mtg block suit vert corrug irn

Mounting Block Suit Vertical Corrugated Iron

Catalogue Number: 450VC
mtg block suit vert corrug irn
Colour: White Electric
Colour: Per UOM Std.
  • White Electric 1 PCE

Specifications

hide show
Product brand
Clipsal
Product or component type
mounting block
Shape
rectangular
Sustainable offer status
Green Premium product
REACh free of SVHC
Yes
EU RoHS Directive
Pro-active compliance (Product out of EU RoHS legal scope)
Toxic heavy metal free
Yes
Mercury free
Yes
RoHS exemption information
Yes
China RoHS Regulation
 Pro-active China RoHS declaration (out of China RoHS legal scope)
Environmental Disclosure
ENVPEP121018EN
Circularity Profile
N/A

Documents & downloads

hide show
Filter items
  • All

  • Product Brochures

  • CAD Files and Packs

  • Technical Data Catalogues

  • Installation Instruction

  • Product Environmental

  • Specifications

  • Case Studies

  • Certificates (MSDS)

Frequently Asked Questions

hide show

Is there an insulated version of 450VC vertical corrugated iron mounting block?

Unfortunately, we do not have an insulated version of 450VC. Depending on the requirement we have 238 mounting boxes or the black plastic insulating shroud which can be used with 450VC. Customer needs to ensure they are following the wiring regulation. 

For further information, please visit 
https://www.clipsal.com/Trade/Products/ProductDetail?catno=238 
https://www.clipsal.com/Trade/search-results?q=insulating%20shroud


238

Will part 450VC fit part number WSC227/2?

Yes, the 450VC will fit the WSC227/2.

For more information, please refer to the link https://www.clipsal.com/Trade/Products/ProductDetail?catno=450VC


User-added image

What is the part number for a mounting block to suit a corrugated surface?

The 450VC-WE suits corrugated iron.
This is compatible with all standard Bakelite series with 84mm centred mounting holes.

Please go to the website via the following link https://www.clipsal.com/Trade/Products/ProductDetail?catno=450VC and check under the Documentation Tab for more information.




 

Is there a version of the 450VC-WE which is the vertical mounting block suitable for vertical corrugated iron?

No, unfortunately we only have 450VC-WE which is a horizontal mounting block suitable for vertical corrugated iron.

Is there a mounting block to suit corrugated iron?

Yes, the part number is 450VC which is avaliable in White (WE) or Grey (GY).
However, this mounting block suits vertical corrugated iron ONLY.\

For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=450VC


 

 

Why is my Back-UPS ES giving a Constant tone with the Power on LED flashing?

Issue:

Why is my Back-UPS ES giving a Constant tone with the Power on LED flashing?


Product Line:

BACK-UPS ES


Environment:

BE350G, BE450G, BE550G, BE650G1 and BE750G


Cause:

If this is a new installation confirm that the internal battery was connected properly.

Refer to the user manual for instructions on this procedure.

The Back-UPS ES performs an internal self-test every 14 days, the internal self-test checks the integrity of the battery. If the battery fails the self-test, the Power on LED will flash and the unit will emit a constant tone. This is a WARNING that the battery may be near the end of its life, replacement is typically recommended within 2-4 weeks.


Resolution:

Step 1:

Verify that the UPS is not being overloaded:

- The Back-UPS ES 350 can support 350VA or 200Watts on the battery powered outlets.

- The Back-UPS ES 450 can support 450VA or 257Watts on the battery powered outlets.

- The Back-UPS ES 550 can support 550VA or 330Watts on the battery powered outlets.

- The Back-UPS ES 650 can support 650VA or 390Watts on the battery powered outlets.

- The Back-UPS ES 750 can support 750VA or 450Watts on the battery powered outlets.


 

APC recommends plugging only the computer and monitor in the battery powered outlets, other peripherals should be plugged into the ""Surge Only"" outlets on the labeled on the the UPS. Outlet strips or surge protectors should NEVER be plugged into any UPS. Remove any excessive load from the UPS. On the same note if the Back-UPS ES is close to being fully loaded (>80% of the battery outlet’s watt capacity) it is not recommended that the Back-UPS ES be used as a master on/off switch to turn on your equipment. Instead power the Back-UPS ES on, letting it complete its self-test before turning on the connected equipment.



Step 2:

A self test should be performed with the UPS fully charged (charging without interruption or transfer to battery for 5 hours) and normal load attached. To do this, power down all equipment attached to the battery outlets. Then reboot the Back-UPS ES by turning it off then count to 5 and power it back on. If the constant tone clears, then it was a false onbattery condition and the unit has been reset. It now is ready to be used again. Proceed to step 3 if it does not clear.


Step 3: (proceed only if "step 2" does not clear the Replace Battery Condition)

The Back-UPS ES comes with a 3 year warranty which includes the internal battery. If the Back-UPS ES was purchased within 3 years, please contact APC Support and reference the steps performed in this document. Also include the exact part number and serial number found on the bottom of the Back-UPS ES.

 

If the Back-UPS ES is outside of the 3 year warranty, click HERE for upgrade and battery replacement options

Can the A9C20732 switch 400V?

No, it is only rated to switch 250V

Is the ATV12 drive available in 460V?

Issue:
Needs a  ATV12 drive with 460V.

Product line:
ATV12, Altivar 12

Environment:
All

Cause:
Customer wants the ATV12 drive for a 5HP, 460V motor.

Resolution:
The ATV12 model is only available for 208-230V motors.  For 460V ratings, use the ATV312 or the ATV320 which has units available up to 20HP, 460V.

What is the part code for a DOL starter 400v, 4A

 The part code LE1M35N712

What is the part number for a 1 pole 4amp 250VDC MCB?

The part number for a 1 pole 4amp 250VDC MCB is - A9N61504

What is the plate to cover the hole from a 149 flush box

Use PDL 683/683C + 2 x PDL 650VH

What is the Metal Cover Plate option for PDL 650VH ?

Suits PDL 686M# metal cover plates

What is the part number for a 250VAC 10amp foot switch?

The part number for a 250VAC 10amp foot switch is - 360-WE

For further information, visit the link below:-
https://www.clipsal.com/Trade/search-results?q=360
User-added image

Is there a skirting mount double power outlet rated to 15A, 250V?

Unfortunately not, we do not have skirting mount double power outlet rated to 250V 15A .

In 15A , 250V, skirting mount, we have the following options:

16/15 -  Single Power Outlet 250V 15A, Skirting Mount, Plate size 98 x 41mm at centre.
For further information, please visit
https://www.clipsal.com/Trade/Products/ProductDetail?catno=16/15

16/2MF1510 - Double Power Outlet 250V 15A and 10A combination, Skirting Mount, suits ducting (156.5 x 44mm).
For further information, please visit
https://www.clipsal.com/Trade/Products/ProductDetail?catno=16/2MF1510

 

Can I run a 460Vac motor on a 575Vac ATV61 or ATV71 drive?

Issue:
Can I run a 460Vac motor on a 575Vac ATV61/ATV71 drive?

Product Line:
ATV61 ATV71 

Environment;
All

Cause:
Test motor 460Vac Line supply 575Vac

Resolution:
No, not recommend. 
A drive is designed to run on a motor with same voltage rating.

What is the min/max load on PDL 624TM?

Maximum Load: 450W, 1.8A resistive. Minimum Load: 20W, 0.1A resistive
https://www.pdl.co.nz/product-details.aspx?rcat=products&catid=0&id=1924

Are the Acti 9 Contactors rated 400V AC?

Yes, they are. Rated operational voltage is 400v, insulation rating is 500v.
 

What is the part number for a 56 series 3 pin plug , 250VAC , 32amp?

The part number for a 56 series 3 pin plug ,  250VAC ,  32amp is - 56P332
For further informaTION , VISIT LINK BELOW:-
https://www.clipsal.com/Trade/search-results?q=56P332
User-added image

What should parameter bFr be set to if you are using a 50hz 400vac motor?

Issue:
What should parameter bFr be set to if you are using a 50hz 400vac motor?

Product Line:
ALTIVAR ATV61

Environment:
All
 
Cause:
Installation / Setup

Resolution:
Drive settings for bFr, nPr, UnS , nCr and nSP settings,  should match the motor nameplate.
in this case bFr will be set to 50hz and UnS will be set to 400vac

What is the recommended line reactor part number for a 15HP 460VAC drive?

Issue:
What is the recommended line reactor part number for a 15HP 460VAC drive?

Product Line:
All

Environment:
All

Cause:
Input or output line/load reactor part numbers.

Resolution:
RL02503 is open style.
RL02513 is enclosed NEMA type 1.
Both are 5% reactors rated for 15HP 480V 3 phase.
This reactor will fit the ATV31HD11N4, ATV61HD11N4 and ATV71HD11N4 or any 15HP 460VAC drive.

What is the dimension of the fascia of 7500ATP?

The dimension of the fascia of 7500ATP is 450mm x 370mm.
For further information, please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=7500ATP
 

Can you feed 230vac into an 480vac Altviar ATV drive to run a 230vac motor?

Issue:
Can you feed 230vac into an 480vac Altviar ATV drive to run a 230vac motor?

Product Line:
Altivar ATV61, ATV71, ATV312, ATV212 ATV32

Environment:
All

Cause:
They ordered the wrong drive with 480vac they need a 230vac drive can they use the 480vac to run the 230v motor?

Resolution:
No you will need to order the correct drive to match the motor amps, hp and application.

 

What is the part number of a double pole, weatherproof 10A, 250VAC socket with a flap suitable for a caravan?

10DWP is a double pole, IP44, 10A, 250VAC auto-switched socket with a flap suitable for a caravan. It is available in black or white colour.
For further information, please visit
https://www.clipsal.com/Trade/Products/ProductDetail?catno=10DWP
User-added image
 

What replacement coils are available for the LC1F500?

Issue:
What replacement coils are available for the LC1F500?

Product Line:
TeSys F-Line Contactors

Environment:
All Product Lines

Cause:
Can not find it in the Digest

Resolution:

For LX1 standard style coils (most common):

24VAC (40 - 400 hz) = Not Available
48VAC (40 - 400 hz) = LX1FK048
110VAC (40 - 400 hz) = LX1FK110
120AC (40 - 400 hz) = LX1FK110
208VAC (40 - 400 hz) = LX1FK200
220VAC (40 - 400 hz) = LX1FK220
240VAC (40 - 400 hz) = LX1FK240
277VAC (40 - 400 hz) = LX1FK280
380VAC (40 - 400 hz) = LX1FK380
415VAC (40 - 400 hz) = LX1FK415
440VAC (40 - 400 hz) = LX1FK415
480VAC (40 - 400 hz) = LX1FK415
600VAC (40 - 400 hz) = LX1FK600


For LX9 special coils:


24VAC (40 - 400 hz) = LX9FK910
48VAC (40 - 400 hz) = LX9FK917
110VAC (40 - 400 hz) = LX9FK925
120AC (40 - 400 hz) = LX9FK925
208VAC (40 - 400 hz) = LX9FK930
220VAC (40 - 400 hz) = LX9FK931
240VAC (40 - 400 hz) = LX9FK932
277VAC (40 - 400 hz) = LX9FK932
380VAC (40 - 400 hz) = LX9FK936
415VAC (40 - 400 hz) = LX9FK936
440VAC (40 - 400 hz) = LX9FK937
480VAC (40 - 400 hz) = LX9FK937
600VAC (40 - 400 hz) = Not Available







 

What is the replacement part number for MRCD20-30, 2 pole, 20A, 250V, 30mA, IP66 RCD?

The replacement part number for MRCD20-30,  2 pole, 20A, 250V, 30mA, IP66 RCD is 56RC. 56RC is also 2 pole, 20A, 250V, 30mA, IP66 RCD.
For further information, please visit
https://www.clipsal.com/Trade/Products/ProductDetail?catno=56RC
User-added image

Fuse and circuit breaker rating for LXM32

Issue:
What is the fuse or circuit breaker rating for LXM32 drives?

Product Line:
LXM32

Resolution:
For 115VAC and 230VAC drives, the maximum fuse to be connected upstream is 25 Amps, Class CC or J as per UL 248-4, alternatively circuit breakers with B or C characteristic.
For 400VAC and 480VAC drives, the maximum fuse to be connected upstream is 30/32 Amps, Class CC or J as per UL 248-4, alternatively circuit breakers with B or C characteristic.

CM2000 Alarm and Event Setpoint Selection

Product Line:
CM2000 Series Meters

Environment: 
Alarm and Event Setpoint Selection 

Cause:
The CM2000 series meters has onboard alarms and events that can be configured. There are 4 setpoint settings for each alarm/event: Pickup Value, Pickup Delay, Dropout Value, and Dropout Delay.

The Pickup and Dropout values can be chosen as a certain percent above or below the nominal value for that measurement.

Example:  Alarm 16 is an overvoltage alarm. If the desired pickup value is 105% of the nominal voltage and the nominal voltage is 480V, the pickup value would be 504V. If the desired dropout value is 95% of the nominal voltage, the dropout voltage would be 456V.  
 
Resolution:
The attached spreadsheet can be used to help determine the desired pickup and dropout values for voltage related alarms/events based on the nominal voltage and the desired pickup and dropout %. 

*For information on configuring alarms from the front panel check out FA218966

Is there a horizontal version of Iconic 3041/45, single pole 250V, 45A cooking appliance isolator?

3041/45, single pole 250V, 45A cooking appliance isolator can be vertical or horizontal mounted. However the mechanism orientation cannot be changed.
For further information, please visit https://www.clipsal.com/Trade/Products/ProductDetail?CatNo=3041/45

What is the alternate part number for 250V, 3 flat pin 10A Matrix plug MPV310?

56P310 can be used as an alternate part number for 250V, 3 flat pin, 10A Matrix plug MPV310. 56P310 is a straight plug rated at IP66, 250V, 10A, 3 Flat Pins. For further information, please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=56P310
User-added image

A customer's main power supply is 380Vac, and his motor nominal voltage is 440Vac. Could the motor output voltage also reache to 440Vac at nominal spe...

Goals and Symptoms

A customer's main power supply is 380Vac, and his motor nominal voltage is 440Vac. Could the motor output voltage also reache to 440Vac at nominal speed if "Uns" is set to 440? Is there any problem of this setting?

Causes and Fixes

It's not possible for the inverter to provide a output voltage upper to the main supply ( lower possible ). So in your case you can try to supply the motor under 380 V, you will obtain instability but depend to the application.


Legacy KB System (APS) Data: RESL157202 V1.0, Originally authored by on , Last Edited by on
Related ranges: Altivar 58

What is the significance of the 'C' or 'B' suffix on an ATV320 drive part number?

Issue:
What is the significance of the 'C' or 'B' suffix on an ATV320 drive part number?

Product Line:
Altivar 320

Environment:
All

Cause:
N/A

Resolution:
B suffix is a bookshelf version of the ATV320 drive.  This is a slim style version.
C suffix is a compact version of the ATV320 drive.  This is a more cube-shaped drive.   

ETSNZ - Are Acti9 iC60 MCBs suitable for DC applications?

Yes, Acti9 iC60N/H MCBs are suitable for DC applications ranging from 12VDC to 250VDC subject to the number of poles connected in series and the required breaking capacity.
The attached document shows the number of poles that are required to be connected in series in relation to the supply voltage and the breaking capacity that is achieved. 

 

What is the max current rating of an ATS22 relay?

Issue:
What is the max current rating of an ATS22 relay?

Product Line:
Altistart 22, ATS22

Environment:
All

Cause:
N/A

Resolution:
Max switching capability:
5A - 250VAC or 30VDC on resistive load (p.f.=1)
2A - 250VAC or 30VDC on inductive load (p.f=0.4)

What is the NEMA 1 Kit for ATV71 over 350HP @ 575VAC?

Issue:
What is the NEMA 1 Kit for ATV71 over 350HP @ 575VAC?

Product Line:
AV71HC40Y
AV71HC50Y
AV71HC63Y

Environment:
Any.

Cause:
Nema 1 Kit part number.

Resolution:

There is no Nema 1 Kit for these 3 drives.
There is only the IP31 kit.
 

Can I get a 8839 enclosed drive in a 600V ?

Issue:
Can I get an ATV61 8839 enclosed drive in a 600V ?

Product Line:
8839 EFD MFD

Environment:
All

Cause:
Need weather proof enclosure.

Resolution:
No. Enclosed drive products maximum voltage is 480V, not available in 600V.

What is the part number of IP66 rated, 250V, 10A, 3 flat pin auto switched outlet?

The part number of IP66 rated, 250V, 10A, 3 flat pin auto switched outlet is 56SO310A. This auto switched outlet is double pole.
For further information, please refer to the below link:
https://www.clipsal.com/Trade/Products/ProductDetail?catno=56SO310A
User-added image
 

Does Clipsal offer 250V, 15A double pole outlets?

Listed below are the part numbers for 250V, 15A double pole outlets:
15D15
For further information, please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=15D15​

25D15
For further information, please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=25D15

2015D15
For further information, please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=2015D15

2025D15
For further information, please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=2025D15

C2015D15
For further information, please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=C2015D15

C2025D15
For further information, please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=C2025D15
 

Can a 480Vac drive be used to control a 240Vac motor?

Issue:
Can a 480Vac drive be used to control a 240Vac motor?

Product Line:
All drives that range from 400/480Vac

Environment:
All serial numbers for units that range from 400/480Vac

Cause:
Drive voltage range does not match motor nameplate data.

Resolution:
A higher voltage rated drive can be used on a lower voltage rated motor, but it is not recommended because the drive will generate voltage spikes at very high levels which could slowly damage the drive.
If doing so, it is recommended that a sine wave filter be added on the drive output to reduce those voltage spikes.

What are the part numbers of the 32A and 45A cooker switches that are unmarked?

Below are the part numbers of the cooker switches that are unmarked.
2031/45 Single-pole 250V, 45A - 2000 Series
C2031/45 Single-pole 250V, 45A - C2000 Series
2031D32 Double-pole 415V, 32A - 2000 Series
C2031D32 Double-pole 415V, 32A - C2000 Series
2031/45N Single-pole, includes Neon, 250V, 45A - 2000 Series
C2031/45N Single-pole, includes Neon, 250V, 45A - C2000 Series
2031D32N Double-pole, includes Neon, 415V, 32A - 2000 Series
C2031D32N Double-pole, includes Neon, 415V, 32A - C2000 Series
For further information, please visit https://updates.clipsal.com/ClipsalOnline/Files/Brochures/A0000272.pdf

What is the part number and watt rating of the heating element used on ATV660 units rated for 200 HP at 460V.

Issue:
What is the part number and watt rating of the heating element used on ATV660 units rated for 200 HP at 460V.

Product Line:
ATV630/660

Environment:
All

Cause:
N/A

Resolution:
The heater is a 100W, 110-250V, part # NSYCR100WU2C.

What is the replacement for 4SS025, din rail mount, 250V, 10A 3pin twin switched socket outlet?

 4SSO25D is the replacement for 4SS025. 
 4SSO25D is 250V 10A 3 pin twin socket double-pole, 8 modules.
For further information, please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=4SSO25D


 

Can you wire R2 relay on the ATV28 drive to a 115Vac light?

Issue:   Can you wire R2 relay on the ATV28 drive to a 115Vac light?
 
Product Line:   ATV28
 
Environment:  All
 
Cause:   N/A
 
Resolution:   Yes. The R2 relay contacts are rated for 1.5A 250Vac and 30Vdc.


 

What is the Schneider recommended part number for an output filter for a 60 horsepower, 460 volts motor?

Issue:
,What is the Schneider recommended part number for an output filter for a 60 horsepower 460 volts motor?

Product Line:
ALTIVAR 61/71

Environment:
60 HP/ 460 volts output filters

Cause:
1 - Product Selection & Services

Resolution:
KLCUL80A2

How is the IPR (motor power) parameter calculated on an ATV61/71?

Issue:
How is the IPR (motor power) parameter calculated?

Product Line:
Altivar ATV61

Environment:
All

Cause:
IPr parameter

Resolution:
In order to calculate and/or monitor motor power, need to consider the speed of the motor, Power factor and efficiency.
The Power Factor and Efficiency drop at lower speeds.

Here are a couple of examples/calculations:
AH3 at 60hz: 96A x 460Vx sqrt(3) x 0.7(PF &Eff) = 53.54 kW
AH3 at 30hz: 35A x 230V x sqrt(3) x 0.43(PF & Eff) = 6.0 kW

Accuracy is about 10%

To identify the voltage limits or Tolerence for the ZB4-BW0** transformer pilot light bodies? Can the ZB4BW055 operate upto 440V?

Goals and Symptoms

To identify the voltage limits or Tolerence for the ZB4-BW0** transformer pilot light bodies? Can the ZB4BW055 operate upto 440V?

Facts and Changes

ZB4
ZB4BW
Transformer
Voltage Limits

Causes and Fixes

The voltage limit is +/- 10%.
=> Mini = 360V~ - Maxi = 440V~.
 


Legacy KB System (APS) Data: RESL160826 V1.0, Originally authored by LaBe on 09/19/2007, Last Edited by LaBe on 09/19/2007
Related ranges: Harmony style 4

What is the Maximum Surge Withstand on the Analog I/O For a 76xx/75xx?

The Analog Inputs and Outputs are isolated to 750V. There is no grounding inside the meter for the analog I/O's. These circuits are isolated from the internals (CPU, etc) of the meter.
Refer to the datasheet https://www.pwrm.com/PRODUCTS/ION7650.




Last Revised: December 3, 2007
Applies To: ION 7500 / 7600, 7550 / 7650
Public
All content © 1992-2007 Schneider Electric


Legacy KB System (APS) Data: RESL190147 V1.0, Originally authored by KBAdPM on 12/04/2007, Last Edited by KBAdPM on 12/04/2007
Related ranges: ION7550/ION7650, ION7500/ION7600

Is there a 3 position marked "1, 0, 2" 2 pole cam switch 16A available?

Yes, the part number for a 3 position marked "1, 0, 2" 2 pole cam switch 16A is a 7GN12/52/U.
Brief :

 Rotary Cam Switches and Accessories, Rated Thermal Current (Ith) = 12A AC23A rating - 6kW at 415V. Rated Insulation Voltage Ui = 480V. Maximum 16A Fuse (gG/gL) for 3kA short circuit protection, 2 Pole 12A 60° changeover switch with Off marked 1-O-2.

Some of the key features are:

  • Front mounting
  • AC23A Rating
  • Changeover switch with OFF marked 1-O-2
For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=7GN12/52/U​

 

 

 

Where are the DC bus connections on a ATV61 drive?

Issue:
Where are the DC bus connections on a ATV61 drive?

Product Line:
All ATV61/71 drives

Environment:
All

Cause:
N/A

Resolution:
The DC connections are at PA/+ and PC/-.  Please refer to the installation manual for more information.

What is the rated Short-Circuit Making Capacity (Icm) value for Compact NS MCCB?

The rated Short-Circuit Making Capacity (Icm) for Compact NS Moulded Case Circuit Breaker is as per the table attached and is dependent on the Short-Circuit Breaking Capacity (Icu).

(Note: Table is extracted from IEC 60947-2 document)

Example:
 
For NS 100 N, 100A MCCB at 440V, Short-Circuit Breaking Capacity (Icu) = 35 KA then, Icm = 2.1 x Icu = 73.5 KA. 
 
Note:
 
According to the IEC 60947-2, if the Rated Making capacity (Icm) is equal to the value specified in the IEC paragraph 4.3.5.3, it is not imperative to have a marking on the circuit breaker.
This is the reason for not publishing this information concerning the marking on the circuit breaker and the values in catalogue.
 
Icm can be calculated by the instruction as per the table provided in the IEC document.

What is the part number of the socket to suit clock point plug 409/3, 250V, 5A, 50Hz, 3 pin?

The part number of the socket to suit clock point plug 409/3 is 408/3. 408/3 is rated at  250V, 5A, 50Hz, 3 pin.
For further information on 408/3, please visit:
https://www.clipsal.com/Trade/Products/ProductDetail?catno=408/3
User-added image
For further information on 409/3, please visit:
https://www.clipsal.com/Trade/Products/ProductDetail?catno=409/3
User-added image