Quantcast

Clipsal - Mounting Accessories, Wall Boxes Metal, Poured Concrete, 1 Gang

Clipsal - Mounting Accessories, Wall Boxes Metal, Poured Concrete, 1 Gang

Clipsal - Mounting Accessories, Wall Boxes Metal, Poured Concrete, 1 Gang

Item Number: 160

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Product brand

Clipsal

Surface treatment

electro-galvanized

Sustainable offer status

Green Premium product

Physical

Number of gangs

1 gang

Length

97 mm

Width

50 mm

Depth

39 mm

REACh Regulation

Free of Substances of Very High Concern above the threshold

REACh free of SVHC

Yes

EU RoHS Directive

Pro-active compliance (Product out of EU RoHS legal scope)

Toxic heavy metal free

Yes

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

 Pro-active China RoHS declaration (out of China RoHS legal scope)

Environmental Disclosure

ENVPEP110719EN

Material

Material

steel

Others

Package 1 Bare Product Quantity

1

Shape

rectangular

Cable entry number

9

Location of connection

rear

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Weight

0.143 kg
Show all specifications

Frequently Asked Questions

hide show

What is an USF fault on the ATV312 drives?

Issue
USF showing on the ATV312 drives.

Product Line:
Altivar ATV31 and ATV312

Environment:
All

Cause:
Drive is tripping on USF or undervoltage fault.

Resolution:
USF means undervoltage fault.
Get a digital meter and check your input line voltages on L1 L2 L3
ATV312........M2 drive will trip on USF if the line voltage is 160VAC or less
ATV312........M3 drive will trip on USF if the line voltage is 160VAC or less
ATV312........N4 drive will trip on USF if the line voltage is 300VAC or less
ATV312........S6 drive will trip on USF if the line voltage is 430VAC or less

Can a BMXDAO1605 or BMXDAO1615 be used to switch 24 VDC?

The BMXDAO1605 or BMXDAO1615 can not be used to switch DC.

The operation range is 20~264 VAC.

What does the Rated short time withstand current (Icw) for the breaker mean?

Rated short time withstand current is the value of short time withstand current, assigned to the equipment by the manufacturer, that the equipment can carry without damage, under the test conditions specified in the relevant product standard.
It's generally expressed in kA for 0.5, 1 or 3 seconds. This is an essential characteristic for air circuit breakers. It is not significant for molded-case circuit breakers for which the design targets fast opening and high limiting capacity.
Icw is different from one breaker to another and its value can be found in the product catalogue.
Masterpact MTZ catalogue
Masterpact NT/NW catalogue

Aveva Edge text display becomes unreadable on high resolution monitors

SUMMARY:
This article explains how to correct display issues for Aveva Edge when run on high resolution monitors.
 
SITUATION: 
Tested on: Aveva Edge 2020 R2, Monitor Resolution (3840 x 2160)
 display issue

ACTION:
Please follow the instructions in the screenshot below. Reboot will be required for changes to take effect.
fix
 

What is the DALI Line Alert indicator mean on the DCBM2-1608

dcbm2-1608

The red Alert (ALT) LED is active only when the Line Controller discovers an error from at least one of the DALI devices being polled for status.

Alert Indicator

 
 

What is the guard for a 22mm push-pull mushroom head operator, similar to cat. no. 9001 K56*M?

Issue:
Identify the part number for a guard for a 22mm push-pull mushroom head operator.

Product Line:
Harmony 22mm, XB4, XB5, Push Buttons

Environment:
Push Buttons and Operator Interface

Resolution:
Catalog number ZBZ160* is a metal guard for 40mm mushroom head operator.
ZBZ1600Chrome Plated
ZBZ1602Black
ZBZ1604Red
ZBZ1605Yellow
ZBZ1606Blue
Show More