 750WPR do

          How do I know if I my stock of the 750WPR-GY Infrascan is possibly affected by the recent batch related component issue?

          Check the manufacturing date code on the bottom of the unit box or on the label under the mounting base. Products manufactured after May 2017 are not affected and are ok to use. If you have stock manufactured prior to this date, we are happy to provide free of charge replacements through our warranty process, by contacting Customer Care on email : CustomerCare.AU@schneider-electric.com or Telephone: 137328

          Can 750WPR be used for Resistive Loads?

          The 750WPR can be used for Resistive Loads.

          https://www.clipsal.com/Trade/Products/ProductDetail?CatNo=750WPR

           

          Which motion sensors have ESS approval?

          750WPR is ESS approved.

          What is the sensing range of the 750WPR?

          The sensing range for the 750WPR , at the optimum height of 2.4metres is 18metres



           

          What is the part number for the replacement knuckle for the 750WPR?

          The part number for the replacement knuckle for the 750WPR is - 750-KNUCKLE

          For further information, visit the link below:-
          https://www.clipsal.com/Trade/search-results?q=750-KNUCKLE
          User-added image

          Can it 750WPR be used with LED lights?

          Because it is a three wire device, the relay terminal can completely isolate, allowing for no minimum load. This makes it suitable for LED lighting.

          Can more than one 750WPR be used to control the same load?

          Yes. Three wire devices can be connected in parallel to control the same load.

          Does the 750WPR have the double click override function?

          No, it will need to have an override switch wired into the circuit.
           

          What is the maximum time setting on a Clipsal 750WPR

          The maximum time setting is 20 minutes

          What is the warranty period for 750WP?

          This Clipsal Product is guaranteed against faulty workmanship and materials for a
          period of five (5) years from the date of installation. This warranty is expressly subject to the Clipsal product being installed, wired, tested,
          operated and used in accordance with the manufacturer’s instructions.

          For further information on this product, please visit https://www.clipsal.com/Trade/Products/ProductDetail?CatNo=750WP

          User-added image

          What is the part number for the CBus version of the 750WPR?

          The part number is 5750WPL.
          Please click this link for further information https://www.clipsal.com/Trade/Products/ProductDetail?catno=5750WPL

          User-added image

          What is part number for mounting base to suit 750WPR?

          The part number for mounting base to suit is a 750MBA.
          For more information please refer to the link below:
          https://www.clipsal.com/Trade/Products/ProductDetail?catno=750MBA

          What is mounting base to suit 750WPR?

          The mounting base to suit is a 750MBA.
          For more information please visit the link below:
          https://www.clipsal.com/Trade/Products/ProductDetail?catno=750MBA

          How do i stop my LED Flood light from flashing when connected to my 750WP 2-wire Sensor?

          The LED Light is not working correctly with 750WP 2-Wire Sensor because it is NOT a compatible load.
          If controlling a LED load via a sensor is required, you will need to use a 3-Wire version. The part number for a 3 Wire version is a 750WPR.
          Please see the compatibility chart below:
          Catalogue Number 750WP 750WPR
          Compatible Load Types Incandescent Incandescent
            240V Halogen 240V Halogen
            Iron Core Transformers Fluorescent Loads
            N/A Iron Core Transformers
            N/A Electronic Transformers
            N/A Shaded Pole Induction Motors (Exhaust fans, (5A Max)
            N/A Split Phase Induction Motors (ceiling fans, 5A Max)
            N/A Other Motor Loads (Limit to 5A Max)
          Incompatible Load Types Electronic Transformers N/A
            Fluorescent Loads N/A
            Discharge Lamps N/A
            Motor Loads N/A

          Some of the key features for the 3 wire 750WPR Outdoor sensor are:
          • 10A maximum load current
          • Stand-by power consumption is less than 1W
          • 3 Wire
          • Neutral required
          • 30 seconds warmup time
          • 18 metre radius x 110° rated detection field at maximum sensitivity
          • 5 seconds to 20 minutes timer delay range
          • Cables accommodates 4 terminals, up to 2 x 2.5mm² cable per terminal
          • Relay switching method
          For further information please visit www.clipsal.com/Trade/Products/ProductDetail?catno=750WPR

          Why is LED Light not working correctly with 750WP?

          The LED Light is not working correctly with 750WP 2-Wire Sensor because it is not a compatible load.
          If controlling a LED load via a sensor is required, you will need to use a 3-Wire version. The part number for a 3 Wire version is a 750WPR.
          Please see the compatibility chart below:
          Catalogue Number 750WP 750WPR
          Compatible Load Types Incandescent Incandescent
            240V Halogen 240V Halogen
            Iron Core Transformers Fluorescent Loads
            N/A Iron Core Transformers
            N/A Electronic Transformers
            N/A Shaded Pole Induction Motors (Exhaust fans, (5A Max)
            N/A Split Phase Induction Motors (ceiling fans, 5A Max)
            N/A Other Motor Loads (Limit to 5A Max)
          Incompatible Load Types Electronic Transformers N/A
            Fluorescent Loads N/A
            Discharge Lamps N/A
            Motor Loads N/A

          Some of the key features for the 3 wire 750WPR Outdoor sensor are:
          • 10A maximum load current
          • Stand-by power consumption is less than 1W
          • 3 Wire
          • Neutral required
          • 30 seconds warmup time
          • 18 metre radius x 110° rated detection field at maximum sensitivity
          • 5 seconds to 20 minutes timer delay range
          • Cables accommodates 4 terminals, up to 2 x 2.5mm² cable per terminal
          • Relay switching method
          For further information please visit www.clipsal.com/Trade/Products/ProductDetail?catno=750WPR



           

          Is it possible to use a 750WPR in a freezer?

          No, unfortunately the temperature rating is 0 to +50 degrees.
          Please see link and document below for more information.

          https://www.clipsal.com/Trade/Products/ProductDetail?catno=750WPR

          https://updates.clipsal.com/ClipsalOnline/Files/Brochures/W0000781.pdf

           

          Can you use a 31CAP on the 750WPR 3 wire sensor?

          Yes, the 31CAP can be used on both 2 wire and 3 wires sensors.

          For further information please visit www.clipsal.com/Trade/Products/ProductDetail?catno=31CAP

          What is part no for load capacitor to suit Led load on 750WPR

          Part no for load capacitor is 31LCDA

          for more information on this part please refer to https://www.clipsal.com/Trade/Products/ProductDetail?catno=31LCDA

          User-added image

          Can you install more than 1 750WPR to control the same load?

          Yes, you can.
          For further information, visit the link below:-
          https://www.clipsal.com/Trade/search-results?q=750WPR



           

          Can you wire an over ride into a 2 wire 750WP?

          Yes. In order to get the system to work, you will need to wire in either 2x 30M's or a 30MAM into a wall plate and connect to the sensor.

          For further information on the sensor, please visit https://www.clipsal.com/Trade/Products/ProductDetail?CatNo=750WP

          User-added image

          What is the part number for the hinge section on the 750WP range?

          The part number is 750-KNUCKLE-GY.

          Can you have multiple 750WP 2 wire sensors wired in parallel?

          No, unfortunately you will need the 3 wire version. The part number for a 3 wire sensor is 750WPR.
          Some of the key features are:
           

          • 10A maximum load current
          • Stand-by power consumption is less than 1W
          • 3 Wire
          • Neutral required
          • 30 seconds warmup time
          • 18 metre radius x 110° rated detection field at maximum sensitivity
          • 5 seconds to 20 minutes timer delay range
          • Cables accommodates 4 terminals, up to 2 x 2.5mm² cable per terminal
          • Relay switching method

          For further information please visit www.clipsal.com/Trade/Products/ProductDetail?catno=750WPR

           

          What is the range of a Clipsal 750WPR passive infrared sensor

          The beam scans a 18m radius out from the sensor and around 110 degrees in an arc

          Does the 750WPR have a 2x toggle (soft) manual override?

          No, any override switch is physical and not controlled by the sensor.

          Is the knuckle available as spare part for Infrascans

          Yes the part no is 750-Knuckle and it will suit both 2 wire 750WP  & 3 wire 750WPR

          Is there part number for the seal to suit the sensor 750WPR available?

          Yes,  the seal part number is 750-GASKET.

          What is the part number for a 2 wire version of the 750WPR?

          The part number for a 2 wire version of the 750WPR is a - 750WP.
          Some of the key features are:
          • 5A maximum load current
          • 10mA maximum off-state leakage current
          • Stand-by power consumption is less than 1W
          • 2 Wire
          • 30 seconds warmup time
          • 18 metre radius x 110° rated detection field at maximum sensitivity
          • 5 seconds to 20 minutes timer delay range
          • Cables accommodates 4 terminals, up to 2 x 2.5mm² cable per terminal
          • Triac switching method
          For further information please visit www.clipsal.com/Trade/Products/ProductDetail?catno=750WP

          What is the part number for a 750WPR sensor in C-Bus?

          The part number for a 750WPR sensor in C-Bus is a 5750WPL.
          Some of the key features are:
          • Depending on the installation design, can provide an energy efficient solution
          • Passive Infrared Occupancy Outdoor Sensor
          • A light emitting diode (LED) on the sensor head can be programmed to turn when movement is detected, via the installation software, enabling easy positioning and commissioning of the sensor
          • Time-out variation from 1 second to 18 hours, 12 minutes and 15 seconds, is set via the installation software
          For further information please visit www.clipsal.com/Trade/Products/ProductDetail?catno=5750WPL



           

          Do you do the 750WPR in black?

          No, unfortunately the 750WPR is only available in one colour, that being grey.

          Some of the key features are:
          • 10A maximum load current
          • Stand-by power consumption is less than 1W
          • 3 Wire
          • Neutral required
          • 30 seconds warmup time
          • 18 metre radius x 110° rated detection field at maximum sensitivity
          • 5 seconds to 20 minutes timer delay range
          For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=750WPR

          Can the 750WP sensor supply LED's?

          The 750WP was not tested on LED loads, however a Load correction device may be used in conjunction for LED lighting loads. Load correction device part number = S31LCDA
          Also check what LED driver is being used.

          Can you get the bit that goes between the base and the sensor on the 750WP

          The part number is 750-KNUCKLE-GY
           

          Where should the Load correction devices 31CAP and S31LCDA be used?

          The 31CAP is to be use with the following two wire products
          Infrascan 750WP, 751, 753.
          Timer 31VETR
          Sunset Switch WS226SSR/2, 56SSR/2, 31VSSR/2

          The S31LCDA is suitable for use with Clipsal & Schneider Electric 2-Wire, mains powered Dimmers that use
          Leading Edge, Trailing Edge and Universal Dimming.
          Other Suitable loads: Dimmable CFL/ Dimmable LED with Electronic control

          (Load correction Devices may not correct all problems)
          Installation Instructions can be found on the Clipsal.com Website.
           

          Can the 750WP be used with LED lamps?

          The 750WP is not compatible with electronic transformers, so can not be used for LED lights.

          However, the 750WPR can be used to control LED lights.

          For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=750WP
           

          Can you wire 2 750WPR 3 wire sensors in parallel?

          Yes, the 3 wire 750WPR sensor can be wired in parallel with multiple 3 wire sensors.
          Some of the key features are:
           

          • 10A maximum load current
          • Stand-by power consumption is less than 1W
          • 3 Wire
          • Neutral required
          • 30 seconds warmup time
          • 18 metre radius x 110° rated detection field at maximum sensitivity
          • 5 seconds to 20 minutes timer delay range
          • Cables accommodates 4 terminals, up to 2 x 2.5mm² cable per terminal
          • Relay switching method

          For further information please visit www.clipsal.com/Trade/Products/ProductDetail?catno=750WPR

          Is there a corner mounting bracket for the 750WPR?

          No there is not a corner mounting bracket for the 750WPR.
          However there is a knuckel bracket, part number 750-KNUCKLE.

          For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=750-KNUCKLE

          Infrascan 750WPR is not operating correctly when a manual override on switch is wired in parallel with the LED indicator wired to stay on when the load is on.

          You are getting a backfeed through your switchwire which is causing the relay in the infrascan to stay on. The solution would be to install a diode on your switchwire to stop the backfeed going to your sensor.

          Video: How to setup basic connection to SCADAPack 570/575

          Video:

          How to setup basic connection to SCADAPack 570/575

          Product Line

          SCADAPack 570, SCADAPack 575

          Environment

          Remote Connect

          Description

          This video will provide a brief demonstration of getting basic communications with SCADAPack 570/575 RTU.

          Does the 750WPR has a manual override?

          The 750WPR can be Manually overriden by wiring as per the install instructions with a physical switch. The unit itself does not have an inbuilt system for manual override.



          For further information please visit https://updates.clipsal.com/ClipsalOnline/Files/Brochures/W0000781.pdf

          Can the 750 Series Infrascan be remotely triggered ?

          Yes, you can remotely trigger the sensor using something like a 30MBP.



          For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=750WPR.

          Will a 2-wire Infrascan 750WP Sensor operate with 20W load?

          No, Unfortunately a 20W load will not operate a 2-wire Infrascan 750WP Sensor as it has a minimum load of 40W. You can increse the minimum load by adding multiple lights or a larger light. Alternatively you can install a product called a 31CAP which is a capacitor specifically designed to "increase" the minimum load. 

          The characteristics of a 31CAP capacitor are:
          Values Description
          Amp 0.025A (Ampere)  =  25mA (Milliampere).
          Watts 6W
          Voltage 240V
          Microfarad 0.33μF
          Maximum amount stacked in parallel 3

          For further information please visit www.clipsal.com/Trade/Products/ProductDetail?catno=31CAP

           

          Why can't I purchase Schneider Electric US Lighting Control products any more?

          Issue:
          As of March 1, 2015 all US Lighting Control products (EXCEPT Powerlink and MVP panels) will enter their obsolescence phase and will no longer be purchasable for new orders. Management of the Prosumer Business has made a strategic decision to stop the Lighting Control initiative and concentrate our effort in new businesses with higher growth potential – Connected Home, Building Control in small buildings, and Electric Vehicle solutions.

          Product Line:
          All US Lighting Control product except Powerlink and MVP panels are affected. CBus, Occupancy Sensors, Low Voltage Switches, Relay Panels, Emergency Lighting Control Panels, Schneider Electric branded Current Limiting Panels, and Architectural Dimming Panels.

          Environment:
          US Lighting Control products

          Cause:
          Management of the Prosumer Business has made a strategic decision to stop the Lighting Control initiatives.

          Resolution:
          See cross reference sheet attached for available completive cross references.