Quantcast

General Accessories Screws, 32mm x M3.5 x 0.8 Pitch, Plated

General Accessories Screws, 32mm x M3.5 x 0.8 Pitch, Plated

General Accessories Screws, 32mm x M3.5 x 0.8 Pitch, Plated

Item Number: 355

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Product brand

Clipsal

Surface treatment

zinc plated

Physical

Length

32 mm

Screwdriver shape

Philips

EU RoHS Directive

Compliant

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

Product out of China RoHS scope. Substance declaration for your information

Environmental Disclosure

ENVPEP060307EN

Others

Thread type

M3.5

Shape of screw head

  • panhead
  • slotted

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Weight

2 g

Package 1 Height

0.5 mm

Package 1 width

0.5 mm

Package 1 Length

34 mm
Show all specifications

Frequently Asked Questions

hide show

Does iEM3000 Series Meter have internal battery?

There are two types of clock behaviours found on iEM3000 meter series.
iEM3110, iEM3210, iEM3150, iEM3250, iEM3310 and iEM3350
These meters lose the clock immediately after the power interruption as there is no super capacitor or battery built-in. When power is interrupted, the date and time are reset and you must enter configuration mode to configure the clock, if you require time information.

iEM3115, iEM3135, iEM3155, iEM3165, iEM3175, iEM3215, iEM3235, iEM3455/iEM3555, iEM3465/iEM3565, iEM3275, iEM3335, iEM3355, iEM3365, iEM3375, iEM3455, iEM3465, iEM3555 and iEM3565
These meters could  keep the clock running for up to 3 days in absence of external power, the meter design uses a built-in super capacitor (not a battery) to power the clock only and keep it running. If power is interrupted for longer than 3 days, the device automatically displays the screen to set Date and Time when power is restored.

Refer to User manual for further information (page 28).
https://www.se.com/ww/en/download/document/DOCA0005EN/

DM2355N Power Meter and Modbus

Issue

I cannot find the Modbus Register List for the METSEDM2355N Power Meter

 

Product Line

METSEDM2355N

 

Environment

Medium Meters

 

 

Resolution

Please find the attached Modbus Register List for the METSEDM2355N Power Meter

What are the repair parts for the HU363SS, series F6? (may be shown as F06)

Issue:
Repair parts

Product Line:
Heavy Duty Safety Switch

Resolution:
The repair parts for the HU363SS, series F6 (F06) are as follows. No other parts are available.
Line Base Assembly - 4056775250 (arc suppressor not included)
-Line Base mounting screw - 4020515101 (3 required)
-Arc Suppressor Assembly - 4056635550
-Arc Suppressor mounting screw - 4020514501 (1 required)
-Lug assembly - 4025101851 (per lug)
-Lug Mounting Screw - 4020514202 (per lug)
-Mechanism Assembly - 4056646950 (NOTE: handle coupling, cover interlock defeat coupling, and lockplate gaskets may also need replacing)
-Handle Coupling - 4056699850
-Cover Interlock Defeat Coupling - 4056699750
-Handle Assembly - 4056894150 (also recommend replacing lockplate gaskets)
-Lockplate - 4056894201 (also recommend replacing lockplate gaskets)
-Lockplate Gasket - 4050322802 (2 required)
-Lockplate mounting screw - 2194900001 (2 required)
-Ground Lug - 4025101851 (2 required)
-Ground Lug Mounting Screw - 4020514801

How to enable Area Of Interest in Geo SCADA Expert?

The following applies to both Geo SCADA Expert / ClearSCADA

Area of Interest is not enabled by default. You can enable Area of Interest feature by ticking the check box in Alarms section of Server Configuration.

Right click on Server Icon > Server Configuration  > System Configuration > Alarms


image.png

Please note you will have to restart the Geo SCADA Expert server for the changes to take effect. 

Is there a replacement for DALI CLILMP14012X3DA2 LED Lights?

Unfortunately there is No direct replacement for this part.

 image.png
Customer will have to use our panel LED i.e CLITPLP3/4/5/6 and will have to source the DALI driver from a different manufacturer.

Discontinued DALI Driver specifications: https://eref.se.com/au/en/myse/product-pdf/CLITPLPDRVDALI
image.png

Which direction the H1 side of MTZ neutral CT (TCE external sensor) to be installed?

Please see below diagram from the MTZ Neutral Current Transformer Instruction Sheet.

image.png

As you can see, H1 is always oriented to the bottom side (of the breaker) and H2 to the top side (of the breaker)
In fact, the CT is always installed in the same way whatever the way the breaker is fed (top or bottom)
.



Please see the below illustrations for better understanding. 
image.png


You can install the neutral CT above or below or same level as the breaker, but H1 side of the neutral CT is always facing the direction where the bottom of the breaker is. Please see below.
image.png



The reason for this is that the internal CTs installed inside the beakers, face their H1 side towards the bottom terminals of the breaker. Since, we cannot change the orientation of the internal phase CTs, we have to match the same orientation in the neutral CT as well. i.e. H1 is always oriented to the bottom side (of the breaker) and H2 to the top side (of the breaker)
image.png
Show More