Quantcast

Clipsal Iconic LED Mechanism, Green

Green | Clipsal Iconic LED Mechanism, Green

Clipsal Iconic LED Mechanism, Green

Item Number: 40N-GR

Datasheet

Product Dimensions

Width icon

Width23 mm

Height icon

Height23 mm

Depth icon

Depth32 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

Pro Series

Product or component type

indicator module

Surface treatment

untreated

Physical

Device presentation

mechanism with central plate

Type of packing

polybag

Device mounting

clip with locking bar

[Ue] rated operational voltage

250 V

Local signalling

LED green for status

Height

23 mm

Width

23 mm

Depth

32 mm

Net weight

0.016 kg

Material

Material

  • PC (polycarbonate): housing
  • PA66: housing

Others

Package 1 Bare Product Quantity

1

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

2.2 cm

Package 1 Width

2.2 cm

Package 1 Length

2.4 cm

Package 1 Weight

16.98 g
Show all specifications

Frequently Asked Questions

hide show

What is the maximum output current of the ATV61HD30N4?

Issue:
Maximum continuous output current rating of the ATV61HD30N4.

Product Line:
ATV61

Environment:
ATV61HD30N4 only

Cause:
Customer unable to find information in current literature.

Resolution:
The maximum continuous output current rating of the ATV61HD30N4 is 66 amps.


 

What is the inrush current of the ATV61 High horse power VFDs?

Issue:
Inrush current of the ATV61 / ATV71 High horse power VFDs.

Product Line:
ATV61HC11N4,  ATV61HC31N4, ATV61HC25N4,  ATV61HC40N4,  ATV61HC63N4
ATV71HD90N4, ATV71HC20N4,  ATV71HC25N4,  ATV71HC31N4,  ATV71HC50N4 

Environment:
All 

Cause:
Application requirement.

Resolution:
Inrush current
Drive power  [kW]             I peak [A] (~2ms)                  I peak [A] (~2ms)
ATV71    ATV61               @ 480V +10%                        @ 400V
90               110                   275                                        208
200             250                   556                                        421
250             315                   764                                        579
310             400                   802                                        608
500             630                  1500                                     1136

What is the size of the DC choke used with an ATV61HC25N4 and ATV61HC40N4?

Issue:
DC choke dimensional size used with an ATV61HC25N4 and ATV61HC40N4.

Product line:
Altivar ATV61

Environment:
Part number specific, all serial numbers

Cause:
None

Resolution:
The DC choke used with these models is designated DC-CHOKE 3. 
There are 2 units per ATV61HC25N4.
There are 3 units per ATV61HC40N4.
See the attached file for dimensional information.

What is the part number of the Main Control board for ATV71HD22N4?

Issue:
ATV71HD22N4:  Need to replace the Main Control board.

Product Line:
ATV71

Environment:
ATV71HO75N4, ATV71HU15N4, ATV71HU22N4, ATV71HU30N4, ATV71HU40N4, ATV71HU55N4, ATV71HU75N4, ATV71HD11N4, ATV71HD15N4, ATV71HD18N4, ATV71HD22N4, ATV71HD30N4, ATV71HD37N4, ATV71HD45N4, ATV71HD55N4, ATV71HD75N4

Cause:
Need the Main Control board part number.

Resolution:
The Main Control board part number for these drive is VX4A71100Y

What is ATV71 fan control board part number and troubleshooting LEDs?

Issue:
ATV71 Fan control board part number and troubleshooting LEDs.

Product Line:
Alitvar ATV71 High HP

Environment:
All

Cause:
There are two troubleshooting LEDs on the fan control board.

Resolution:
See the attached file to see the LED troubleshooting codes.

Please note that the following drives have the fan control board.

Frame size 10 is ATV71HC11N4 and ATV71HD75M3X
Frame size 11 and 12 are ATV71HC13 thru HC16N4
Frame size 13 and 14 are ATV71HC20N4 thru HC40N4
Frame size 15 is ATV71HC50N4

 
Frame size 10,11 and 12
1 Fan control board (VX5A1400)
1 Heat sink fan (VZ3V1212)

Fame size 13
1 Fan control board (VX5A1400)
2 Heat sink fans (VZ3V1212)

Frame size 14
2 Fan control boards (VX5A1400)
3 Heat sink fans (VZ3V1212)

Frame size 15
2 Fan control boards (VX5A1400)
4 Heat sink fans (VZ3V1212)

What are the different residual current device categories?

IEC 60755 describes general requirements for residual current operated protective devices.

Vigi modules (Vigi NG125, see example in the figure)
The add-on Vigi module is the most flexible residual current device (it is installed in combination with a circuit breaker).
Vigi are covered by the IEC 61009 and IEC 62423 series of standards.

Residual Current operated Circuit Breakers without integral overcurrent protection (RCCB) (Acti9 iID, see example in the figure)
The Acti 9 iID RCCB is the main residual current device in the facility and is used as the main incomer. RCCB are covered by the IEC 61008 and IEC 62423 series of standards.

Residual Current operated circuit Breakers with integral Overcurrent protection (RCBO) (Acti 9 iCV40N, see example in the figure)
RCBO = combination of circuit breaker and residual current device function in the same product. This can be obtained by combining the circuit breaker with its Add-on Vigi Module.
RCBO are covered by the IEC 61009 and IEC 62423 series of standards.

Socket RCD (SRCD) (see example in the figure) SRCD are covered by the IEC 62640 series of standards.

❺ Industrial type circuit breakers incorporating the RCD function must comply with Annex B of IEC 60947-2.
Residual current devices with a separate toroid are standardized in Annex M of IEC 60947-2.


Reference document - CA908066E
 