Browse all
Browse all

Acti9 iC60 RCBO Residual current breaker with overcurrent protection (RCBO) 3P+Ns, C Curve, 40A, 30mA, A type, 6000A

Home ProductsCircuit ProtectionActi9Residual current breaker with overcurrent protection (RCBO)

Acti9 iC60 RCBO Residual current breaker with overcurrent protection (RCBO) 3P+Ns, C Curve, 40A, 30mA, A type, 6000A

Item Number: A9DC6940

Datasheet

Product Dimensions

Width icon

Width54 mm

Height icon

Height112 mm

Depth icon

Depth77.2 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range Acti9
Product or component type residual current breaker with overcurrent protection (RCBO)

Physical

[in] rated current 40 A at 30 °C
[ue] rated operational voltage 400/415 V
Control type toggle
Local signalling ON/OFF indication
Mounting mode clip-on
Mounting support DIN rail
Height 112 mm
Width 54 mm
Depth 77.2 mm
Net weight 462 g
Mechanical durability 20000 cycles
Electrical durability 5000 cycles
Connections - terminals screw clamp terminal (top) 1-25 mm² rigid without cable end
Wire stripping length power circuit: 11 mm for bottom connection
Standards AS/NZS 61009.1
Ip degree of protection IP20
Relative humidity 95 % at 55 °C
Ambient air temperature for operation -5...60 °C
Ambient air temperature for storage -25...70 °C
Reach free of svhc Yes
Toxic heavy metal free Yes
Mercury free Yes
Rohs exemption information Yes
Environmental disclosure ENVPEP2308033EN
Eu rohs directive Compliant

Others

Package 1 bare product quantity 1
Legacy weee scope In
Outside of Europe
Package 2 bare product quantity 16
Average percentage of bio-based plastic content 0 %
Average percentage of recycled plastic content 0 %
Weee label N/A
Weee applicability Finished product
Warranty duration(in months) bmecat 18
Circuit breaker application distribution
Product name Acti9 iC60 RCBO
Device short name iC60N3 RCBO
Poles description 3P + Ns
Earthing system TN
Curve code C
Earth-leakage sensitivity 30 mA
Breaking capacity 6000 A Icn at 400/415 V
Neutral position left
Number of protected poles 3
Device location in system outgoer
Network frequency 50/60 Hz
Network type AC
Trip unit technology thermal-magnetic
Residual current tripping technology voltage dependent
Earth-leakage protection time delay instantaneous
Earth-leakage protection class type A
[icw] rated short-time withstand current Icw: 250 A during 8/20 µs impulse withstand
[ics] rated service breaking capacity 6000 A
Limitation class 3
[ui] rated insulation voltage 500 V
[uimp] rated impulse withstand voltage 4 kV
Surge current 250 A
Suitability for isolation yes conforming to IEC 61009-1
Comb busbar and distribution block compatibility YES
9 mm pitches 6
Provision for padlocking padlockable with padlock Ø 4 mm
Locking options description ON/OFF locking facilities
Tightening torque power circuit: 2.5...2.5 N.m top
Earth-leakage protection integrated
Test button operating voltage 260...457 V
Operating voltage earthleakage protection 150...457 V
Grid distance 45 mm
Locking options description handle sealable with cable diameter 1.4mm in OFF or ON position
Tropicalisation 2
Unit type of package 1 PCE
Number of units in package 1 1
Package 1 height 12.7 cm
Package 1 width 6.6 cm
Package 1 length 9 cm
Package 1 weight 539 g
Unit type of package 2 S02
Number of units in package 2 16
Package 2 height 15 cm
Package 2 width 30 cm
Package 2 length 40 cm
Package 2 weight 9.376 kg
Green premium status for reporting Green Premium product
Total lifecycle carbon footprint 44 kg CO2 eq.
Carbon footprint of the manufacturing phase [a1 to a3] 5.16357713717693
Carbon footprint of the manufacturing phase [a1 to a3] 5 kg CO2 eq.
Carbon footprint of the distribution phase [a4] 0.0466229642147117
Carbon footprint of the distribution phase [a4] 0 kg CO2 eq.
Carbon footprint of the installation phase [a5] 0.0822505427435387
Carbon footprint of the installation phase [a5] 0.1 kg CO2 eq.
Carbon footprint of the use phase [b2, b3, b4, b6] 37.42
Carbon footprint of the use phase [b2, b3, b4, b6] 37 kg CO2 eq.
Sustainable packaging No
Carbon footprint of the end-of-life phase [c1 to c4] 1.32113936381709
Carbon footprint of the end-of-life phase [c1 to c4] 1 kg CO2 eq.
Pvc free Yes
Energy efficiency optimized False
F-gas free N/A
Take-back No
Product contributes to saved and avoided emissions No
Removable battery N/A
Total lifecycle carbon footprint 44.0335900079522
Average percentage of recycled metal content 0 %
Packaging made with recycled cardboard No
Packaging without single use plastic No
Pvc free Yes
End of life manual availability ENVEOLI2308033EN
Take-back No
Warranty (in months) 18

Documents & downloads

Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • Environmental Disclosure

  • End of Life Manual

  • Installation Instruction

  • Declaration of Conformity

  • Certificates (MSDS)

  • Declaration of Conformity (Sustainability)