Standard Series, Automatic Single Socket Outlet Mechanism, 250VAC, 10A, Panel Mount

White Electric | Standard Series, Automatic Single Socket Outlet Mechanism, 250VAC, 10A, Panel Mount

Standard Series, Automatic Single Socket Outlet Mechanism, 250VAC, 10A, Panel Mount

Item Number: 10MP-WE

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

Standard Series

Product or component type

socket-outlet

Product brand

Clipsal

Sustainable offer status

Green Premium product

Physical

Quantity per set

set of 1

Marking

without marking

Local signalling

without light indicator

Device mounting

flush

Fixing mode

by screws

[In] rated current

10 A

[Ue] rated operational voltage

250 V AC

Depth

33 mm

Length

43 mm

Width

42 mm

Fixing center

84 mm

Number of poles

1

Standards

  • AS/NZS 3100
  • AS/NZS 3112
  • AS/NZS 3133:approval number S/1

REACh Regulation

Reference contains Substances of Very High Concern above the threshold

EU RoHS Directive

Compliant

Mercury free

Yes

China RoHS Regulation

Product out of China RoHS scope. Substance declaration for your information

RoHS exemption information

Yes

Environmental Disclosure

ENVPEP120506EN

Others

Package 1 Bare Product Quantity

1

Cover type

complete housing

Socket additional information

with hinged lid

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

3.4 cm

Package 1 Width

4.3 cm

Package 1 Length

4.3 cm

Package 1 Weight

47.1 g

Unit Type of Package 2

BB1

Number of Units in Package 2

5

Package 2 Height

7 cm

Package 2 Width

8.8 cm

Package 2 Length

11 cm

Package 2 Weight

266 g

Unit Type of Package 3

CAR

Number of Units in Package 3

50

Package 3 Height

11.7 cm

Package 3 Width

25 cm

Package 3 Length

31 cm

Package 3 Weight

50 kg
Show all specifications

Frequently Asked Questions

hide show

What are the technologies used in RCD?

Voltage Independent Technology
Residual current devices using Voltage Independent Technology can continue to operate in the event of a complete voltage loss or neutral break.

The residual current device consists of:
  • high magnetic performance core (ex: nanocristalline)
  • a high-sensitivity relay
  • an electronic interface analyzing the signal.
  • The toroid provides information on the leakage current and the power required to trip the device.
  • The electronic circuit and the relay are not connected to the electrical network. Power is provided only by the leakage current.
  • Even if there is an accidental break of the neutral conductor or a voltage drop, the entire electromechanical system will continue to operate, allowing the residual current device to trip.

Voltage Dependent Technology (with and without FE)
A voltage source is required to operate this technology.
For Schneider Electric residual current devices, earth fault protection is provided in the event of a voltage drops down to 50 V.

In the case of VDT technology ("Voltage Dependent Technology"), the toroid only provides information about the leakage current.
The power required for tripping is supplied by the electrical network.


"Voltage Dependent Technology" RCDs supplied via the FE (Functional Earth)
In the event of loss of supply (required to address the fault and trip), there are two categories of behavior:
  • Category 1: the RCD does not open and continuity of service is optimum, because the load is powered on when the voltage is restored, but the RCD is unable to operate if the loss of power supply is the result of a neutral break. The presence of line voltage is a hazard because the RCD is no longer able to perform its protection function in the event of contact with the line potential
 
  • Category 2: the RCD opens if there is loss of power supply (including in the event of neutral break). After the voltage is restored, the RCD must be reclosed to power on the load again.
To improve the level of protection provided by category 1 RCD, in the event of neutral breaking, the product is supplied by redundancy via the FE (line to FE supply instead of line to neutral), allowing it to continue to perform its protection function.
This configuration allows the behavior of VDT RCDs to be compared with that of VIT RCDs.
 
  • conformity with the standards is confirmed by a national conformity mark on the product. The mark is assigned by a third-party organization independent of Schneider Electric. This involves regular sampling at the production site to ensure continued conformity with the standards in question.
According to the standard requirements, all electrical equipment protected by VD with FE RCDs must be earthed to ensure maximum earthing resistance as follows:
  • Ue = 110 V: 50 ohm,
  • Ue = 230/240 V: 100 ohm.

Reference document - CA908066E

What are the different residual current device categories?

IEC 60755 describes general requirements for residual current operated protective devices.

Vigi modules (Vigi NG125, see example in the figure)
The add-on Vigi module is the most flexible residual current device (it is installed in combination with a circuit breaker).
Vigi are covered by the IEC 61009 and IEC 62423 series of standards.

Residual Current operated Circuit Breakers without integral overcurrent protection (RCCB) (Acti9 iID, see example in the figure)
The Acti 9 iID RCCB is the main residual current device in the facility and is used as the main incomer. RCCB are covered by the IEC 61008 and IEC 62423 series of standards.

Residual Current operated circuit Breakers with integral Overcurrent protection (RCBO) (Acti 9 iCV40N, see example in the figure)
RCBO = combination of circuit breaker and residual current device function in the same product. This can be obtained by combining the circuit breaker with its Add-on Vigi Module.
RCBO are covered by the IEC 61009 and IEC 62423 series of standards.

Socket RCD (SRCD) (see example in the figure) SRCD are covered by the IEC 62640 series of standards.

❺ Industrial type circuit breakers incorporating the RCD function must comply with Annex B of IEC 60947-2.
Residual current devices with a separate toroid are standardized in Annex M of IEC 60947-2.


Reference document - CA908066E
 

Can I install a rectangular sensor upstream from a circuit-breaker.?

Yes, a rectangular sensor can be installed upstream or downstream of a circuit breaker.

What Earth leakage protection relay do I require?

Firstly Choose from the two types of relays, (DIN rail mount or Front-panel mount) Using the tables below.
Then make a selection dependent on the voltage required along with the settings desired.


Vigirex Earth Leakage Protection Relay (DIN rail mount)
TYPEPOWER SUPPLYSETTINGSREFERENCE
RH21M12 to 24V AC- 12 to 48V DC30mA-Inst, 300mA-Insta or 300mA-60ms56160
 48V AC30mA-Inst, 300mA-Insta or 300mA-60ms56161
 110 to 130V AC30mA-Inst, 300mA-Insta or 300mA-60ms56162
 220 to 240V AC30mA-Inst, 300mA-Insta or 300mA-60ms56163
 380 to 415V AC30mA-Inst, 300mA-Insta or 300mA-60ms56164
 440 to 525VAC30mA-Inst, 300mA-Insta or 300mA-60ms56165
RH99M12 to 24V AC- 12 to 48V DC30mA to 30A- Inst to 4.5s56170
 48V AC30mA to 30A- Inst to 4.5s56171
 110 to 130V AC30mA to 30A- Inst to 4.5s56172
 220 to 240V AC30mA to 30A- Inst to 4.5s56173
 380 to 415V AC30mA to 30A- Inst to 4.5s56174
 440 to 525V ac30mA to 30A- Inst to 4.5s56175




Vigirex Earth Leakage Protection Relay (Front-Panel mount)
TYPEPOWER SUPPLYSETTINGSREFERENCE
RH21P12 to 24V AC- 12 to 48V DC30mA-Inst, 300mA-Insta or 300mA-60ms56260
 48V AC30mA-Inst, 300mA-Insta or 300mA-60ms56261
 110 to 130V AC30mA-Inst, 300mA-Insta or 300mA-60ms56262
 220 to 240V AC30mA-Inst, 300mA-Insta or 300mA-60ms56263
 380 to 415V AC30mA-Inst, 300mA-Insta or 300mA-60ms56264
 440 to 525VAC30mA-Inst, 300mA-Insta or 300mA-60ms56265
RH99P12 to 24V AC- 12 to 48V DC30mA to 30A- Inst to 4.5s56270
 48V AC30mA to 30A- Inst to 4.5s56271
 110 to 130V AC30mA to 30A- Inst to 4.5s56272
 220 to 240V AC30mA to 30A- Inst to 4.5s56273
 380 to 415V AC30mA to 30A- Inst to 4.5s56274
 440 to 525V ac30mA to 30A- Inst to 4.5s56275
RHU220 to 240V AC15mA to 30A- Inst to 5s28560(1)

Then choose a Toroidal to suit:
Vigirex Sensors (Toroidal and rectangular)
TYPEDESCRIPTIONDIMENSIONRATED OPERATIONAL CURRENTREFERENCE
Closed Toroid,A-typeTA3030mm65A50437(2)
 PA4050mm85A50438(2)
 IA8080mm160A50439
 MA120120mm250A50440
 SA200200mm400A50441
 GA300300mm630A50442
Split Toroid, OA-typePOA46mm85A50485
 GOA110mm250A50486
Rectangular SensorsSmall Rectangular Sensors280 x 115mm1600A56053(3)
 Large Rectangular Sensors470 x 160mm3200A56054(3)

For further information please visit https://www.se.com/au/en/product-range/1014-vigirex/?parent-subcategory-id=4250
Earth-leakage relay RH10M - 1 A - 24 VEarth-leakage relay RH10P - 30 mA - 24 V