Quantcast

Conduit Bend, Large Sweep, 90Deg, PVC, 50mm

Grey | Conduit Bend, Large Sweep, 90Deg, PVC, 50mm

Conduit Bend, Large Sweep, 90Deg, PVC, 50mm

Item Number: 247L50-GY

Retail
$107.88
RRP (Inc. GST)

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Sustainable offer status

Green Premium product

Product brand

Clipsal

Range of product

Series 247L

Physical

Environmental Disclosure

ENVPEP100802EN

Mercury free

Yes

REACh free of SVHC

Yes

REACh Regulation

Free of Substances of Very High Concern above the threshold

China RoHS Regulation

 Pro-active China RoHS declaration (out of China RoHS legal scope)

EU RoHS Directive

Pro-active compliance (Product out of EU RoHS legal scope)

RoHS exemption information

Yes

Toxic heavy metal free

Yes

Length

360 mm

Standards

AS/NZS 2053

Material

Material

PVC (polyvinyl chloride)

Others

Package 1 Weight

0.538 kg

Diameter

50 mm

Operating angle

90 °

Inner radius

320 mm
Show all specifications

Frequently Asked Questions

hide show

Is part number 242/50 suitable for underground?

Yes. Part number 242/50 is suitable for underground.

Is there a 246/50 in orange?

Yes we do but it is manfactured to order.

Parts needed to upgrade a Masterpact NW breaker from a Micrologic 3.0 or 5.0 to the 3.0A 5.0P 6.0P 5.0H or 6.0H trip units

Inquiry:
Which parts are needed to upgrade a Masterpact NW breaker from a standard trip unit to a Micrologic 3.0A 5.0P 6.0P 5.0H or 6.0H?

Product Line:
Masterpact NW

Resolution:
Both fixed and drawout breakers need connector S33101 and the trip unit:
3.0A S141A
5.0A S143A
6.0A S144A
5.0P S163A
6.0P S164A
5.0H S173A
6.0H S174A

A neutral CT is required if the breaker is applied on a 4-wire system and new trip unit is a 6.0A, 6.0P, or 6.0H.
A neutral CT is also required if the breaker is applied on a 4-wire system and the new trip unit is a 5.0P being used for ground-fault alarm.
See attached table for catalog numbers.

Fixed circuit breakers also need the following parts in addition to connector S33101:
External Voltage Sensing S47506 (P and H trip units only, if Voltage sensing is required)
Secondary Disconnects (3) S47075 and (1) S47074
BCM S47405 (if modbus is required)

Drawout circuit breakers also need the following parts in addition to connector S33101:
External Voltage Sensing S48533 (P and H trip units only, if Voltage sensing is required)
Secondary Disconnects (3) S47850 and (1) S47849
BCM S48384 (if modbus is required)
 

Are EasyPact MVS circuit breakers for sale in the USA or Canada?

Issue:
Where can I buy a EasyPact MVS breaker?

Product Line:
EasyPact MVS circuit breakers

Resolution:
There are no plans for a general release of the EasyPact MVS circuit breaker line in the US.