Specifications

hide show
Range
Clipsal - Series 4
Product or component type
residual current breaker with overcurrent protection (RCBO)
Product brand
Clipsal
Device application
distribution
Poles description
1P + N
Neutral position
left
Number of modules
1
Number of protected poles
1
[In] rated current
32 A
Network type
AC
Trip unit technology
thermal-magnetic
Curve code
C
Earth-leakage sensitivity
30 mA
Earth-leakage protection class
type A
Breaking capacity
6 kA
[Ue] rated operational voltage
110 V AC
Local signalling
ON/OFF indication
Mounting mode
clip-on
Mounting support
DIN rail
IP degree of protection
  • IP20 conforming to IEC 60529
  • IP40 (modular enclosure) conforming to IEC 60529
    • Sustainable offer status
      Green Premium product
      REACh Regulation
      Reference contains Substances of Very High Concern above the threshold
      EU RoHS Directive
      Compliant
      Mercury free
      Yes
      RoHS exemption information
      Yes
      China RoHS Regulation
      Product out of China RoHS scope. Substance declaration for your information
      Environmental Disclosure
      ENVPEP100702EN_V1
      Circularity Profile
      N/A
      WEEE
      The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

      Documents & downloads

      hide show
      Filter items
      • All

      • Product Brochures

      • CAD Files and Packs

      • Technical Data Catalogues

      • Technical Leaflet

      • Product Environmental

      • Installation Instruction

      • Operating Manuals

      • Specifications

      • Certificates (MSDS)

      • Corporate Marketing

      Frequently Asked Questions

      hide show

      What is the part code for a 56 Series with a 32a 10ma RCBO

      Part codes you need a PDL 56CB4  with a 4RCBE232/10

      Looking for a 10mA 20A RCBO.

       Part code is 4RCBE220/10

      What is the part number for a 20A, 10mA RCB?

       The part number is 4RCBE220/10s

      What is the part code for a 40A 2P 10mA RCD

      Use a 4RCBE240/10 RCBO

      What is the part code for an RCBO 10mAmp 20Amp needed for a school

       The part code is a 4RCBE220/10.

      What is the part number for a single module RCBO 32a 10mA

       
       
       
       
      The part number is 4RCBE232/10S

      What is the part code for a 10A 1phase Socket protected by 10mA RCD

      You can use 56SO310 +56CB4 + 56E3 + 4RCBE210/10

      What is part number for 2pole 10ma 16amp MCB/RCD?

      Part no 4RCBE216/10

      Do 4RCBE220/10S suit Schneider chassis?

      4RCBE216/10S does NOT fit onto a standard Chassis.
      reason is the two small terminal screws for active and neutral do not match  the tee off spacing 

      What is the part number for a 20A RCBO double pole?

      The part number for a 20ARCBO double pole is 4RCBE220/10.

      Do Clipsal have a 20a single module RCBE @ 10ma suited for hospital use ?

       
       
       
       
      Yes we do , In this case it would be the 4RCBE220/10S.
      To be approved for use in hospitals the RCBO must be approved as "Type 1" (ie: 10mA sensitivity, switch both Neutral and Active, and trip in <40ms)
      The below range of Slimline RCBO's are rated as Type 1 and therefore compatible


      For more information on Clipsal Circuit protection please visit the Clipsal web site on the provided link https://www.clipsal.com/Trade/search-results?q=circuit%20protection

      Whats the part number for a 10mA, 20A RCD MCB?

      The part name is 4RCBE220/10S

      Is there a 32A super immune RCBO?

      Yes the part number is a 4RCBM232SI30. this is commonly used with motors, pumps and generators as it is more immune to voltage spikes resulting in less nuisance tripping.
       

      is the 4RCBE210/10S and similar a Type 1 RCBO used for hospital applications ?

      In hospital applications, Type1 RCBO must be used.

      4RCBE210/10S is a type 1 RCBO. However it is different to the one used in medilec panels.

      Is the part 4RCBE220/30S still available?

      Yes

      Do you do a 3 pole version of a 4RCBM232/30?

      Unfortunately we do not offer a 3 pole version of a 4RCBM230/30.

      However as an alternative we can offer a A9F54432 (4 Pole 32A Circuit Breaker) and a A9V06763 (Vigi Block).

      For further information please visit www.clipsal.com/Trade

      what is the KA rating 4rcbm232/30.

      For this 4RCBM series  range the KA rating is above 25a is limited to 6KA and below 25amps is 10ka.

      Is there a 2 Pole, 10A, 10mA, RCBE?

      Yes, the part number for a 2 Pole, 10A, 10mA, RCBE is a 4RCBE210/01.

      What is part number for 20amp 10ma single module RCD/MCB?

      The part number for 20amp 10ma single module RCD/MCB is a 4RCBE220/10S.

      Does 4RCBM220/30 switch both active and neutral?

       4RCBM220/30 will switch both active and neutral.
      For further information, please visit https://www.clipsal.com/Trade/Products/ProductDetail?CatNo=4RCBM220/30

      What are the dimensions for the 4RCBE220/30S?

      The dimensions for the 4RCBE220/30S are - L93mm x D72mm x W18mm

      For further information , visit link below:-
      https://www.clipsal.com/Trade/search-results?q=4RCBE220/30S
       

      What is the replacement for a 4EBE232/10?

      The replacement for a 4EBE232/10 is a 4RCBE232/10.
      Some of the key features are:
      • Unique new white finish for a fresh modern look
      • Base module = 18 mm wide, compact standardised and consistent module dimensions
      • Lift-up terminals. Safer ‘no hot spot’ terminations and all cable strands are locked in
      • Cable automatically guided to the correct position: terminals with guard
      • Fast closure
      • The presence of the green strip guarantees physical opening of the contacts and allows operations to be performed on the downstream circuit in complete safety
      • Same housing as AC type MCBs. Uniformity in space requirements and installation
      • Superior, safe and reliable DC breaking per pole
      • Used with marine, telecommunications, solar power, emergency power, battery power
      • Excellent breaking capability for its compact size
      • 36mm Modular Spacing
      • Surge current protected to 250 A at 8/20 uS
      • Operating temperature: -5 to 40 deg C
      • 2 degree of pollution
      • Rated Impulse withstand Voltage is 4kV
      • 40 ms Trip times
      • Standard type
      • 1 phase
      For further information please visit www.clipsal.com/Trade/Products/ProductDetail?catno=4RCBE232/10

       

      Replacement for the 4RCBE110/10

      This part has been replaced with 4RCBE210/30S