Quantcast

Compact Interpact Switch Disconnector INS40, 3 Poles, 40A

Compact Interpact Switch Disconnector INS40, 3 Poles, 40A

Compact Interpact Switch Disconnector INS40, 3 Poles, 40A

Item Number: 28900

Retail
N/A
RRP (Inc. GST)

Product Dimensions

Width icon

Width90 mm

Height icon

Height85 mm

Depth icon

Depth62.5 mm

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Sustainable offer status

Green Premium product

Warranty

18 months

Range

ComPact

Range of product

INS40...160

Product or component type

switch disconnector

Physical

Control type

rotary handle

Mounting mode

fixed

Mounting support

  • DIN rail
  • plate
    • Mechanical durability

      20000 cycles

      Electrical durability

    • AC-22A: 1500 cycles 220/240 V AC 50/60 Hz
    • DC-23A: 1500 cycles 250 V DC 2 poles in series
    • AC-22A: 1500 cycles 380/415 V AC 50/60 Hz
    • AC-22A: 1500 cycles 440 V AC 50/60 Hz
    • AC-22A: 1500 cycles 500 V AC 50/60 Hz
    • AC-23A: 1500 cycles 220/240 V AC 50/60 Hz
    • AC-23A: 1500 cycles 380/415 V AC 50/60 Hz
    • AC-23A: 1500 cycles 440 V AC 50/60 Hz
    • AC-23A: 1500 cycles 500 V AC 50/60 Hz
    • DC-22A: 1500 cycles 250 V DC 2 poles in series
      • Height

        85 mm

        Width

        90 mm

        Depth

        62.5 mm

        Net weight

        0.5 kg

        Standards

      • IEC 60947-1
      • IEC 60947-3
        • Product certifications

        • KEMA-KEUR
        • CCC
          • IP degree of protection

            IP40 conforming to IEC 60529

            IK degree of protection

            IK07 conforming to EN 50102

            Ambient air temperature for operation

            -25-70 °C

            Ambient air temperature for storage

            -50-85 °C

            REACh Regulation

            Free of Substances of Very High Concern above the threshold

            REACh free of SVHC

            Yes

            EU RoHS Directive

            Compliant

            Toxic heavy metal free

            Yes

            Mercury free

            Yes

            RoHS exemption information

            Yes

            China RoHS Regulation

            X

            Environmental Disclosure

            ENVPEP1304023

            California proposition 65

            WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

            [Ie] rated operational current

          • AC-22A: 40 A AC 50/60 Hz 220/240 V
          • DC-23A: 40 A DC 125 V 2 poles in series
          • AC-22A: 40 A AC 50/60 Hz 380/415 V
          • AC-22A: 40 A AC 50/60 Hz 440/480 V
          • AC-22A: 40 A AC 50/60 Hz 500 V
          • AC-23A: 32 A AC 50/60 Hz 500 V
          • AC-23A: 40 A AC 50/60 Hz 220/240 V
          • AC-23A: 40 A AC 50/60 Hz 380/415 V
          • AC-23A: 40 A AC 50/60 Hz 440/480 V
          • DC-22A: 40 A DC 125 V 2 poles in series
            • [Ue] rated operational voltage

            • 125 V DC
            • 500 V AC 50/60 Hz
              • Others

                Handle colour

                black

                Upside connection

                front

                Downside connection

                front

                Cable cross section

                1.5-50 mm²

                Maximum power

              • AC-23: 11 kW at 220/240 V AC 50/60 Hz
              • AC-23: 18.5 kW at 500/525 V AC 50/60 Hz
              • AC-23: 20 kW at 380/415 V AC 50/60 Hz
              • AC-23: 22 kW at 440 V AC 50/60 Hz
                • Rated duty

                  uninterrupted

                  Intermittent duty class

                  class 120 - 60 %

                  Enclosure dimensions for Ithe

                  190 mm x 115 mm x 55 mm

                  [Icw] rated short-time withstand current

                • 0.067 kA during 20 s conforming to IEC 60947-3
                • 1.73 kA during 3 s conforming to IEC 60947-3
                • 3 kA during 1 s conforming to IEC 60947-3
                • 5.5 kA during 30 s conforming to IEC 60947-3
                  • Connection pitch

                    18 mm

                    Compatibility code

                    INS40

                    Unit Type of Package 1

                    PCE

                    Number of Units in Package 1

                    1

                    Package 1 Weight

                    601 g

                    Package 1 Height

                    0.2 cm

                    Package 1 width

                    9.8 cm

                    Package 1 Length

                    10 cm

                    Unit Type of Package 2

                    S03

                    Number of Units in Package 2

                    18

                    Package 2 Weight

                    11.442 kg

                    Package 2 Height

                    30 cm

                    Package 2 width

                    30 cm

                    Package 2 Length

                    40 cm

                    Unit Type of Package 3

                    P12

                    Number of Units in Package 3

                    144

                    Package 3 Weight

                    102.872 kg

                    Package 3 Height

                    80 cm

                    Package 3 width

                    80 cm

                    Package 3 Length

                    120 cm

                    WEEE

                    The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

                    Product name

                    Compact INS

                    Device short name

                    Compact INS40

                    Switch-disconnector name

                    Compact INS40

                    Poles description

                    3P

                    Network type

                  • DC
                  • AC
                    • Network frequency

                      50/60 Hz

                      [Ui] rated insulation voltage

                      690 V AC 50/60 Hz

                      [Uimp] rated impulse withstand voltage

                      8 kV

                      [Ith] conventional free air thermal current

                      40 A at 60 °C

                      [Icm] rated short-circuit making capacity

                    • 15 kA switch-disconnector alone 500 V AC at 50/60 Hz
                    • 75 kA with upstream protection circuit breaker 500 V AC at 50/60 Hz
                      • Suitability for isolation

                        yes

                        Contact position indicator

                        yes

                        Visible break

                        no

                        Pollution degree

                        3
                        Show all specifications

                        Frequently Asked Questions

                        hide show

                        What is the heat dissipation for INS/INV 40-2500A ?

                        The heat dissipation for the INS/INV 40-2500A is listed in the attachment below . 
                        Refer to the power dissipated per pole.
                        Power Dissipated.png

                        INS/INV40 to 2500 A Switch Disconnector Catalogue : https://download.schneider-electric.com/files?p_Doc_Ref=28900Catalogue&p_File_Ext=.PDF