Specifications

hide show
Range
MAX4
Product or component type
residual current breaker with overcurrent protection (RCBO)
Product brand
Clipsal
Poles description
2P
Number of modules
2
[In] rated current
40 A
Curve code
C
Earth-leakage sensitivity
30 mA
Earth-leakage protection class
type A
Breaking capacity
6000 A
[Ue] rated operational voltage
240 V AC
[Uimp] rated impulse withstand voltage
4 kV
Size
81 x 36 x 77.5 mm conforming to DIN 43880
Standards
AS/NZS 61009
IP degree of protection
  • IP20
  • IP40
    • Ambient air temperature for operation
      -25-40 °C
      Package 1 Weight
      0.25 kg
      Package 1 Height
      38 mm
      Package 1 width
      86 mm
      Package 1 Length
      100 mm
      Sustainable offer status
      Green Premium product
      EU RoHS Directive
      Compliant
      Mercury free
      Yes
      RoHS exemption information
      Yes
      China RoHS Regulation
      Product out of China RoHS scope. Substance declaration for your information
      Environmental Disclosure
      ENVPEP120401EN

      Documents & downloads

      hide show
      Filter items
      • All

      • Product Brochures

      • Installation Instruction

      • Product Environmental

      • Operating Manuals

      • Certificates (MSDS)

      • Corporate Marketing

      Frequently Asked Questions

      hide show

      What would be the replacement for a 4RCD440A30 ?

      The replacement part would be a 4RC440SI30 which is super immune.

      For more information on this product range please visit the Clipsal website on the link provided
      https://www.clipsal.com/Trade/search-results?q=4rc440si30

      Does 4RCBM220/30 switch both active and neutral?

       4RCBM220/30 will switch both active and neutral.
      For further information, please visit https://www.clipsal.com/Trade/Products/ProductDetail?CatNo=4RCBM220/30

      What is the replacement for part number 4RCBM220G30?

      4RCBM220SI30 is the replacement for part number 4RCBM220G30. 4RCBM220SI30 is RCD/MCB, 2 module, 2 Pole, 20A, 30mA, 10KA, C-Curve SI-type, super immune,  A-type, surge current protected to 3000 A 8/20ms.
      For further information, please refer to the below link:
      https://www.clipsal.com/Trade/Products/ProductDetail?catno=4RCBM220SI30
      User-added image
       

      What is the part number for replacement 40amp RCBO - 4RCBE140/30?

      The part number for replacement 40amp RCBO - 4RCBE140/30 is - A9D11840

      For further information , visit link below:-
      https://www.schneider-electric.com.au/en/search/+A9D11840
       

      Is there a 32A super immune RCBO?

      Yes the part number is a 4RCBM232SI30. this is commonly used with motors, pumps and generators as it is more immune to voltage spikes resulting in less nuisance tripping.
       

      What is the part code for a 40A 2P 10mA RCD

      Use a 4RCBE240/10 RCBO

      Is the RCBM210/30 an RCD only ,or is it a combination RCD/MCB?

      The RCBM210/30 is a combination RCD/MCB.

      For further information , visit link below:-
      https://www.clipsal.com/Trade/search-results?q=RCBM210/30
      User-added image

      What are the features for the 4RC440SI30?

      Some of the key features are:
      • Unique new white finish for a fresh modern look
      • Base module = 18 mm wide, compact standardised and consistent module dimensions
      • Lift-up terminals. Safer ‘no hot spot’ terminations and all cable strands are locked in
      • Cable automatically guided to the correct position: terminals with guard
      • Fast closure
      • The presence of the green strip guarantees physical opening of the contacts and allows operations to be performed on the downstream circuit in complete safety
      • Same housing as AC type MCBs. Uniformity in space requirements and installation
      • Superior, safe and reliable DC breaking per pole
      • Used with marine, telecommunications, solar power, emergency power, battery power
      • Excellent breaking capability for its compact size
      • Super immune type
      • 75 mm modular spacing
      • Operating temperature: -5 to 40 deg C
      • Degree of pollution is 2
      • Rated Impulse withstand voltage is 6 kV
      For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=4RC440SI30
       

       

      What is the part number for residential 40A combo RCD & CB?

      The part number for residential 40A combo RCD & CB is a 4RCBM240/30.
      Some of the key features are:
      • Seperate RCD trip flag for easy fault finding
      • new insulated openings for easy busbar installation
      • No need to cut the busbar providing safe and quick fit off
      • Same base module as the 10ka mcb, uniformity in space requirements and installation
      • Same housing and installation features as the mcbs. Safe, easy and fast installation
      • Top and bottom line and load compatible for ease of installation
      • Labelled terminals. Safe, easy and fast installation
      • Top and bottom clip allowing dismounting with comb busbar in place
      • Busbar compatible through an insulated slot
      • Surge current protected to 250a 8/20μs/li>
      • Operating temperature: -5 to 40 deg C
      • Standard type
      • 1-phase
      • 4 kV Rated impulse withstand voltage
      For further information please visit www.clipsal.com/Trade/Products/ProductDetail?catno=4RCBM240/30






       

      What is the alternative to the 4RCBE210/30?

      Within the Schneider Electric range, the alternative for the 4RCBE210/30 is A9D11210

      What is the replacement for 4EL40/2/30?

      The replacement part name is 4RC240/30

      What is the part number for a 2 pole 16amp 10kA RCBO?

      The part number for a 2 pole 16amp 10kA RCBO is - 4RCBM216/30

      For further information , visit link below:-
      https://www.clipsal.com/Trade/search-results?q=4RCBM216/30

      User-added image
      Show More