clip conduit 40mm

Half Saddle Conduit 40mm Hot Dip Galvanised

Catalogue Number: 180HD40
clip conduit 40mm
Retail
$3.29
RRP (Inc. GST)

Specifications

hide show
Product brand
Clipsal
Diameter
40 mm
Material
steel
Surface treatment
hot-dip galvanized
Length
74 mm
Width
32 mm
Height
41 mm
Package 1 Weight
35.5 g
Package 1 Height
38 mm
Package 1 width
32 mm
Package 1 Length
77 mm
REACh free of SVHC
Yes
EU RoHS Directive
Pro-active compliance (Product out of EU RoHS legal scope)
Toxic heavy metal free
Yes
Mercury free
Yes
RoHS exemption information
Yes
China RoHS Regulation
 Pro-active China RoHS declaration (out of China RoHS legal scope)

Frequently Asked Questions

hide show

Conext SW - Installation/ Wiring issue.

Issue:

Customer is installing the Conext SW and wants to confirm the wiring of the AC and DC cabling. 

Environment:

Conext SW 2524 120/240 Split-phase (865-2524)
 
Conext SW 4024 120/240 Split-phase (865-4024)


Resolution:
 

See the attached wiring diagrams for the Conext SW and Conext SW-NA.
Do not mix AC and DC wiring in the same conduit or panel. Consult the applicable installation code for details.
There are two dual 3/4" /1" trade-size knockouts on the side panel and another two on the bottom panel for AC wiring. Use the same trade size of strain relief as the trade size of the knockout(s) you are using.

 

What's the difference between the SyMax Model 50 programmable controllers 8005CP50 and 8005CP51?

The difference between the two SyMax Model 50 programmable controllers is the power voltage rating.
8005CP50 is a 120/240 VAC Processor Unit.
8005CP51 is a 24 VDC Processor Unit.


Legacy KB System (APS) Data: RESL169642 V1.0, Originally authored by on , Last Edited by on
Related ranges: Sy/Max

XW Won't qualify generator.

Issue:

XW inverter charger will not qualify AC generator. AC IN light blinks
AC input qualification, overloading the generator, unable to sustain battery charging and and running loads (multi-tasking)


Environment:

XW 4024/4548/6048 with AC generator


Resolution:

1) Ensure generator is split phase 120/240, not 120 monophase or 120/208V. Voltage from (L1 to N) and (N to L2) should add up exactly to (L1 to L2) voltage
3) Recommended, size your generator 2 times the rating of the XW system.
2) Ensure no neutral to ground bond in Generator
3) Connect gen output to AC2, not AC1 and open up AC2 parameters in XW advanced settings - ac settings menu
4) Reduce max charge rate in XW
5) If Kohler RES series generator, see  Solution 1179

Cause:

1) XW can only connect to splt-ph 120/240 unless converted to monophase 
2) Potential ground loop
3) AC2 qualification parameter window much wider than AC1
4) Gen being overloaded by combination of house loads and XW charger.

Can a circuit breaker be operated at a voltage less than the voltage marked on the breaker?

Inquiry:
Is it OK to apply a circuit breaker on a voltage system rated lower than the rating of the breaker?

Product Line:
MCB and MCCB circuit breakers

Cause:
Circuit breakers are typically marked only with a few standard voltages, while other voltage systems exist.

Resolution:
Yes. According to 2011 NEC article  240.83(E), a circuit breaker may be used at voltages equal to or less than its voltage rating. 
When applied on a system of lower voltage than marked, he interrupting rating is equal to the next highest marked interrupting rating. 
The only exceptions to application at less than rated voltage are:
1. QO and HOM -GFI, -EPD, -AFI, -CAFI, and DF circuit breakers must be applied on 120/240 Vac systems only (they need over 100 Vac to power the electronic modules)
2. EHB-EPD and EDB-EPD type breakers which must be applied on 480Y/277 systems only

NOTE:  Circuit breakers marked with DC ratings only are not suitable for application on AC systems, and circuit breakers marked with AC ratings only are not suitable for application on DC systems.

How do I hardwire 10kva and 20kva transformers in a 208/120 or 240/120 environment

Issue:
Implementing a hardwire stepdown transformer in a 208v or 240v environment


Product Line:

Smart-UPS / Symmetra

Environment:

APTF10KT01, APTF10KW01, and APTF20KW01, All Serial Numbers

Cause:

Unbalanced UPS outputs require a stepdown transformer to power 120v loads


Resolution:

This document refers to installing  the APTF10KT01, APTF10KW01, and APTF20KW01 transformers in a North American 120/240 or 120/208 environment. For installations in other regions please consult the users manual.

The wiring block outputs are as follows:


For domestic use, make sure that the Terminal Block Jumper is installed between the Ground Terminal and Terminal 8 on the output wiring block, as illustrated on page 8 of the user manual. Please also make sure that the input voltage switch is in the correct position.

The step-down transformer provides 240/120 output as 2 120v hots, a neutral, and a ground. It provides 208v output as a 120v hot, an 88v hot, and a ground. The 120v hot (terminal  7) and the 88v hot (terminal 9) are 180 degrees out of phase. You will measure 208v from terminals 7 to 9. The step-down transformer is not able to provide 2 120v hots that are 120 degrees out of phase as you would see with utility power.



 Note: If your installation requires both 208v and 120v output power you will need 2 separate subpanels: a 240v/120v panel and a dedicated 208v subpanel.

Lost Neutral - effects on loads and UL1449

Issue:

Lost Neutral - effects on loads and UL1449

Product Line:

All Back-UPS, Back-UPS PRO and Personal Surge

Environment:

Lost Neutral in electrical infrastructure.

Cause:

Lifted neutral at utility panel.

Resolution:

In a typical balanced load with all loads using the neutral return and the neutral is severed, the voltage from each Phase appears across each load and is added on itself. This is a typical fault condition. Underwriter's Laboratories realized that this fault condition is common and it is not up to the Surge Protection Industry to prevent these failures but in the event of this common failure, UL addressed this condition by requiring all Surge Protectors to pass a fault of 240 VAC at different current levels to simulate different loads. These currents are: 125 mA rms. 500 mA rms. 2.5 A rms. and 5 A rms. They also require an unlimited current test (1000 A rms. or greater). 240 VAC is used because most household wiring is 120/240 3 wire single phase and a lost neutral produces 240 VAC. The unit during this test has cheesecloth wrapped around it. The unit may not emit flame nor can it char the cheesecloth nor can it create an opening in the housing that exposes live metal parts large enough for a child's finger to be inserted. After the test, the unit may not allow leakage currents of > 0.5 mA from Line to Ground and Neutral to Ground also it must withstand a dielectric voltage of 240 VAC for minute between each protected mode. Our units have passed this stringent test requirement in order to get UL recognition and to insure the safety of our customer's lives and property.
 

Energy Meter shows "Phase Loss" Alarm

Issue
Energy meter shows “Phase Loss” alarm on front display.

Product Line
Energy meter (EMB and EME series).

Environment
Installing/wiring energy meter

Cause
If the voltage of any phase is measured as less than 75% of the voltage on any other phase, the display will show PHASE LOSS and indicate the specific phase(s).

Resolution
If the energy meter is installed with the proper number of phases (see selection below to determine this) then the phase voltages should be verified. If the number of phases installed is not correct, then the phase loss alarm will be indicated in all operating conditions.

It’s very important to know the model number of your Energy meter.  
For example, users see “Phase Loss” error when they use EMB2043 (1 phase, 3 wire) with 1 phase, 2 wire application.

As a result, it’s very important for users to know their application and use appropriate meter that meets their system type.  Please review the tables below for selecting correct meter.

Basic 120/240 Volt 208 Wye

EMB1010 Basic 100A 1 Phase, 2 wire installation 1 CT
EMB1021 Basic 200A 1 Phase, 2 wire installation 1 CT
EMB1032 Basic 300A 1 Phase, 2 wire installation 1 CT
EMB2010 Basic 100A 1 Phase, 3 wire installation 2 CTs
EMB2021 Basic 200A 1 Phase, 3 wire installation 2 CTs
EMB2032 Basic 300A 1 Phase, 3 wire installation 2 CTs
EMB2043 Basic 400A 1 Phase, 3 wire installation 2 CTs
EMB2083 Basic 800A 1 Phase, 3 wire installation 2 CTs
EMB3010 Basic 100A 3 Phase, 4 wire installation 3 CTs
EMB3021 Basic 200A 3 Phase, 4 wire installation 3 CTs
EMB3032 Basic 300A 3 Phase, 4 wire installation 3 CTs
EMB3043 Basic 400A 3 Phase, 4 wire installation 3 CTs
EMB3083 Basic 800A 3 Phase, 4 wire installation 3 CTs
EMB3084 Basic 800A 3 Phase, 4 wire installation 3 CTs
EMB3164 Basic 1600A 3 Phase, 4 wire installation 3 CTs


Extended Range 120/480 Volt Wye

EME1010 Basic 100A 1 Phase, 2 wire installation 1 CT
EME1021 Basic 200A 1 Phase, 2 wire installation 1 CT
EME1032 Basic 300A 1 Phase, 2 wire installation 1 CT
EME2010 Basic 100A 1 Phase, 3 wire installation 2 CTs
EME2021 Basic 200A 1 Phase, 3 wire installation 2 CTs
EME2032 Basic 300A 1 Phase, 3 wire installation 2 CTs
EME2043 Basic 400A 1 Phase, 3 wire installation 2 CTs
EME2083 Basic 800A 1 Phase, 3 wire installation 2 CTs
EME3010 Basic 100A 3 Phase, 4 wire installation 3 CTs
EME3021 Basic 200A 3 Phase, 4 wire installation 3 CTs
EME3032 Basic 300A 3 Phase, 4 wire installation 3 CTs
EME3043 Basic 400A 3 Phase, 4 wire installation 3 CTs
EME3083 Basic 800A 3 Phase, 4 wire installation 3 CTs
EME3084 Basic 800A 3 Phase, 4 wire installation 3 CTs
EME3164 Basic 1600A 3 Phase, 4 wire installation 3 CTs


NOTE: the meter will operate, however the phase loss alarm will constantly be present if the improper meter is in use.