switch keytag key only

Short Key Tag

Catalogue Number: 2034VKT
switch keytag key only
Colour: White Electric
Colour: Per UOM Std.
  • White Electric 1 PCE
Added to cart

Specifications

hide show
Range of product
Standard Series
Product brand
Clipsal
Product or component type
key tag
Depth
7 mm
Length
92 mm
Width
40 mm
Material
plastic
EU RoHS Directive
Compliant
Environmental Disclosure
ENVPEP120506EN
Circularity Profile
N/A

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Product Brochures

  • Technical Data Catalogues

  • Installation Instruction

  • Product Environmental

  • Operating Manuals

  • Specifications

  • Certificates (MSDS)

Frequently Asked Questions

hide show

What is the part number for the key only for the 2036VKT4?

The part number for the key only for the 2036VKT4 is 2036VKT.

Some of the key features are:
  • To suit 2036VKT and 36VKT series switches
For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=2036VKT
 

​Is there an alternative C-Bus Switch for 5034NL-WE?

Yes, one off 2034VH + one off 5031NMML + three off 5031NMS

Do you make a 2031VHA like the 2032VHA?

Unfortunately, we only make a 2 gang version.

What is the white cover plate for a 2031VCS

The part code is 2000-WE surround cover plate

​Is there an alternative C-Bus Switch for SC5034NL-WE?

Yes, one off C2034VH + one off 5031NMML + three off 5031NMS

Does the 2031V66 come in architrave?

No it doesnt

Can the mech from 2031VETF be bought seperately ?

No, the mech is intergrated into the grid, and cannot be purchased seperately.

What is part no for key tag only to suit 2036VKT3N

Part no 2036VKT
for more information on this part please refer to https://www.clipsal.com/Trade/Products/ProductDetail?catno=2036VKT

User-added image
 

Can the 2031VETR switch 24V DC?

No, it is only for 240V~.

For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=2031VETR

Do you do the 2031V66 with double pole switches?

No, the 2031V66 does not have double pole mechanisms.

Some of the key features are:
  • Switches have been re-designed to provide mechanisms that can be re-orientated horizontally or vertically
  • 1 gang weatherproof switch

For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=2031V66

Can the 2031VETR be two wayed?

Yes the 2031VETR can have a remote switch wired to it.

For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=2031VETR

Does the 2031VETR switch an exhaust fan?

Yes the 2031VETR will switch small motor loads. (maximum 2A)

For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=2031VETR


 

Does the 2031VETR have dip switches?

Yes, the 2031VETR does have dip switches.

For more information, please refer to the link:
https://www.clipsal.com/Trade/Products/ProductDetail?catno=2031VETR

Can the grid for the 2031v66 be purchased without mechs?

No, We do not supply or encourage this as the 2031v66 has a specific gasket set up to ensure weatherproof rating and this may be compromised if tampered with therefore we only sell them assembled.

What is the mech that fits in the 2031V66 switch?

Unfortunately we dont do the mech as a spare part it is essentually a 30 mech with a rubber seal between the contacts ant the dolly and we dont do that mech as a spare part.

Can part number 30M35 be used in 2031V66?

No. Unfortunately, part number 30M35 CANNOT be used in 2031V66.

 

Can the 2031VETR and 2031VETR3 operate without a neutral?

The 2031VETR3 will not operate without a neutral however the 2031VETR WILL operate without a neutral as it was designed purely as a 2 wire device I.e. Active & Switched Active.

What are the nine current settings on the Vigirex relay catalog number 56372 (56372TD), or RH99M?

Product Line:
Circuit Breakers

Environment:
Electrical Distribution Equipment

Resolution:
The settings are 30ma, 100ma, 300ma, 500ma, 1A, 3A, 5A, 10A, 30A.

How many LUFN auxiliary blocks may be installed on a U-line starter?

Issue:
What is the quantity of LUFN auxiliary blocks, that  may be installed on a U-line starter?

Product Line:
PTCTR - Contactors

Environment:
Tesys U-line

Resolution:
Just one LUFN** or function module per starter.


 

What is the time delay available on the 31VETF or 2031VETF?

The 31VETF Series is adjustable to allow fans to continue to run from 3 minutes to 10 minutes (approximately) after the lighting is turned off. The delay adjustment is accessible on the
rear of the device.

Is the 2031vetr available in the C2000 series?

It is only available in either the standard series ( 31VETR) or 2000 series ( 2031VETR)

Is mech only available for part number 2031VETR?

No the mech comes only complete in plate.

Are the discrete inputs for a Zelio 2 smart relay sinking or sourcing type?

Issue:
Discrete what the inputs for a Zelio 2 smart relay are sinking or sourcing type?
Product Line:
Zelio Smart Relays
Environment:
Zelio Logic 2 Smart Relays
Cause:
Determine thw typr on inputs on a Zelio Smart Relay.        
Resolution:
The inputs for the Zelio smart relays are three wire PNP compatible. No NPN unit is available
 

What is the difference between a QO and QOB breaker?

Issue:

What is the difference between a QO and QOB breaker?

Product Line:

QO and QOB

Environment:
Electrical Distribution Systems

Resolution:
A QO breaker is plug on mounting, and can be used in QO load centers, old NQO and NQOD panelboards, and current NQ panelboards. A QOB breaker uses a bolt-on connection to the bus, and can be used in old NQOB and NQOD panelboards, and current NQ panelboards. Otherwise the breakers are the same.

A DC shunt trip on a Powerpact M, P, or R frame breaker fails to trip the breaker with rated voltage applied.

Product Line:
Circuit Breakers
PowerPact M, P, and R

Environment:
Electrical Distribution Equipment

Resolution:
Polarity needs to be - on C1 and + on C2. If this does not correct the problem with proper voltage applied, replace the shunt trip.
 

​Is there an alternative C-Bus Switch for SL5034NL-WE?

 No alternative with the same style look, but it can be replaced with a different style look with the same functionality switch.
  1. It can be replaced with Classic C2000 Series Grid Plate and 30 Mech switches, one off C2034VH + one off 5031NMML + three off 5031NMS
  2. It can be replaced with Slimline SC2000 Series Grid Plate and 30 Mech switches, one off SC2034VH + one off 5031NMML + three off 5031NMS

What is the timing range for a 2031VETR-WE?

The timing range for a 2031VETR-WE is 15 seconds to 254 minutes.
Please see following link for complete range
https://www.clipsal.com/Trade/Products/ProductDetail?catno=2031VETR3

What is the minimum load for a 2031VETR?

The minimum load for a 2031VETR is 20mA.

For more information, please refer to the link:
https://updates.clipsal.com/ClipsalOnline/Files/Brochures/W0001508.pdf 

What is an ATV31****378?

Issue:  
What is an What is an ATV31****378?
 
Product Line: 
ATV31
 
Environment:
N/A

 
Cause:   N/A
 
Resolution:   
This is a special drive for Buhler Company. The 378 suffix indicates that logic input LI6 can be used as a 24vdc pulsed speed reference. Would need to obtain a replacement from Buhler Company. May also be identified as S378 suffix.

What do the terms AC1 and AC3 mean?

Issue:
What are the utilization categories AC-1 and AC-3?

Product Line:
Schneider Electric Products

Environment:
Inductive and Resistive Loads

Resolution:
AC-1 - This category applies to all AC loads where the power factor is more than 0.95. These are primarily non-inductive or slightly inductive loads, such as resistive loads. Breaking the arc remains easy with minimal arcing and contact wear. 

AC-3 - This category applies to squirrel cage motors with breaking during normal running of the motor.
On closing, the contactor makes the inrush current, which is about 5 to 7 times the rated full load current of the motor.
On opening, the contactor breaks the rated full load current of the motor.

What is the recommended Fuse or Circuit Breaker (OCPD) size for Altivar 61 drives?

Refer to the attached Quick Start Annex, document S1B86981. 
 

How does 2031VETF run on timer switch operate?

The Clipsal 2031VETF Series is an electronic time delay switch which provides extended exhaust fan operations to ensure proper ventilation in bathrooms and toilets. It uses a single switch to operate both lighting and an exhaust fan. Both loads switch on simultaneously when the switch is operated, but when the lighting is turned off, the exhaust fan continues to run for several minutes.
Time Delay Intervals Available:
The 201VETF Series is adjustable to allow fans to continue to run from 3 minutes to 10 minutes (approximately) after the lighting is turned off. The delay adjustment is accessible on the rear of the device.
Operation:
Turning on the switch will cause both the lights and the fan to operate. The electronic timer starts when the switch is turned off. The lights are controlled directly by the switch, however, the fan will run for its preset timer period when the lights are turned off. Turning the lights on and off again, while the fan is still running, will cause the timer period to restart.
The fan will activate for a timer cycle whenever power is re-applied to the unit. eg. initial installation, power failure/return, fan replacement.
for further information. please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=2031VETF
User-added image

 

is there a push button timer which i can place in a switch plate with other switches

We do not do a timer which is removable, the closest is a 2031VETR3-WE.
This comes on it's own plate which it cannot be removed from.
This timer allows the operator to push the button and will remain on until the time has lapsed.
please see below link for more information.
https://www.clipsal.com/Trade/search-results?q=2031vetr

Is there a timer switch in Saturn Series available?

No, however you can use the timer 2031VETR  as a remote timer ie place it in the ceiling and have cables running to a Saturn Series plate with a bell press. When the bell press is pressed it will trigger the 2031VETR.

Bell press part number is a 60PBBP

The saturn series plate less mechanism is 4061VH.

Is the 2031V66 switch 2 way compatible?

Yes, as it is based on 30 series mech with 4 terminals it is 2 way compatible.

Some of the key features are:
  • 1 gang weatherproof switch
  • Standard size gridplate and surround complete with one 30M switch
  • Vertical mount
  • 116 mm Length x 76 mm Width x 30 mm Depth
  • 84 mm apart Mounting centres

For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=2031V66

What is the part number for an OFF delay timer for a 20amp strip heater?

There is no OFF delay timer that has 20amp rating .
You can use run on timer  , 2031VETR , controlling 20amp contactor with 240VAC coil - LC1D09U7 for 20amp resistive load
For further information , visit link below:-
https://www.clipsal.com/Trade/search-results?q=2031VETR
https://www.schneider-electric.com.au/en/search/LC1D09U7
User-added image

Is the communicating shunt trip and close coil for the Masterpact continuous-duty or momentary?

Issue:
Is the communicating shunt trip and close coil for the Masterpact continuous-duty or momentary?

Product Line:
Circuit breakers

Environment:
Masterpact NW NT, Powerpact P R

Resolution:
Constant voltage must be supplied to terminal C3
Voltage may be applied continuously to terminal C2, but  the plunger will only extend for 0.5 seconds and then retract. 
The coil may be operated via Modbus commands, but operation will also only be momentary.  It is not possible to keep the coil energized with Modbus.

With the non-communicating device the plunger will stay extended as long as voltage is applied to the terminals.
 

Do you need to take into consideration the service factor of the motor when setting the trip range on the Solid State Motorlogic overload relay?

Issue:
Do you need to take into consideration the service factor of the motor when setting the trip range on the Solid State Motorlogic overload relay?

Product Line:
Solid State Overload relay

Environment:
Micrologic Solid State Overload Relays

Cause:
Product features

Resolution:
If the continuous - rated motor has a service factor of 1.0, then you would set the dial to 90% of the motor's full load current.
Otherwise, there is a built in service factor of 1.15 - 1.25. If the continuous - rated motor has a service factor of 1.15 - 1.25,
set the dial to the motor's full load current rating. All other service factor ratings will need to be calculated by others.


 

How can a custom length of support tube be achieved with the XVB Indicating Bank?

Issue:
Needs to know how How can a custom length of support tube be achieved with the XVB Indicating Bank

Product Line: 
Push Buttons and Operator Interface

Environment:
22 mm Push Buttons

Resolution:
Use the conduit adapter part number XVBC00 and the desired length of .5`` (1/2) conduit.

Can circuit breakers be reverse-fed or back-fed? A compiled list included.

Product Line:
Circuit Breakers

Environment:
Electrical Distribution Equipment

Resolution:
Any circuit breaker that does NOT have Line and Load (or + and - on DC breakers) identifying markings may be reverse fed. This includes all Square D industrial thermal-magnetic and electronic trip circuit breakers.  See the compiled list below:

Breakers that can be back fed and exceptions (This is a work in process list, it is probably not inclusive and does not yet include legacy breakers):
  • HOM (Excludes those with suffix GFI, EPD, AFI, CAFI and DF.)
  • QO and QOB (Excludes those with suffix GFI, EPD, EPE, AFI, CAFI and DF.)
  • QOU
  • Multi 9 products (Excludes the products rated 125VDC, and 250-500Vdc. Also excludes ID Residual current switches, GFP, DPN VIGI and Vigi modules.)
  • E frame for NF panel (Excludes those with suffix EPD.)
  • Powerpact H, J and L frame (Excludes those with T or R suffix, which are breakers with replaceable trip units. Also excludes those with Fxx suffix, which are "frame only" sold without terminations or trip unit.)
  • Powerpact Q frame
  • Powerpact M, P and R frame
  • Masterpact NT and NW (Excludes Masterpact DC rated breakers)
  • NOTE: Any Legacy or Powerpact breakers with GFM and ELM module attached cannot be reverse fed.

How many faults can a breaker interrupt?

Issue:  
What number of short circuits or faults are Square D breakers rated to interrupt?

Product line:  
Circuit breakers

Environment: 
UL489 listed circuit breakers

Resolution:  
This is a summary of what breakers do for UL489.  Requirements vary, so please refer to the UL489 for complete details.

At Rated Current (handle rating):  
Frame Size Amperes Full Load Operations No Load Operations
0-100 6,000 4,000
101-225 4,000 4,000
226-600 1,000 5,000
601-800 500 3,000
801-2500 500 2,000
2501-4000 400 1,000

Overload:  
The circuit breaker is operated making and breaking 600% of its continuous current rating, but not less than 150 ampere. 
For circuit breakers through 1600 ampere, the number of 600% operations is 50
For larger circuit breakers through 4000 ampere, the number of operations is 25.

Short Circuit: 
For circuit breakers rated 240 Vac and higher, two 10 kA short circuit tests per pole and one test with all poles connected in series is performed.  For example, a 3-pole circuit breaker receives seven short circuit tests.

High Available Fault Current Tests (twice at interrupting rating):  
After qualifying a set of circuit breakers to the standard tests, a manufacturer can have additional circuit breaker samples tested on higher than standard available fault currents.